Phthalic Anhydride
Phthalic Anhydride
PROCESS DESCRIPTION Ftalic anhidride is produced by oxidation reaction between O-xylene and air. Reaction ocurrs in a PBR reactor, where its used V2O5 like catalyst. The operation conditions inside reactor for pressure and temperature are 3 atm and 300C, respectively. To achieve this conditions inside reactor, is necessary blend between o-xylene and air get pressure and pre-heat before input to reactor. Next, its shown the reactions involve in production process of ftalic anhydride:
PROCESS DESCRIPTION
CONTROL SPECIFICATIONS
1)
A loop control is necessary to keep the temperature at 146C in the outlet flow of leaving of the first heat exchanger. If the temperature is lower than 144 oC, a visible alarm is generated, the o-xileno pump is shutdown
TT-O1
PID
Stop
FCV-01
CONTROL SPECIFICATIONS
2)
If the temperature of o-xileno in the outlet of second heat exchanger is higher than 305 oC, the steam valve is closed. If the temperature is lower than 295 oC, the steam valve is open to allow the temperature rise
CONTROL SPECIFICATIONS
3)
The concentration of o-xylene in the mixer must remain at 33% mol. If the concentration is over 33,5% mol, a visible alarm is generated and the valve oxylene should be locked
SL-02
CONTROL SPECIFICATIONS
4)
The pressure exerted by o-xileno in the reactor must be monitored. Is necessary to keep the pressure at 3 atm. If the pressure in the reactor is above this value, a relief valve opens to decrease
CONTROL SPECIFICATIONS
5)
The reactor outlet temperature must be maintained between 390 C and 400 C. If the temperature is higher than 400 C, Hitec valve is opened. If the temperature is below 390 C the valve should be closed Hitec
CONTROL SPECIFICATIONS
6)
In the distillation column is required distillate concentration is between 95% and 99% of phthalic anhydride. If the concentration is below 95%, it generates a visible alarm, opening a recirculation valve and valve blocks the distillate
CONTROL SPECIFICATIONS
7)
The production of ftalic anhydride should be monitored for knowing the total discharge monthly.
FT-01
CONTROL SPECIFICATIONS
8)
Maleic anhydride is a pollutant to the environment thus it is necessary to monitor and register the concentration. A visible alarm is generated if maleic anhydride concentration is higher than 10 ppm
AT-
03
CONTROL SPECIFICATIONS
9)
The distillation tower needs a continuous stream flow feeding with phthalic anhydride and maleic anhydride, for this there are two pumps in parallel, the first is always ON, and the second is ON when the first pump fails
1 Start Output Stop MOTOR PU-02 S/S
PU-02 STA
PU-02 AU
PUMP 02 FAIL
PU-03 S/S
MOTOR
Interlock
PU-03
STA
PU-03
AU
OUTPUT LIST
INPUT LIST Temperature Transmitter 01 Temperature Transmitter 02 Temperature Transmitter 03 Analite Transmitter 01 Analite Transmitter 02 Analite Transmitter 03 Flow Transmitter 01 Pressure Transmitter 01
Pu-01 S/S
Pu-02 S/S Pu-03 S/S
INPUT AND OUTPUT LIST TOTAL DISCRETE OUTPUT CARDS REQUIRES TOTAL ANALOG OUTPUT CARDS REQUIRES Strobe Light 01 Strobe Light 02 Strobe Light 03
Strobe Light 04
Flow Control Valve 02 Flow Control Valve 04 Flow Control Valve 05 Flow Control Valve 06 Flow Control Valve 07 Flow Control Valve 08
Pu-01 S/S
Pu-02 S/S Pu-03 S/S Its necessary two discrete output card of 8 instruments for 13 instruments