Underground Cables
Electrical Power Transmission & Distribution
Dr. Furqan Asghar
1
1. Introduction
• Since the loads having the trend towards growing
density. This requires the better appearance,
rugged construction, greater service reliability and
increased safety. An underground cable essentially
consists of one or more conductors covered with
suitable insulation and surrounded by a protecting
cover. The interference from external disturbances
like storms, lightening, ice, trees etc. should be
reduced to achieve trouble free service. The
cables may be buried directly in the ground, or
may be installed in ducts buried in the ground.
2
Introduction
3
Advantages & Disadvantages
Advantages
– Better general appearance
– Less liable to damage through storms or lighting
– Low maintenance cost
– Less chances of faults
– Small voltage drops
Disadvantages
– The major drawback is that they have greater installation cost and
introduce insulation problems at high voltages compared with
equivalent overhead system
4
2. Construction of Cables
5
Construction of Cables
• Core or Conductor
A cable may have one or more than one core
depending upon the type of service for which it
is intended. The conductor could be of
aluminum or copper and is stranded in order to
provide flexibility to the cable
• Insulation
The core is provided with suitable thickness of
insulation, depending upon the voltage to be
withstood by the cable
The commonly used material for insulation are
impregnated paper, varnished cambric or rubber
mineral compound
6
Construction of Cables
• Metallic Sheath
A metallic sheath of lead or aluminum is provided
over the insulation to protect the cable from
moisture, gases or others damaging liquids
• Bedding
Bedding is provided to protect the metallic sheath
from corrosion and from mechanical damage due
to armoring. It is a fibrous material like jute or
hessian tape
7
Construction of Cables
• Armouring
Its purpose is to protect the cable from
mechanical injury while laying it or during the
course of handling. It consists of one or two
layers of galvanized steel wire or steel tape
• Serving
To protect armouring from atmospheric
conditions, a layer of fibrous material is provided
8
CABLE STRUCTURE
9
Properties of Insulating Material
High resistivity: to avoid leakage current
High dielectric strength: to avoid electric breakdown of cable
Low thermal co-efficient
Low water absorption
Low permittivity
Non – inflammable
Chemical stability: to avoid reaction with acid and alkaline, etc.
High mechanical strength: to withstand the mechanical handling
High viscosity at impregnation temperature
Capability to with stand high rupturing voltage
High tensile strength and plasticity
10
Properties of Insulating Material
11
Insulating Materials for Cables
• Rubber
It can be obtained from milky sap of tropical trees or from oil
products
It has the dielectric strength of 30 KV/mm
Insulation resistivity of 10^17 ohm.cm
Relative permittivity varying between 2 and 3
It readily absorbs moisture, soft and liable to damage due to rough
handling and ages when exposed to light
Maximum safe temperature is very low about 38 C
12
Insulating Materials for Cables
• Vulcanized India Rubber
It can be obtained from mixing pure rubber with mineral compounds i-e
zinc oxide, red lead and sulphur and heated upto 150 C
It has greater mechanical strength, durability and wear resistant property
The sulphur reacts quickly with copper; so tinned copper conductors are
used
It is suitable for low and moderate voltage cables
13
Insulating Materials for Cables
• Impregnated Paper
This material has superseded the rubber, consists of chemically pulped
paper impregnated with napthenic and paraffinic materials
It has low cost, low capacitance, high dielectric strength and high
insulation resistance
The only disadvantage in use of paper is hygroscopic, for this
reason
paper insulation is always provided protective covering
• Varnished Cambric
This is simply the cotton cloth impregnated and coated with
varnish
As the varnish cambric is also hygroscopic, so need some
protection
Its dielectric strength is about 4KV / mm and permittivity is 2.5 14
Insulating Materials for Cables
• Polyvinyl chloride (PVC)
This material has good dielectric strength, high insulation resistance and high
melting temperatures
These have not so good mechanical properties as those of rubber
It is inert to oxygen and almost inert to many alkalis and acids
• XLPE Cables (Cross Linked Poly-ethene)
This material has temperature range beyond 250 – 300 C
This material gives good insulating properties
It is light in weight, small overall dimensions, low dielectric constant and high
mechanical strength, low water absorption
These cables permit conductor temperature of 90 C and 250 C under normal
and short circuit conditions
These cables are suitable up to voltages of 33 KV
15
XLPE cable view
16
3. CLSSIFICATION OF CABLES
• Cables are classified based on type of insulation and
voltage for which they are made. However, the later
method of classification is preferred
• Low tension (L.T) ----- up to 1000V
• High tension (H.T) ----- up to 11, 000V
• Super tension (S.T) ---- from 22KV to 33KV
• Extra high tension (E.H.T) cables --- from 33KV to 66KV
• Extra super voltage cables ------beyond 132KV
17
Extra High Tension Cable
18
Low Tension Cable
19
3- Core Cables/3-Phase Cables
Belted Cables
In these cables, the conductors are wrapped with oil
impregnated paper, and then cores are assembled with filler
material. The assembly is enclosed by paper insulating belt
These can be used for voltages up to 11KV or in some cases
can be used up to 22KV
High voltages beyond 22KV, the tangential stresses becomes
an important consideration
As the insulation resistance of paper is quite small along the
layer, therefore tangential stress set up, hence, leakage current
along the layer of the paper insulation is faced
This leakage current causes local heating, resulting breaking
of insulation at any moment
20
3-core belted Cable
21
3- Core Cables/3-Phase Cables
Screened Cables
• These can be used up to 33kv but in certain
cases can be extended up to 66kv
• These are mainly of two types
• H-type
• S.L type cables
22
3- Core Cables/3-Phase Cables
H-TYPE Cables
• Designed by H. Hochstadter
• Each core is insulated by layer of impregnated paper
• The insulation on each core is covered with a metallic
screen which is usually of perforated aluminum foil
• The cores are laid in such a way that metallic screen
make contact with one another
• Basic advantage of H-TYPE is that the perforation in
the metallic screen assists in the complete impregnation
of the cable with the compound and thus the possibility
of air pockets or voids in the dielectric is eliminated
• The metallic screen increase the heat dissipation power
of the cable
23
3- Core Cables (H-Type)
24
3- Core Cables/3-Phase Cables
S.L - Type: (Separate Lead)
• Each core insulation is covered by its own lead
sheath
• It has two main advantages, firstly the separate
sheath minimize the possibility of core-to-core
breakdown. Secondly, the bending of cables
become easy due to the elimination of over all
sheath
• The disadvantage is that the lead sheaths of S.L
is much thinner as compared to H-Type cables,
therefore greater care is required in
manufacturing
25
3- Core Cables (S.L. Type)
26
3- Core Cables/3-Phase Cables
Pressurized Type Cables
• In these cables, pressure is
maintained above atmosphere either by oil or by
gas
• Gas pressure cables are used up to 275KV
• Oil filled cables are used up to 500KV
27
3- Core Cables/3-Phase Cables
Oil Filled Cables
• Low viscosity oil is kept under pressure and
fills the voids in oil impregnated paper under
all conditions of varying load
• There are three main types of oil filled cables
a. Self-contained circular type
b. Self-contained flat type
c. Pipe Type cables
28
3- Core Cables (Oil filled)
29
Advantages of Oil Filled
Cables
• Greater operating dielectric stresses
• Greater working temperature & current carrying
capacity
• Better impregnation
• Impregnation is possible after sheath
• No void formation
• Smaller size of cable due to reduced
dielectric thickness
• Defect can easily be detected by oil leakage
30
Gas Pressure Cables
In these cables, an inert gas like nitrogen is used to exert
pressure on paper dielectric to prevent void formation
These are also termed as Compression cables
They insulated cores similar to solid type
The cable is inserted in a pressure vessel which may be a
rigid steel pipe, commonly known as pipe line
compression cable
The nitrogen gas is filled in vessel at nominal pressure of
1.38*10^6 N/m2 with a maximum pressure of 1.725*10
^6 N/m2
31
Gas Pressure Cables
32
Gas Insulated Cables (GIC)
• In GIC cables, high pressure sulphur hexaflouride
(SF6) fills the small spaces in oil impregnated paper
insulation and suppresses the ionization.
• Most EHV and UHV lines insulated with sulphur
hexaflouride (SF6) gas are being used extensively for
voltages above 132 KV up to 1200 KV.
• These cables are very popular for short lengths, river
crossings and high way crossings.
33
Gas Insulated Cables (GIC)
34
Advantages of GIC
Gas Insulated Cables have several advantages
over oil filled cables such as;
• Efficient heat transfer, hence can carry more
current
• Low dielectric loss and low capacitance
• SF6 gas is non-toxic, chemically stable
and non-inflamable
• Terminations of GIC cables are simpler
and cheaper
35
4. Laying/Installation of Underground Cables
• The reliability of underground cable network
depends to a considerable extent upon
proper laying
• There are three main methods of Laying
underground cables
a. Direct Laying
b. Draw-in system
c. Solid system
36
Direct Laying
• This method is cheap and simple and is most
likely to be used in practice
• A trench of about 1.5 meters deep and 45 cm
wide is dug
• A cable used to be laid inside the trench and is
covered with concrete material or bricks in
order to protect it from mechanical injury
• This gives the best heat dissipating conditions
beneath the earth
• It is clean and safe method
37
Disadvantages of Direct Laying
• Localization of fault is
difficult
• It can be costlier in
congested areas where
excavation is expensive
and inconvenient
• The maintenance cost is
high
38
Draw-in System
• In this technique, duct of concrete is laid in ground
with main holes at suitable positions along the cable
route
• The cables are then pulled into positions from main
holes
39
Advantages/Disadvantages of Draw-in
System
• It has very high initial cost
• Heat dissipation conditions are not good
• This method is suitable for congested areas
where excavation is expensive and
inconvenient
• This is generally used for short lengths cable
route such as in workshops, road crossings
where frequent digging is costlier and
impossible
40
Solid System
• Inthis system, the cable is laid in open pipes
or troughs dug out in earth along the cable
route
• The troughing is of cast iron or treated wood
• Troughing is filled with a bituminous after cable
is laid
• It provides good mechanical strength
• It has poor heat dissipation conditions
• It requires skilled labour and favorable
weather conditions
• It is very much expensive system
41
Solid System
42
Solid System
43
5. Grading of Cables
• Since the stresses are maximum at surface of
the conductor or inner most part of the
dielectric, the stress goes on decreasing as
outer most layer is reached
• Since the process of achieving the uniform
electrostatic stresses on the dielectric of cables
is known as Grading of cables
44
Grading of Cables
• The un-equal distribution of stresses is
undesirable because;
• if dielectric is chosen according to maximum
stress, the thickness of cable increases or either
this may lead to breakdown of insulation.
• The following are the two main methods of
grading
• Capacitance grading
• Inter sheath grading
45
6. Types of Cable
• CablesFaults
are generally laid in the ground or in
ducts in the underground distribution system. For
this reason, there are little chances of faults in
underground cables. However, if a fault does
occur it is difficult to locate and repair the fault
because conductors are not visible.
Nevertheless, the following are the faults most
likely to occur in underground cables
• Open circuit fault
• Short Circuit Fault
• Earth Fault
46
Types of Cable Faults
• When there is a break in the conductor of a cable,
it is called open circuit fault
• The open circuit fault can be checked by megger.
For this purpose, the three conductors of the 3-
core cable at the far end are shorted and earthed
• The resistance between each conductor and earth
is measured by a megger and it will indicate zero
resistance in the circuit of the conductor that is
not broken
• However, if the conductor is broken, the megger
will indicate infinite resistance in the circuit
47
Types of Cable Faults
• When two conductors of a multi-core cable come
in electrical contact with each other due to
insulation failure, it is called a short circuit fault
• Again, we can seek the help of a megger to check
this fault
• For this purpose the two terminals of the megger
are connected to any two conductors
• If the megger gives zero reading, it indicates short
circuit fault between these conductors
• The same steps is repeated for other conductors
taking two a time
48
Types of Cable Faults
• When the conductor of a cable comes in
contact with earth, it is called earth fault or
ground fault
• To identify this fault, one terminal of the
megger is connected to the conductor and the
other terminal connected to earth
• If the megger indicates zero reading, it means
the conductor is earthed. The same procedure
is repeated for other conductors of the cable
49
7. Physical Limitations of Underground Lines
The main argument against constructing underground
systems is usually financial. But costs are not the only
limitation
The laws of physics limit how physically long a power
line can be.
These limits are relatively unimportant on overhead lines
But will severely limit high voltage underground cable
systems
The higher the voltage, the shorter the line
length must be.
The limiting effects become very important
at
transmission voltages, especially 100,000 Volts
and above.
Limiting effects may also be important for sub-50
transmission voltages; i.e. 69,000 Volts and 35,000
Physical Limitations: The Effect of Capacitance
• Capacitance causes current to flow even when no load is
connected to the cable. This is called “line charging
current”.
• Underground line capacitance for power cables is
far
higher than overhead line capacitance
o
Wires are closer to each other
o
Wires are closer to the earth (within a few inches)
o
Underground lines have 20-75 times the line
charging
current that an overhead line has (depending on
line voltage)
o
If a line is long enough, the charging current could
be
equal to the total amount of current the line can carry. 51
Summary of Costs:
Overhead vs.
• Underground
Transmission: Underground may be 4-20 times
Overhead.
• Sub transmission: Underground may be 4-20
times Overhead
• Distribution: Underground may be 2-10 times
Overhead
• New underground may be cheaper than overhead
in special conditions and costs vary greatly from
utility to utility and place to place.
52
THANKS
53