BA SR 2.1 For Slide HV - LV Panel Testing - Bus-Bar
BA SR 2.1 For Slide HV - LV Panel Testing - Bus-Bar
2.1.
LIST OF TESTS
Conductivity test / Low Resistance Test. Insulation Resistance Test. High Voltage Test. List of Testing Equipments.
2.1
2.1.1
2.1.2
2.1.3 The measured value of bus resistance should be around 20 micro ohm * Number of Joints.
2.2.1 2.2.2
2.3.1 During Hi-Potential test, fuse of PT should be removed. 2.3.2 Normally this test carried out for all Breaker and busbar of switchgear in same time. 2.3.3 Put all the breaker in service position and make sure all breaker in ON condition ,except incomers bus bar and insulators are thoroughly cleaned and all nut bolts are adequate tightened. 2.3.4 Apply DC Voltage across phase to phase and note down the leakage current in record sheet. 2.3.5 Repeat the procedure 1.3.3 for phase to earth and all breaker should be made OFF and racked out.
Multimeter. Megger. Micro-ohm meter. High voltage testing kit. Clamp on meter. Hand tools, etc.