Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Protections
Basic Information & Recommendations
P ar t - I
Kamin Dave
Senior Application Engineer
DOBLE ENGINEERING COMPANY
Generator Protections
Stator Protections
Rotor Protections
Exciter Protections
Backup Protections
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Protections
Stator Protections:-
1. Generator differential Protection (87G)
2. Generator Split Phase differential Prot(50D)
3. Over Voltage Protection (59)
4. Over all Generator- Transformer differential
Protection (87GT)
5. 0 – 95% Stator E/F & 100% Stato r
E/ Protection (59N/27TN)
6. Protection against Stator winding
ov Heating & over loading (51O/L)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Protections
Rotor Protections:-
1. 1 s t & 2 n d Rotor E/F Protection (64F1/64F2)
2. Stator Unbalanced current Protection (NPS-4
3. Loss of Excitation Protection (LOF-40G)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Protections
Abnormal Operating Conditions:-
1. Reverse Power Protection (32R)
2. Low forward Power Protection (37L/32L))
3. Under Frequency Protection (81U/F)
4. Over Frequency Protection (81O/F)
5. Out of Step or Pole-Slip Protection (78)
6. Generator Over Speeding Protection
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Protections
Other Miscellaneous Protections:-
1. Generator – Transformer Over fluxing
Protection (24)
2. Restricted E/F Protection if it
required
3. Back up Impedance Protection or Back up
Protection using Voltage Dependent (Voltage
restrain / Voltage controlled) over current
unit (21/51V)
4. Breaker Flash over Protection
5. Voltage Balance Scheme
Knowledge Is Power(LOP-60) SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection s c h e m e s a r e recommended fo
Generator Prot based on Size:-
PROTECTION ANSI SMALL MEDIUM LARGE REMARKS
CODE (Up to 10MW) (Up to 10MW) (Above 10MW)
Stator Over heat 51 O/L Yes Yes Yes Only for alarm
Voltage 51V Yes Yes Yes
dependent
O/C
Under Impedance 21 - Optional either Yes Required above
or Back up 21 or 51V 50MW & GT
unit
Impedance
Over voltage or 59 or 24 (99) - Yes Yes
Over fluxing
Under Voltage 27 - Yes Yes Only for alarm
Over frequency 81O - Yes Yes
Under frequency 81U Yes Yes Yes
Generator 87G Yes Yes Yes Less than 1MW
differential optional
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection s c h e m e s a r e recommended fo
Generator Prot based on Size:-
Generator- 87GT - Yes Yes
Transformer
combined
differential
Negative Phase 46 - Yes Yes
sequence
Restricted earth 64R Optional either - -
fault 87G or 64R
Stator E/F 0-95% 51N & 27N & Yes Yes Yes
& 100% 59GN
Rotor E/F-1st & 2nd 64F1 & 64F2 - Yes Yes Stage-1 for alarm
& Stage-2
for Trip
Reverse Power 32 Yes Yes Yes
Low forward 37 - Yes Yes
Power
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection s c h e m e s a r e recommended fo
Generator Prot based on Size:-
Field failure 40 - Yes Yes
Pole slipping 78 - - Yes Above 50MW
single unit
Over speed 12 Yes Yes Yes
Turn to Turn 50/51 - - Yes Above 250MW
fault in single unit
stator
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection s c h e m e s a r e recommended fo
Generator Prot based on Size:-
ROTOR AND BEARING PROTECTION:
PROTECTION ANSI CODE SMALL (UP MEDIUM (UP LARGE REMARKS
TO 1MW) TO 10MW) (ABOVE
10MW)
Vibration Indicator - Yes Yes Yes
Bearing 26 or 38 Yes Yes Yes
temperature &
alarm trip
Bearing Insulation 26 or 38 Yes Yes Yes
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection s c h e m e s a r e recommended fo
Generator Prot based on Size:-
REQUIRED ALARMS:
ABNORMAL AIR COOLED HYDROGEN REMARKS
CONDITION COOLED
Bearing Oil pressure Yes Yes
low
Bearing temperature Yes Yes
high
Stator winding Yes Yes
temperature high
Lubricating oil Yes Yes Sp. For diesel
temperature low generator
Governor oil pressure Yes Yes Sp. For STG
low
Cooling water inlet Yes Yes
pressure low
Battery voltage low Yes Yes Sp. For battery
starting
engine
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Tripping Criteria:
Class-A Tripping:
Turbine Trip + GCB Trip + Field Breaker
Trip
Class-B Tripping:
Turbine & Boiler Trip
Class-C Tripping:
GCB Trip only or GCB & FB Trip
GCB = Generator Circuit Breaker
FB = Field Breaker
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Tripping Criteria
TRIP TYPE: TT GCB FB
DIFFRENTIAL
STATOR EARTH
ROTOR EARTH
OVERVOLTAGE
OVERCURRENT
UNBALANCE
UNDERFREQUENCY
Knowledge Is Power SM
Apparatus Maintenance and Power Management
ACA - PROT - 2 / 45 for Energy Delivery
Tripping Criteria
TRIP T YPE TT GCB FB
UNDEREXCITATION
W/ O LOSS OF
FIELD
WITH LOSS OF
FIELD
REVERSE POWER
SHORT TIME (STAGE-2)
LONG TIME (STAGE-1)
(OPERAT ES AT TT)
ONLY
Knowledge Is Power SM
Apparatus Maintenance and Power Management
ACA - PROT - 3 / 45 for Energy Delivery
Technical Specification: Generator
588 MVA, 16.2 kA, 21 0.85 PF
kV, : 3.5 bar
Hydrogen gas pressure
Excitation : 340 V, 4040 A
Critical s p e e ds : 864, 1806
(exciter), 2388 rpm
Short ratio : 0.52
circuit re actance Xd” : 7.2
Sub-transient
Negative Sequence % reactance(X G 2 ) :
8%
Transient reactance : 24.1 %
Xd’ : 231 % (1/0.52)
Synchronous reactance Xd
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: Generator
Zero Sequence Reactance (X0) : 13%
Time (Td”) short circuit : 0.032s
Time (Td’) short circuit : 0.75s
Short Circuit Ratio (SCR) : 0.52
Capacitance between Stator Winding & Ground : 0.385 microF
Surge Capacitance bet n St e p- up Tr & GCB : 0.25 microF/Phase
Capacitance bew n TR winding & Ground : 0.2 microF/Phase
NB:
Sub-transient reactance Xd” is use d for Breaker rating calculations.
Transient reactance Xd’ is used for O/C & E/F relay co-ordination &
motor starting studies.
Higher SCR, lower the reactance, higher the machine size & higher the
cost. Lower the SCR, higher the reactance, low the machine size &
low the cost
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: Generator
Unity PF lag 433 MVA
Unity capability: PF 250 MVA
Total lead losses 6920 kW;
capability:up:
Break
• Iron: 600kW;
• Short circuit: 2800kW
• Excitation: 1390kW; Windage:
1680kW
• Bearing and shaft seals: 450
kW
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
T echnical Specification: PMG-Pilot
Exciter
Low excitation p o w e r- 4 0 0 HZ permanent magnet
generator is provided a s pilot exciter with
brushless exciters.
The PMG ELP 5 0 / 4 2 - 3 0 / 1 6 is rated : 65
KVA, 220 V, 3 Ph, 91 A and 158 A for field forcing.
Frame has laminated core with 3ph wdg. Rotor has
mounted poles. Permanent magnets a r e screwed to
poles.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: Brushless
Exciter for 5 0 0 MW- B E 7 0 /9 0 -3 0 /6 -
20
Rating: 3840 kW, 6300 A, 600
V10 seconds
Current & voltage: 7050
output: 8600 A, 820 V.
Nominal current : 4030 Amp.
kW
Response ratio: >2
60 diodes p e r wheel (20 p e r arm )
Current pe r diode: 67 A,
with 6 out of 20 diodes failed:and 96 A
Armature dia: 70 cm; Length 90
cm
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification : Generator Capability Curve
450 0.4 0.7
400 MAX 0.85
RATED
LAG 300 0.9
200 0.95
100
MVAR
100 200 300 400 500 1.0
0
MW 588
100
LEAD
0.95
200
250 Knowledge Is Power SM
0.85 P.F
. ARON Apparatus Maintenance and Power Management
07 31 for Energy Delivery
Technical Specification: 500MW
Generator Efficiency
99
% 98.5
98
97.5
97
0 25% 50% 75%
100%
LOAD IN MW : % FULL LOAD
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: Generator
Flux density stator & rotor : 2 - 2.5
Tesla
H2 coolers heat load : 4424 kW
Continuous unbalanced load :8%
Short time negative sequence I 2 t : 10s
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Unbalanced Load – Time Curve
10
6
2
1
I2 t = 10 s e c
I2
PU
0.1
0.08
t in Seconds
0.03
0.3 1 10 100 100
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Over Current Limit: 3 - P h a s e
Balanced Load
2.2 Stator O/C Curve of 500MW
I
Machine
2.0
PU
1.8
1.6
1.4
1.2
10 20 40 100 200
Knowledge Is Power
60
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Over Current Limit: 3 - P h a s e
Balanced Load
Stator O/C Curve Limit a s per
ANSI C50.13-1989
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
PERMISSIBLE LOADING
RATED MVA min: 1 2 5 10
+5%
SHORT TIME
RATED MVA
-10% -5% 0 +5%
FREQ. DEVIATION VOL
2
CONTINUOUS
1
3 RATED MVA - 5%
%MVA 90 95 97 100 -5% SPEED
PF=RATED +3%
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Generator Data for Relay Setup
IRating = 16200 Ampere
CTR = 20000/5A
IRating on secondary = (IRating)/ (CTR)
= (16200) / (4000)
= 4.05A
VRated = 21000V
PTR = 21/0.110kV
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Generator Data for Relay Setup
VRating on secondary = (VRating)/ (PTR)
= (21000) / (190.90)
= 110V (L-L)
VRating on secondary = (VRating)/ (PTR*1.7325)
= (21000) / (190.90*1.7325)
= 63.5V (L-N)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Connection: P T Input “Line to Line
Voltage”
VL-L = 21000V
VNOMINAL = 110VL-L
VAB
VBC
Relay
VCA
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Connection: P T Input “Line to Line
Voltage”
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Connection: P T Input “Line to
Ground Volatge-3 wire”
VL-L = 21000V
VNOMINAL = 110VL-L
VAB
VBC
Relay
VCA
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Connection: P T Input “Line to
Ground Voltage”
VL-L = 21000V
VL-N = 2 1000V/1.7325
VNOMINAL = 63.5VL-N
VAN
VBN
Relay
VCN
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Connection: P T Input “Line to
Ground Voltage”
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overheating Protection
(51O/L)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overheating Protection (51O/L)
Causes:
Over Loading of Generator
Stator Over Current
Short-circuited laminations
Failure of core bolt insulation
Failure of Ventilation
Coolant circuit failure
Setting Criteria: Based on Generator O/L
Curve (Say: 115% for 30s)
RTD or PT100 is required to s e n s e over
temp.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overheating Protection (51O/L)
What is the difference between Stator
Over Load & Over Current???
Stator Over Load:
Power Output of Machine (KVA or KW)
e x c e e d s it’s maximum continuous over
load power limit
PMAX(KW) = 1.7325*V L-L *I LOAD *COS (Ang)
Machine voltage is not much reduce during
over load condition (i.e. 8 5 - 9 5 % of V R a t e d )
Phenomenon is much harmful for Prime
over (i.e. Turbine/Engine)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overheating Protection (51O/L)
What is the difference between Stator
Over Load & Over Current???
Stator Over Current:
Stator current e x c e e d s it’s maximum limit
during faults
Machine voltage collapse & reduced below
30% (Depends on Faults & Location)
PMAX(KW) = 1.7325*V L-L *I LOAD *COS (Ang)
Phenomenon is much harmful for Stator
winding (Slide22 shows; ANSI limit)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overheating Protection (51O/L)
+VE 2.5s – 25s
-VE
51O/L-Timer
51O/L-1
R
3 R 51O/L 51O/L-Timer-1
75-200%
Annunciation ckt.
DC Circuit
G
Power Circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overvoltage Protection
(59)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Over Voltage Protection (59)
Causes:
Transient Over Voltages
• Surge Voltages mainly originate in
Transmission System because of
Lightning Strokes
Power Frequency Over Voltages
• Defective operation of AVR
• Sudden Load thrown off
Protection is normally offered by other
relays like over fluxing relay
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Over Voltage Protection (59)
Setting Criteria: Based on Generator Open
circuit voltage characteristic Curve.
Normally, Inverse Characteristic element is
used for S t a g e - 1 for Alarm/Trip (Say: 105%
to 110% of Un for 45s to 50s)
Definite Time element is used for S t a g e - 2
for Tripping (115% to 125% for 500ms to
3000ms). S t a g e - 2 must e s e t below the
maximum stator voltage possible, taking in to
account magnetic core saturation.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Over Voltage Protection (59)
Advisable to provide surge diverters
for TG also - to b e connected
between p h a se s & earth. Design value
(1.2 - 1.4)*Un allows 50 Hz over
voltage on load rejections.
Surge diverters to b e explosion proof
or other constructional m ea sure s
be taken to avoid danger to
person s or near by
components in c a s e of over
voltages. Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator- Transformer
Overfluxing Protection (24)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator- Transformer Over Fluxing
Protection (24)
Causes:
Generator Regulator Problem
• AVR or Voltage Regulator Fails
• Operating Error during off line manual
regulator operation
• Loss of VT supply of AVR
System Problem
• Unit Load Rejection: Full Load or –
Partial Load
• Power System Islanding during Major
disturbances in Grid
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator- Transformer Over Fluxing
Protection (24)
Fundamental Voltage & Flux relation:
= N*Flux*Frequency
E AVE
But, Foam Factor (E RMS /EAVE ) is 1.11;
= 1.11*N*Flux*Frequency
ERMS
Flux = (ERMS ) / (1.11*N*Frequency)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator- Transformer Over Fluxing
Protection (24)
Flux = (VN / F N ) - - - € (Volts/Hz)
Flux increases when System voltage rises
at Rated Frequency
Flux increases when System Frequency
fall at Rated Voltage
Saturation of Magnetic Core of the GT due to
ex ceed ed the V/Hz ratios
Serious Over heating will occur in bolts &
support structure of machine which destroys
their own insulation a s well a s coil insulation
if the phenomenon persist for longer duration
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator- Transformer Over Fluxing
Protection (24)
Specific Over Fluxing Protection is not
Mandatory & It is generally offered
a s an optional by other Protection
like Over Voltage. Protection should
be in circuit whenever field CB is
closed
IEEE C50.13 Generator should
continuous withstand 105% of rated
excitation at full load
Normally Inverse & DMT type relays
Knowledge Is Power
a r e used for application SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator- Transformer Over Fluxing
Protection (24)
Setting Criteria: Based on Generator
V/Hz with stand capability Curve (Say:
1.05 V/Hz or 1.1 V/Hz of Un/Fn)
Normally, Inverse Characteristic
element is used for S t a g e - 1 (1.05 to
1.1 V/Hz for Alarm/Trip for 4 5 - 5 0 s )
Definite Time element is used for
S t a g e - 2 for Tripping (1.15 to 1.25
V/Hz for 2 s - 6s)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator- Transformer Over Fluxing
Protection (24)
Setting Criteria for Inverse Time Over Fluxing relay
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency
Protection (81)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency Protection (81)
Causes:
Demand of Active Power suddenly Increases in
Power Grid
Islanded system, inadequate input quantity and
quality of fuel (i.e. Problem occur in Steam valve
in Steam Turbine or Fuel Pump in Diesel
Engine/Gas Engine etc.)
Islanded system, Two or more Machines a r e
running in parallel on more than 70% load &
outage of machine due to machine fault, increases
load on another machine to create under freq. on
running machine
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency Protection (81)
It’s a Prime-mover Protection. Each
turbine is having critical speed.
Operation of machine at a sp e e d which
is close to critical s p e e d would
causes excessive vibration in
Primemover & also it produces
mechanical s t r e s s in turbine blades
Prolonged operation at under
frequency would result in to damage
of Primemover
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency Protection (81)
As per IEC, BS and ANSI standards,
limits of voltage & frequency variation
within which the generator can operate
at full load without exceeding
specified temperature by more than
10 d e g r e e
A typical example of Under freq
withstanding capability of ABB
generator a s shown below slide;
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency Protection (81
Frequenc Rated P.F.=1.0, P.F.=0.8, No Load
y in % Voltage
P = PN P = PN P =0
100% 100% Cont. Cont. Cont.
96% 100% Cont. Cont. Cont.
95% 100% Cont. 30Min. Cont.
92.5% 100% 30Min. 2 Min. Cont.
90% 100% 2 Min. - Cont.
87.5% 100% - - 30Min.
85% 100% - - 2 Min.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency Protection (81
Setting Criteria: Based on Generator
Permissible Loading Curve (Say: 48.5Hz for
50Hz)
Normally, S t a g e - 1 is the delayed tripping
(Say: 48.5Hz for 3 s - 1 0 s )
S t a g e - 2 element is also delayed but
operating is lesser than S t a g e - 1 element
(Say: 48Hz for 0.5s - 5s)
Operation at Frequency below 47.5Hz
allowed only for 2 - h o u r s in entire life of s e t
(Turbine)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Over Frequency
Protection (81)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Over Frequency Protection (81)
Causes:
Full or Partial Load Rejection (Load
thrown off)
Overshedding of Load during a major
system disturbance
Condition is not a serious problem since
control system or operator action can be
used to quickly rest ore generator s p eed but,
if it is not then Machine may pull out of step
condition & it is required to trip on over
freq protection
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Over Frequency Protection (81)
Setting Criteria: Based on Transient
Stability (Say: 50.5Hz for 50Hz)
Normally, S t a g e - 1 is the delayed
tripping (Say: 50.5Hz for 3 s -
10s)
S t a g e - 2 element is also delayed
but operating is le s s e r than S t a g e -
1 element (Say: 51Hz for 0.5s -
5s)
Operation at Frequency above 51.5Hz
allowed only for 2 -
Knowledge Is Power
h o u r s in entire
life of s e t (Turbine)
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under/Over Frequency Protectio
(81)
+VE 0.5s – 5s
-VE
2/81-Timer
52 81G-1
T
0.5s – 5s
2/81-Timer
81G-2
T
Reverse active clutch & Time Motor
86F-2 81G-2
TM
DC Circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under/Over Frequency Protectio
(81)
+VE -VE
86F
TM-1 2/81-1 86F-2
R
86F-3
Annunciation ckt.
86F-1
Trip ckt.
DC Circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection
(32R)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
MVAR MW
F Machine < F System G D Y
MVAR
-MW MW
Relay setting Threshold
-MVAR
Machine Act a s a Synchronous Motor
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
MVAR MW
V Machine < V System
G D Y
F Machine < F System
MVAR
-MW MW
Relay setting Threshold
-MVAR
Machine Act a s a Induction Motor
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
Causes:
Two or more machines a r e running in
parallel & Prime-mover of one of
the machine fails. Turbine has
Problems; exhaust hood temperature
on steam turbines
Sometimes the condition appear during
synchronization of machine, if incoming
machine frequency is lesser than bus
frequency
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
Protection against the motoring action of the
generator while the generator looses it’s
Prime-mover input
Protection is applied for Prime-mover
Normally, Protection is applied only when
machines a r e operating in parallel with each
other a s well a s Power Grid
Generator unaffected by r e v e r s e power, but
act a s a Synchronous Motor (Exporting
Reactive Power & Importing Active Power)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
Effect:
Steam Turbine:-
• Steam turbine tends to overheat, when steam
supply is cut off and the turbine still rotates a s
the generator runs a s motor. Steam turbine,
ac a s a pump and the steam is trapped. Th e
turbulence losses in the trapped steam may
then built up a high temperature in l o w -
pr e s s ur e stage. Hence, the turbine blades a r e
overheated due to windage or air friction.
However, the heat caused by turbulence of the
trapped steam can d e - t e m p e r turbine runner.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
Effect:
Hydro Turbine:-
• In c a s e of hydro turbine, the flow of water
starts reducing or complete cut off and hence
bubbles a r e formed causing cavitations in
the turbine resulting to damage turbine
runner.
Diesel Engine:-
• In c a s e of diesel driven set, loss of motive
power is likely to be cause by some
mechanical failure, such a s bearing over
heating leading to closure of fuel valves, and
continued running is likely to cause several
damages in engine.Is Power
Knowledge SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R): Allowable
limit
Prime Mover Allowable limit of %P of
Reverse Powe r
Diesel (Two c y c l e - 2 25% of rated power
stroke) stroke)
Diesel (Four c y c l e - 4 15% of rated power
Gas turbine (Single shaft) 100% of rated power
Gas turbine (Double shaft) 10% to 15% of rated power
Steam turbine 0.5% to 7.5% of rated power
Hydro turbine 1% to 3% of rated power
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
Sequential Tripping:
Used on Steam Turbine Generator to Prevent
Overspeed
This trip mode only used for boiler/reactor or
turbine mechanical problems
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
Sequential Tripping:
Step 1:
• Abnormal Turbine/Boiler/Reactor condition is
detected
Step 2:
• Turbine Valves closed; Generator allowed to
briefly “Motor” (i.e. Importing Active Power
from Grid)
Step 3:
• A Reverse Power relay in Series with Turbine
Valves position switches confirms all Valves
have closed
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
Sequential Tripping:
Step 4:
• Generator is required to Isolate from Power
System
G D Y
MW
GCB
MVARs
Consider
• Export High MVARs
• Import Low MW
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
Sequential Tripping Logic:
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
Setting Criteria: As the overheating of the
turbine blade does not occur
instantaneously while the generator starts
motoring, so it is not required to trip
instantaneously.
Set Point 1:
• -P<0.5% for Steam Turbine Generator
• Operating Time 10s
Set Point 2:
• -P<0.5% for Steam Turbine Generator
• Operating Time 2 s
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Low Forward Power
Protection (37L)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Low Forward Power Protection (37L)
MVAR MW
G D Y
MVAR
-MW MW
Relay setting Threshold
-MVAR
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential
Protection (87G)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
Protection Against Internal Faults in Machine
Operating Criteria: Differential protection
relay operate when the current at two ends
of feeder differ or mismatch by more than
threshold value of relay (I diff >I diffset )
NGR CT1 CT 2
G Y D
GCB
E I1 F1 I2
R
Idiff = (I1 – I2)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
Protection Against Internal Faults
I1 I2
NGR CT1 CT 2
G1 D Y
3
3
GCB
E F1
I1 I1 I2
R
I2 Idiff = I1+I2
NGR
G2 D Y
GCB
E
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
Protection Against Internal Faults
I1 L
NGR CT1 CT 2
G1 Y D
O
3
3
A
GCB
F1
D
E
I1 I1 R
Idiff = I1
Note: I2 is very less compared to I1 so it will b e neglected
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
Stable for External Faults
I1 I2
NGR CT1 CT 2
G1 D Y
3
3
GCB
I2 F2
E
I2
I1
R
I1 Idiff = I1+I2 = 0
NGR
G2 D Y
GCB
E
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
Mainly Two Ty p e s of Differential
Schemes;
High Impedance Differential Protection
Schemes
Low Impedance Differential Protection
Schemes
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G): High Impedance Scheme
3 3 3
3 3 3
G
Pickup Setting:
5%-25% of
R Y B
IFLC
Metrosil &
Stabilizing Resistor
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G): High Impedance Scheme
Distorted CT output &
Low resistance Path
Stabilizing resistor provide stability: Negligible
Current flows through relay coil
External fault & one of the CT Saturated
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
High Impedance Differential Scheme;
Simple & Low cost Scheme
Only Pickup setting & Easy to s e t it
Stabilizing resister Increases stability of relay
against high through fault current
Operating on current balance principal
Non-linear resistor or Metrosil is required for surge
voltage absorb during internal & through fault
condition
Special PS class CTs (With low turn ratio errors) of
identical ratio & ratings required for scheme
CAG34, MFAC34, MCAG34, etc. relays a r e used a s
high impedance differential relays.
Much suitable for Generator/Motor
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
Essential Requirement for High Impedance
Differential Scheme are;
Equal CT Ratio
Low CT secondary winding resistance
Adequate knee-point voltage output from CTs
Low lead burdens
Harmonic Settings a r e not available, so
scheme is difficult to applied for
Transformer
T h r e e Winding differential protection scheme
become a more complex than low impedance
scheme
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G): High Impedance Scheme
Setting Criteria: Typical Recommended
setting is 10% or 20%
Relay Operating Time should be less
than 50ms.
Ensure through fault stability by
adjusting proper value of stabilizing
resistor
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
Low Impedance Differential Scheme;
Complex & Higher cost Scheme compared to High
impedance scheme
Settings a r e more complex & %Slope Characteristics
settings a r e differ from manufacturer ’s to manufacturer ’s
T h e scheme is also called a s a percentage differential
scheme
For External f a u l t s - - - - - € High restraint current
For internal f a u l t s - - - - - € Low restraint current
High sensitivity during internal faults
Chance of mal-operation of relay during high through fault
current
7UT62/MICOMP632/DUOBIAS/SPAD346 etc. relays ar e
used a s low impedance differential relays
Much suitable for Transformer
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
Low Impedance Differential Scheme;
Normally, Single Slope Characteristic is sufficient
if the Protection is applied for Generator/Motor
because both the CTs a r e on same voltage level,
s o we can minimize %CT e r r or during an external
fault
Dual Slope Characteristic is required if the
Protection is applied for Transformer
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection (87G)
Low Impedance Differential Protection in MICOM P345 Rela
Slope is not start from origin & depends on “IS2”
setting. Turn point for slope is e a s y to s e t
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection (87G)
Low Impedance Differential Protection in 7UM62 Relay
IBias = I1 + I2
First slope is always starts from origin & 2 n d slope is depends on
Base Point2 setting. Turn point for 2 n d slope is s e t in following way;
For example; Base point2 = 2.5A then 2 n d slope starts after 5A
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection (87G)
Low Impedance Differential Protection in REG316 Relay
Slope is starts from origin & cut of point is depends on
“b” setting
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Phase Sequence
Protection (46)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Unbalance phase currents create Negative
Sequence current in Generator Stator
Negative Sequence current interacts with
normal positive sequence current to induce
a double freq. (120Hz) current in Rotor
winding & it causes surface heating
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Generator withstand capacity;
2
I2 t =K
Where;
K = Constant (Large Generator has smaller
“K” value) & It’s differ Manufacturer ’s to
Manufacturer’s
I2 = Negative Sequence current
Table-I shows unbalance withstand capacity
of machine a s per ANSI C50.13-1989
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Ty p e of Generator Permissible NPS current
(I2) Pe r c e nt a ge of
stator winding
Salient Pole
With connected amortisseur windings 10
Without connected amortisseur 5
windings
Cylindrical Rotor
Indirectly Cooled 10
Directly Cooled to 960MVA 8
961 to 1200 MVA 6
1201 to 1500 MVA 5
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
2
Ty p e of Generator Permissible I 2
t
Salient Pole Generator 40
Synchronous Condenser 30
Cylindrical Rotor Generators
Indirectly Cooled 30
Directly Cooled up to 800MVA 10
Directly Cooled (801 to 1600 MVA) S e e curve in
Slide 82
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Adjust Definite Time Tmax & Tmin
in relay shown in below slides
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Tmin is
the Generator Withstand Curve
Definite
Time
Relay Characteristic Inverse
to be s e t below
Generator Cont.
Withstand capacity
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Tmax (Definite Time)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Back up Protection: Relay Operation
reqd. to co-ordinate for HV fault a s
well a s Auxiliaries
500MVA/21KV GT
F1
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Xd” = 7.2%
XG2 = 8%
XT = 9.5%
I1 = I2 = 100 / (Xd” + XG2 + 2XT)
I1 = I2 = 100 / (7.2 + 8 + 2*9.5)
I1 = I2 = 2.92 P.U.
Relay operating time is required to co-ordinate
on HV faults.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection
(40)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
Loss of Excitation Magnetic Coupling
between Stator MMF & Rotor Field
Lost
Prime Mover still driving unit
Large slip frequency current induced in
rotor
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
Basic Diagram
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
Basic Diagram of Brushless Excitation
Auto Manual
BALANCING
R Y M GEN VOLT INSTMT.
SET POINT
B DV M SET
VT MEASURING POIN
CIRCUIT GEN VOLT
COMPENSATE CONTROLLER CONTROLER
CT FOLLOW UP
CONTROL
G GATE GATE
CONTROL CONTROL
DE-EXCITN AUTO-
MANUAL
CONTROL SELECTO
R
EXC
THYR.
PMG
KnFowBledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
Basic Diagram of 210MW Static Exciter
RECTIFIER TRANSFORMER
2500 KVA 15.75 KV/575V
DYN 5
TY1
AVR ~
TY2
AUTO=
FCB CEX
TY3
3000 1200V ~
COIL 220V MANU
= TY4
DC
3000A
G
NO LOAD 917A, 95
FULL LOAD V
5 KVA 415 / 2500A, 300 V
35V
220 V Knowledge Is Power SM
Apparatus Maintenance and Power Management
BATTERY for Energy Delivery
Loss Of Excitation Protection (40)
How Excitation System Works???
Start
Output Terminal Voltage (VG ) of Machine Detected
Reactive Current (IQ) of Machine Detected
Reference Voltage (VGREF ) of Output Terminal of Machine is
Set according to Reactive Current (IQ), Reference Voltage VHREF
Of High Voltage side of Transformer & Transfer function F H of
Phase Compensation
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
How Excitation System Works???
Output Terminal Voltage (VG) is subtracted from reference
VGREF of output terminal of Machine
A timing signal is produced according to difference signal
Output from subtracting unit
Field Current is supplied to Field Winding according to
Timing signal
End
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
How Excitation Fails???
If it Open!!!
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
How Excitation Fails???
If it Fails!!!
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
How Excitation Fails???
If it Fails!!!
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
How Excitation Fails???
If it Shorts or Open!!!
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Causes:
Field Open Circuit (Field current is zero)
Field Short Circuit (Field current is too high)
AVR Control Failure
Accidental Tripping of field breaker
Momentary; It will Import Reactive & Real
Power (Motoring Action)
After Motoring Action; Importing Reactive
Power & Exporting Real Power
Synchronous Generator Becomes Induction
Generator
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G)
MVAR MVAR
G D Y
MW
-MW MW
-MVAR
Machine Act an Induction
Generator Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G)
MVAR MVAR
G D Y
MW
-MW MW
-MVAR
Machine Act an Induction Motor
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Slip Induced Eddy Currents Heat Rotor
Surface
System Voltage Collapse due to Reactive
Power demand Increasing in Power System
Reactive power is drawn from grid
proportional to short circuit ratio. Power
factor is low, end zone heating increases.
Partial loss of excitation may cause
pole slipping-highly detrimental to the
machine.
During failure of field, field suppression
shall be cut off from circuit and active
load d ecr eased to 60% rated within 30
s e c and to 40% in next 1.5 minutes.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
T HW - 2 10 can operat e a t 40% rate d load for
a total period of 15 minutes.
there after.
Set to be tripped
Excitation to be removed when speed is 2000 rpm,
to rotor overheating.
prevent more s e v e r e for Steam Turbine
Problem
Problem less s e v e r e for hydro turbine (Salient Pole)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
How to s e t Relay????
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Rotor Limit
Over Excited
Stator Limit
PF=0.85
Under Excited
Generator Capability Curve
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Generator Capability Curve
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
X Rotor Limit
Over Excited
Stator Limit
PF=0.85
Under Excited
-R R
-X Z=
(KV 2 /MVA)*(CTR/PTR)
Generator Capability Curve: R-X Plot
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Generator Capability Curve
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Initially it’s a Motoring Stator Limit
Action when excitation fails
Xd
Rotor Limit
Gene
rator
Capa
Loss Of Excitation Protection (40)
After Motoring Action Stator Limit
Machine start to work a s
An Induction Generator
Xd
Rotor Limit
Gene
rator
Capa
Loss Of Excitation Protection (40)
Z PU = (MVA Base *Z Ohms )/(KV Base )
2
Z Ohms =
((KV Base 2 )*(Z PU )/(MVA Base )
Xd’Ohms = (21) 2 *(0.241)/(588)
Xd’Ohms = 0.18075 Oh ms - €
Primary side
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Xd’Ohms = 0.18075*(CTR/PTR)
Xd’Ohms = 0.18075*(4000/190.90)
Xd’Ohms = 3.7871 Oh ms - € Secondary side
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Z PU = (MVA Base *Z Ohms )/(KV Base )
2
Z Ohms =
((KV Base 2 )*(Z PU )/(MVA Base )
Xd O h m s = (21) 2 *(2.31)/(588)
Xd O h m s = 1.7325 Ohms
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Xd O h m s = 1.7325*(CTR/PTR)
Xd O h m s = 1.7325*(4000/190.90)
Xd O h m s = 36.3 Oh ms - € Secondary side
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Offset Setting;
(Xd’Ohms )/2= 1.893 Oh ms - € Secondary side
Circle Diameter Setting;
Xd O h m s = 36.3 Oh ms - € Secondary side
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Modern Numerical Relay have Dual
Characteristics
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Machine Operating
Limit in Leading PF
Zone 2 setting c r o s s e s
Steady s t a t e Stability
Limit
Setting Criteria: 1 for Dual Characteristics
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
OFFSET Setting:
Z PU = (MVA Base *Z Ohms )/(KV Base )
2
Z Ohms =
((KV Base 2 )*(Z PU )/(MVA Base )
Xd’Ohms = (21) 2 *(0.241)/(588)
Xd’Ohms = 0.18075 Oh ms - €
Knowledge Is Power SM
Primary side Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
OFFSET Setting:
Xd’Ohms = 0.18075*(CTR/PTR)
Xd’Ohms = 0.18075*(4000/190.90)
Xd’Ohms = 3.7871 Oh ms - € Secondary side
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
ZONE 1 Setting:
Z PU = (MVA Base *Z Ohms )/(KV Base )
2
Z Ohms =
((KV Base 2 )*(Z PU )/(MVA Base )
Xd O h m s = (21) 2 *(1)/(588)
Xd O h m s = 0.75Knowledge
Ohms Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
ZONE 1 Setting:
Xd O h m s = 1.7325*(CTR/PTR)
Xd O h m s = 1.7325*(4000/190.90)
Xd O h m s = 7.857 Oh ms - € Secondary side
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
ZONE 2 Setting:
Z PU = (MVA Base *Z Ohms )/(KV Base )
2
Z Ohms =
((KV Base 2 )*(Z PU )/(MVA Base )
Xd O h m s = (21) 2 *(2.31)/(588)
Xd O h m s = 1.7325 Ohms
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
ZONE 2 Setting:
Xd O h m s = 1.7325*(CTR/PTR)
Xd O h m s = 1.7325*(4000/190.90)
Xd O h m s = 36.3 Oh ms - € Secondary side
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Offset Setting;
(Xd’Ohms )/2= 1.893 Oh ms - € Secondary side
Circle Diameter Setting;
ZONE 1
Xd O h m s = 7.857 Oh ms - € Secondary side
ZONE 2
Xd O h m s = 36.3 Oh ms - € Secondary side
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Setting Criteria: 2 for Dual Characteristics
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40):
MICOM P345 Relay
Setting Criteria: 2 for Dual Characteristics
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
0 - 9 5 % Stator Ground Fault
Protection (59GN)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN)
It provides a protection for stator ground
faults on generator which a r e high
impedance grounded (NGT through NGR or
NGR etc.)
Protection function normally applicable for
unit connected generators
Ground current can be limited up to about 3A
to 25A on primary side
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
IF
VLN = 21000/1.7325
IF PTR = 21000/240V
100 Ohms, 10s
CTR = 20/1A
Maximum Ground Fault Amps = (Line to Neutral Voltage)
-----------------------
(NGR Resistance)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
IF VLN = 21000/1.7325
a
PTR = 21000/240V
100 Ohms, 10s CTR = 20/1A
Ground Fault Amps at fault location = (Maximum Ground Fault
current * %A)/100
Where; %A = (100 – Fault at location of stator winding)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
VLN = 21000/1.7325
PTR = 21000/240V
100 Ohms, 10s
CTR = 20/1A
Maximum Ground Fault Volts = (Line to Neutral Voltage*PT seco n d ary volts)
-------------------------------------
(PT Primary Volts)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
VLN = 21000/1.7325
PTR = 21000/240V
100 Ohms, 10s
CTR = 20/1A
Ground Fault Volts = (Ground fault Amps*PT secondary volts*NGR Resistance)
---------------------------------------------
(PT Primary Volts)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Appendix:
PTR = 21000/240V
NGR Value = 100 Ohms
59GN Relay Range = 5.4V to 20V
Maximum Ground Fault Amps = (Line to Neutral Voltage)
-----------------------
(NGR Resistance)
= (12121.21)
I F-Max
------------------
-------
100
I F-Max
= 121.21 Amps
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Appendix:
PTR = 21000/240V
NGR Value = 100 Ohms
59GN Relay Range = 5.4V to 20V
Fault at 90% location of Stator Winding from Phase
Terminal
%A = (100 – 90) = 10%
Ground Fault Amps at fault location = (Maximum Ground Fault current * %A)/100
IF at location “A” = (121.21*10)/100
IF at location “A” = 12.12 Amps
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Appendix:
PTR = 21000/240V
NGR Value = 100 Ohms
59GN Relay Range = 5.4V to 20V
Fault at 90% Location of Stator Winding from Phase
terminal
Ground Fault Volts = (Ground fault Amps*PT secondary volts*NGR
Resistance)
-------------------------------------
--------
Ground Fault Volts = (12.12*138.52*100)
(PT Primary Volts)
---------------------------
12121.21
Ground Fault Volts = 13.85 Volts
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Appendix:
59GN Relay Setting = 5.4V & TMS = 0.3
Relay Setting % Location “A” Fault Voltage Operating of
from Neutral Magnitude on Relay
relay terminals
5.4V 5% 6.92V
5.4V 25% 34.63V
5.4V 50% 69.264V
5.4V 75% 103.89V
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Appendix:
59GN Relay Setting = 5.4V & TMS = 0.3
Fault Voltage Operating of
Relay Setting % Location “A”
from Neutral Magnitude on Relay
relay terminals
5.4V 1% 1.38V Not Operate
5.4V 2% 2.77V Not Operate
5.4V 3% 4.15V Not Operate
5.4V 4% 5.54V Not Operate
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (50G):
Resistor Ground
Appendix:
PTR = 21000/240V
NGR Value = 100 Ohms
50G Relay Range = 0.1A to 0.4A
CTR = 20/1A
Maximum Ground Fault Amps =
(Line to Neutral Voltage)
----
----
-=- - - (12121.21)
I F-Max
------------------
- - - -- - - - - - -
--- 100
(
I F-Max
= N 121.21 Amps
Knowledge Is Power SM
G
R
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (50G):
Resistor Ground
Appendix:
50G Relay Setting = 0.1A
Relay Setting % Location “A” Fault Current on Fault Current on
from Neutral Primary side secondary side
0.1A 5% 6.06A 0.3A
0.1A 25% 34.63A 1.51A
0.1A 50% 69.264A 3.03A
0.1A 75% 103.89A 4.54A
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (50G):
Resistor Ground
Appendix:
50G Relay Setting = 0.1A
Relay Setting % Location “A” Fault Current on Fault Current on
from Neutral Primary side secondary side
0.1A 1% 1.21A 0.06A
0.1A 2% 2.42A 0.121A
0.1A 3% 3.63A 0.181A
0.1A 4% 4.84A 0.242A
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)
V
Grounding Transformer
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)
IF
VLN = 21000/1.7325
KVPri = 21kV
KVSec = 0.240kV
KVA = 70KVA
R = 0.913 Ohms
Full Load current in Primary wdg = 3.33A
Ground Fault Impedance = 3640.004 Ohms
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)
IF
a
VLN = 21000/1.7325
Assume; Fault is just 10% from Neutral
Ground Fault Volts = (Ground fault Amps*NGTX Impedance)
= (0.333 * 3640.306)
= 1212.12 Volts in Primary
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)
IF
a
VLN = 21000/1.7325
Ratio = 21000/240
= 87.5
Assume; Fault is just 10% from Neutral
Ground Fault Volts = (1212.12) / (87.5) = 13.85V in Secondary
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)
Setting Criteria: Typical Recommended
setting for IDMTL 59GN relay is 5.4V &
TMS is 0.3
Typical Recommended setting for
Definite Time 59GN relay is 5V & 2 s for
Stage-I and 15V & 1 s is for Stage-II.
Neutral Grounding Resistor value should
not be more than Rn = 10 6 /2*3.14*C to
avoid harmful transient over voltage
because of the Fe r r o - r e s o n a n c e
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
100% Stator Ground Fault
Protection (27TN)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)
Two Measuring Methods to Detect
100% SEF Protection Scheme;
(3 r d ) Third Harmonic
Voltage Method
• 3r d Harmonic Under
Voltage Method
• 3r d Harmonic Over
Voltage Method
• 3r d Harmonic Ratio
Method Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)
3 r d Harmonic Voltage Method;
1% to 3% 3 r d Harmonic (Zero sequence)
Line to Neutral Voltage developed by
Generator during Normal condition
because of the capacitance bet n Stator
winding & Ground
3 r d Harmonic Voltage generated by
machine a r e present in the two ends of
Stator Winding, but the magnitude is
different depends on design & loading
Fault very close to neutral; 3 r d Harmonic
voltage reduced to zero (3V0 = 0V)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)
3 r d Harmonic
Current circulate
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)
3 r d Harmonic Under Voltage Method;
27H Under voltage relay detect 3 r d
harmonic voltage (150Hz for 50Hz &
180Hz for 60Hz).
Fault is close to neutral; 3 r d Harmonic
voltage of machine drop down at neutral
end & initiate tripping
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN):
3 RD Harmonic Under Voltage Method
3 r d Harmonic
Under voltage relay 3 r d harmonic
voltage
drop
Because capacitance
Is shorted
IF
IF
3 r d Harmonic
Voltage at Neutral End reduced
3 r d Harmonic
Voltage at Neutral End reduced
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN): 3
Harmonic Under Voltage Method
3 r d Harmonic Present
At normal Load
Condition on both en
3 r d Harmonic drop to
Zero at neutral end
if fault is close
To neutral
3 r d Harmonic drop to
Zero at terminal
end if fault is close
To terminal
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN +59GN
Numerical Relay
3 r d harmonic filter
Extract only 3 r d
Harmonic voltage
59GN Element
27TN Element
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)
Control circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59TN)
3 r d Harmonic Over Voltage Method;
59TN Over voltage relay detect 3 r d
harmonic voltage (150Hz for 50Hz &
180Hz for 60Hz).
Fault is close to neutral; 3 r d Harmonic
voltage of machine Increases at Terminal
end & initiate tripping
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59TN):
3 RD Harmonic Over Voltage Method
IF
IF
3 r d Harmonic
Over voltage relay
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59TN)
Control circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection
(59TN+27TN)
3 r d Harmonic Ratio Method;
In this method; 3 r d Harmonic voltage will
be measured at both sides, at the neutral
(V 3N ) & at the terminal (V 3 T ) of
generator
Normally, Ratio will be constant for
balance load condition
Ratio will be modified when ground fault
occurs
Ground fault will not detected at null point
(Midpoint of winding)
Overlapping scheme (59TN+27TN+59GN)
is reqd. to Knowledge
detect Isground
Power fault at null point
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: 3 r d
Harmonic Ratio Method
Method:1
V 3N V 3T
Operate: V 3 T /V 3 N > Set value
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: 3 r d
Harmonic Ratio Method
Method:2
V 3N V 3T
Operate: V 3 N /(V 3 N + V 3 T ) < Set value
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: 3 r d
Harmonic Ratio Method
Control circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)
Limitation for Directly Connected Machines;
Third Harmonic can Circulate between two
Machines
3 r d Harmonic Voltage varies on Generator
(G1) based on Loading of G2 & G3
Difficult to apply 3 r d Harmonic under
voltage Protection
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
Sub-Harmonic Injection Method;
Sub-Harmonic voltage is injected through
an injection transformer between the
grounding element of the generator &
ground
Usually sub-harmonic frequency is 1/4 t h of
Fundamental frequency. i.e. 12.5 Hz for
50Hz & 15 Hz for 60Hz relay
This scheme provides ground fault
protection with generator energized or
standstill
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
Fn = 50Hz
Xco = 1
- ---------
2*3.14*Fn*C
IC = (Vn / Xco)
Frequency high€ Xco value l e s s - € High “Ic” current flows
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
F inj = 12.5Hz
XCo = 1/(2*pi*F*C)
12.5Hz
XL = 2*pi*F*L
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
Sub-Harmonic Injection Method;
During Ground Fault condition; 12.5Hz
current flows through Ground ckt. T h e
fault resistance appears in parallel with
shunt capacitances to ground. Thus, the
impedance that limits the sub-
harmonic current & this also make the
current change
Capacitive Reactance Increases
Inductive Reactance Decreases
Relay Operates if 12.5Hz Ground fault
current is more than threshold value
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
Equivalent Circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
Sub-Harmonic Injection Method;
Iinj = (E inj )/ (Zinj + Rn + ZC To t a l )
Where;
Einj = Injection Voltage
Zinj = Injection TR Leakage
Impedance
Zinj = (Rinj + j*Xinj)
Rn = Grounding resistor
ZC = Capacitive impedance of
total ckt.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
Appendix;
Iinj = (E inj )/ (Zinj + Rn + ZC To t a l )
Where;
Einj = 56V
Zinj = (36 + j*125)
F inj = 12.5 Hz
Rn = 1212 Ohms
C To t a l = 2.035 microF
ZC = (10 6 ) /
(2*pi*12.5*2.05)= - Is Power
Knowledge SM
Apparatus Maintenance and Power Management
j*6214 Ohms for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
Appendix;
Zinj = (36 + j*125)
Where;
Rinj = 36 Ohms
Xinj = 125 Ohms
Now;
Xinj = (2*pi*50*L)
125 = (2*3.14*50*L)
L = 0.331H
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
Appendix;
Xinj at Low frequency = (2*pi*12.5*L)
= (2*3.14*12.5*0.331)
= 25.98 Ohms
Now;
Zinj = (36 + j*25.98) Ohms
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
Appendix;
Relay setting is 20mA
Iinj during Normal load condition is;
Iinj = (E inj )/ (Zinj + Rn + ZC To t a l )
= (56) / (36+j*25.98)+1212-(j*6214)
= 0.0088A @ 78.67 o
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
Appendix;
Iinj during Fault condition is;
Iinj = (E inj )/ (Zinj + Rn + Z’C To t a l )
Where;
Z’C = (ZC * RF) / (ZC + RF)
RF = Fault resistance
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
Appendix;
Iinj during Fault condition is;
Iinj = (E inj )/ (Zinj + Rn + Z’C To t a l )
= 0.0258A @ 6.67 o
Relay will issue trip command
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Transformer & Grounding Resistor
Method:1
Grounding
Resistor
Injection
Transformer
IF
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Transformer & Grounding Transforme
Method:2
Grounding
Transformer
Separate Injection
Transformer
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection through Grounding Resistor
Method:3
Sub-Harmonic
Voltage Injection
Through Grounding
Transformer
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection Method in 7UM62 Relay
25V AC
Relay Measures
Rm = (V@20Hz)
---------
(I@20Hz)
IF
Operates;
If Rm < Rset
IF
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection Method in MICOMP345 Relay
Band p ass
Filter range
Is 15 to 25Hz
Or
Low P a s s
Filter (Cut of
Freq. 45Hz
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection Method in MICOMP345 Relay
Transfer Function of Low P a s s Fourier Filter
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection Method in MICOMP345 Relay
Operating time of relay
Is faster than Low p a s s filter
Filter Response of Band P a s s Filter
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection Method in MICOMP345 Relay
NGR
100% SEF scheme with Primary Earthing resistor arrangemen
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Earth Fault Protection
(64R)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F)
First Ground Fault will not:
• Affect the operation of generator
• Produce any damaging effects
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F)
First Ground Fault will:
• No current Flow
• Establish Ground reference making a
Second ground fault more likely
• Increase s t r e s s to ground at other points in
Field winding
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F)
Second Ground Fault will:
• Flow of Large Current
• Unsymmetrical Flux distribution
• Air gap flux badly distorted
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F)
Second Ground Fault will:
• Short out part of field winding causing
unit vibration can damage to bearing
• Cause Rotor Heating from Unbalance
current
• Cause arc damage at point of fault
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F)
DC Voltage Injection Method
Potentiometer Method
AC Voltage Injection Method
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): DC
Injection Method
Brush is used to ground
Rotor Shaft
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): DC
Injection Method
Slip Rings Negative Potential Biasing
IF
IF
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F):
Potentiometer Method
•Scheme adopted in Olde
Machine
•Earth fault on Field Wdg
Produce voltage across
Relay
•Maximum voltage produ
If fault occurs at end of
Wdg
• Overvoltage relay opera
•Blind spot would exist at the centre of field when voltage across the
Wdg & fault would not be detected resistor e x c e e ds 64F’s
•Tapping on Potentiometer could be varied Threshold limit
By using “Push button” to detect fault on
Mid point
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F):
Potentiometer Method
FCB
FCB
R1
64R
R2
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): Lo
Frequency Injection Method
LC-filter is the l o w - p a s s
Filter to removed high
Frequency Rotor current
IF Low Frequency injection
Source to inject low freq.
Voltage (20Hz/12.5Hz)
Measuring circuit: Relay o p er ates when actual voltage e x c e e d s
Threshold value (U>)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): Lo
Frequency Injection Method
Low Frequency voltage output is the
Square wave output
Capacitive coupling blocks normal DC
Field voltage, preventing discharge o
Large current
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): AC
Voltage Injection Method in 7UM62
Fundamental Frequency Injection
Rm = U E
----
----
--
IEE
Relay Operates;
36V/45V
If Rm < Rset
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): AC
Voltage Injection Method in 7UM62
Generating square wave voltage
Rm = Ug
-------
Ig
Low Frequency AC Voltage Measurement
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator: Front & Side view
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator: Front view
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
DOBLE ENGINEERING PVT. LTD
305-SAKAR, OLD PADRA ROAD,
VADODARA.
PH: (+91)(265) 655 77 15 & Fax:
(+91)(265) 235 62 85
Cell: (+91 ) 94267 47545 / 98980
55956
E-MAIL:
[email protected] [email protected]Website: www.doble.com
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery