International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 11 Issue: 02 | Feb 2024 www.irjet.net p-ISSN: 2395-0072
A Review on Influence of Fluid Viscous Damper on The Behaviour of
Multi-storey Building Under Different Seismic Zones
Ghanshyam L. Jodhani1, Kishan Pala2
1M. Tech Student, L.J. University, Ahmedabad
2Kishan Jayswal, Assistance Professor, Civil Engineering Department, L.J. University, Ahmedabad, India.
---------------------------------------------------------------------***---------------------------------------------------------------------
Abstract - Here we implemented high rise structure
construction everywhere as we have urbane designing
software and due to improvement in the field of engineering
and technology. As we know if we rise height of building
seismic and wind load response also increase. Indianstandard
codes propose that the displacements and forcesofastructure
are directly relational to itsheight. Continuouslystudyis going
on for reduction of response during extreme horizontal
loading due to shaking and wind. Passivecontrollerdevicelike
various type of dampers is used for controlling response of
shaking and wind load.
Key Words: Fluid viscous dampers, Displacement,
Storey Drift and Storey shear, ETABS.
1. INTRODUCTION
1.1 General
 Which different kind of load is acting on RC
building?
There are many types of loads are acting on RC building.
If we discus majorly in India we consider Dead load, Live
load, Seismic load and Wind load (if height if building is
more than 10m, as per IS 875 part 3). ButaccordingtoIS456
table-18 while we consider earthquake effect then in given
load combination wind loadissubstitute byearthquakeload.
 Dead Load:
Dead load is mainly caused by the individual weight of
the structure and the completionofthestructure.Deadloads
are carried out only in the vertical direction. We can only
assume that no tipping occurred due to static properties.
 Live Load:
Live load is acting due to human stay in building,
furniture, vehicle etc. In different type of building, we
consider different value of Live load as suggested in IS 875
part 2.
 Earthquake Load (Seismic load):
Seismic load is the horizontal load on the building as
result of the shaking of the ground during an earthquake.
Earthquake loads are “dynamic load”. Other types of loads
usually slowly acts on structure, but seismic load act rapidly
and vibrate the structure.
 What is earthquake resistant building?
Earthquake resistant building is defined as there is no
damage allowed in structural member andnomajordamage
allowed in non-structural member in weak earthquake,
Structural damage allowed but not major damage allowed it
should be repairable in moderate or moderately strong
earthquake, and instrongearthquakemajordamageallowed
but structure should not collapse during earthquake, this
type of building known as earthquake resistant building.
 What is damper?
“Dampers are energy dissipation system”.
Dampers are device usedto disperseorabsorbvibration
resulting from earthquake in the structure to increase the
damping and stiffness of the structure.
 Different type of damper majorly used in building.
1] Fluid Viscous Dampers (FVD)
2] Viscoelastic Dampers
3] Friction Dampers
4] Tuned Mass Damper (TMD)
5] Yielding Dampers
6] Magnetic Damper
1.2 Fluid viscous dampers:
Figure 1: Schematic Detailing of Fluid Viscous Damper
Components
Inthefluidviscousdampers,seismicenergyabsorbed
by silicon-based fluid passing through the piston-cylinder
© 2024, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 34
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 11 Issue: 02 | Feb 2024 www.irjet.net p-ISSN: 2395-0072
arrangement. Viscous dampers are used in many building in
higher earthquake zone. It operatesinthetemperaturerange
of 40o C to 70o C. Viscous dampers reduce vibration caused
by earthquake.
 Component of Fluid viscous dampers.
1] Piston Rod
2] Cylinder
3] Silicone Fluid
4] Accumulator Housing
5] Seal and Seal Retainer
6] Chamber-1 and Chamber-2
7] Piston Head with Orifices
8] Control Valve
9] Rod Make-up Accumulator
 Types of connection of Fluid viscous dampers.
There are three ways to connect dampers,
1] In floor or foundation
2] In stern pericardial braces
3] In diagonal braces
Figure 2: stern pericardial braces
Figure 3: Diagonal Braces
Figure 4: Floor or Foundation
1.3 Terminologies:
Displacement:
“The distance from the original position of sample point of
structure to its final location of the deformed structure is
known as displacement of structure.”
Story Drift:
“The lateral displacement of consecutive floor is known as
storey drift.” And “The ratio of floor drift to the floor heightis
known as storey drift ratio.”
Story Shear force:
“The lateral force act on the storey duo to force such as wind
load or seismic load is known as storey shear force.”
Building having less stiffness attracts less storey
shear and buildings havingmorestiffnessattractmorestorey
shear.
1.4 Objective
The main objective of this study is to check the kind of
performance a building can give when designed as per
Indian Standards.
The Analysis of the building frame is carried out by using
structural analysis and design software ETABS (version21).
 To analyse Storey displacement of building.
 To analyse Storey drift of building.
 To analyse Storey shear of building.
We are use ETABS (version 21)foranalysemodel ofRCC
building. Take random parameters of column, beam and
other structural component. Different seismic zone and
different type of soil is considered for analysis.
2. LITERATURE REVIEW
[1] Milton Fernandes 1, Swane Rodrigues 2, Suraj
Sharma3, Smit Raut 4, Mr. Shreeshail Heggond 5,
“ComparativeStudyofSeismicBehavior ofHigh-Rise
Building with and Without Use of Fluid Viscous
Damper Using E-Tabs”, International Journal of
Innovations in Engineering and Science.
G+25 RCC commercial office buildinglocatedin Mumbai
with higher height to plan dimensionratioisexaminedusing
fluid viscous dampers at exterior cornerof building. Model is
run in ETABS 2019 and examined model with two methods,
(1) Equivalent staticmethodand(2)Responsespectrum
method.
For a G+ 25-storey RCC building with and without ice
damper, floor displacements, floor drifts, floor shear forces
and models along x and y directions, static equation method
and response spectrum method time and frequency value
were used.
The study concluded that the floor deflection of a
conventional reinforced concrete building without a tipper
will have the highest deflection compared to a building with
a tipper. By adding dampers to the structure, we will reduce
© 2024, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 35
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 11 Issue: 02 | Feb 2024 www.irjet.net p-ISSN: 2395-0072
the displacement factor and increase the stability of the
structure. Since the displacement value increases as the
height of the building increases, dampers are used to reduce
ground displacement. By adding dampers to the structure,
the inter-storey drift value can be reduced, and the
maximum inter-storey drift value of the building does not
exceed the limit specified in Indian standards.
[2]Daniel C, Arunraj E, Vincent Sam Jebadurai S, Joel
Shelton J, Hemalatha G, “Dynamic Analysis of
Structure using Fluid Viscous Damper for Various
Seismic Intensities”, International Journal of
Innovative Technology and Exploring Engineering
(IJITEE)
Dynamic analysis done for 5 story RCC structure
with fluid viscous damper with different earthquake
intensity, the model is done using SAP 2000 in this research
paper. Using SAP 2000, runthemodelandexaminethemodel
with the dynamic analysis method. Roof displacement and
base shear of RCC building with liquid viscous dampers and
without liquid viscous dampers were investigated.
Based on this research, it is concluded that the base shear
obtained was reduced by 50% for the X-axis using FVD. The
base shear obtained was reduced by 61.3% for the Y-axis
using FVD. The roof drift was reduced by 50.65% for the X-
axis using FVD. The roof drift was reduced by 51.35% for the
Y-axis with FVD.
[3]Vibha More, Dr. Vikram Patil, Somanagouda
Takkalaki, “Dynamic Analysis of RCC Frame
Structures with andWithoutViscousDamperHaving
Different AspectRatio”,IJISET-InternationalJournal
of Innovative Science, Engineering & Technology.
Detailed analytical study of liquid viscous damper
using ETABS version 15. The study is limited to the analysis
of 20 storey and 40 storeys R.C.C. building. A total of four
different structures are modelled for two different heights
and two different aspect ratios.
This work includes a study of the structure with and
without a fluid viscous damper. The different heights to be
considered for this study are 20 storeys and 40 storeys.
Different aspect ratio shouldalso be considered, for example
1, 1.5. The aim of the study is to find out the differences in
various parameters of the structureusingETABSsoftwareby
performing response spectrum analysis.
Liquid viscous dampers will be installed inthebuildingto
combat the acceleration force due to the earthquake. A trial-
and-error method was usedtofindtheoptimallocationofthe
dampers in the building.
Research indicates that up to 44% reduction in floor drift
has been observed when FVD is provided to the 10th floor in
a zigzag pattern, while the reduction is up to 54% when FVD
is provided at all exterior corners in a zigzag pattern. Floor
drift reduced by up to 78% when FVD is secured to the 10th
floor in a zigzag pattern. It is also reduced byupto65%when
FVD is provided at all outer corners in a zigzag pattern.
Approximately 40% reduction in time-period was observed
when using FVD. It was observed that the B model with
aspect ratio of 1 with dampersprovidedwithazigzagpattern
at all outer corners gives a satisfactory result compared to
other models.
[4]Madhuri S L, Lakshmi P S, “Seismic Performance
Evaluation of Fluid viscous Damper”, International
Journal of AdvancesinEngineeringandManagement
(IJAEM).
In this research, a 5-bay X-direction and 5-bay Y-
direction rectangular reinforced concrete structure model
for 15-story frames made of M25-grade concrete for the
beam and slab and M30 for the column and Fe500-grade
steel is built. A scheme with a field width of 5 m is measured.
The expected floor height is 3.6 m. The total width of the
frame is therefore 25 x 25 m. The support conditions are to
be fixed and the reduction factor is to be 5 for soil type 2
(medium) and seismic zone V.
We concluded that the offset of the floor is high on the
upper floor and lower on the base,withincreasingheightthe
offset increases. The displacement of the floors of the
structure without the application of FVD is the maximum
compared to the structure with FVD, and with the
application of FVD in the corners of all floors, the maximum
displacement is reduced compared to other places of the
structure. The floor displacement follows a parabolic path
along the floor height with a maximum value somewhere
near the fourth floor. After the fourth floor, the floor
displacement decreases as the height of the structure
increases. The storey displacement is maximum for the
structure without dampers and is reduced by 47% when
FVDs are placed at the corners of all storey and by 41%
when FVDs are placed at the center of all storey.
[5] N. Priyanka, Dr. J. Thivya, J. Vijayaraghavan,
“SEISMIC STUDY OF MULTI-STOREY STRUCTURE
WITH FLUID VISCOUS DAMPERS USING ETABS”,
International Research Journal of Engineering and
Technology (IRJET).
A seismic study of a multi-story structure resting on
normal terrain with different seismic intensities with and
without the use of liquid viscous dampers is performed. An
RC multi-storey building in seismic zones II, III, IV andVis to
be designed and the most vulnerable buildingamongthemis
to be identified. Fluid viscous dampers with different
strengths can also be used in different types of buildings
because the modelled structure has a low height; smaller
devices were used to start the analysis. The FVD is added to
the structure after it is defined in the joint properties by
adding a new damper exponential in the joint property data.
© 2024, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 36
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 11 Issue: 02 | Feb 2024 www.irjet.net p-ISSN: 2395-0072
From the results, we conclude that responses such as
acceleration, base shear, displacement are reduced when
FVD is included in the design. The seismic performance of
buildings can only be improved by using energy dissipation
devices (dampers) that dissipate the input energy during an
earthquake. Damper placement plays a primary role in
controlling structural vibration. Efficiency is greater when
the dampers are placed in the corners instead of in the
middle. The most vulnerable type of building is in zone V.
Therefore, from this analysis, the location of the damper is
very effective and recommended.
3. CONCLUSION
Fluid viscous dampers are devices to absorb energy
produced by earthquake or wind load or any other lateral
load acting on RCC building.
 Analysis of storey displacement with fluid viscous
damper and without fluid viscous dampersclearlyshow
that maximum displacement of building is reduced by
some percentage after adding fluid viscous dampers.
 Storey drift of building after adding fluid viscous
dampers decrease and base shear also reduce.
 Time period of building is increase so frequency of
building is decrease and less frequency attract less
seismic load.
 Location of fluid viscous dampers also affect on
displacement, storeydrift andotherseismic parameters.
 Corner damping is most effective as compared to other
placement of dampers. middle damping is little bit less
effective as compared to corner damping.
 Building in higher seismic zone getting more
displacement and storey drift as compared to lower
seismic zone.
 If we want to decrease displacementandstoreydrift,we
need to introduce some shock absorber for reduce
movement of RCC building during lateral load acting
during earthquake or high wind speed.
 Fluid viscous dampers are the more effective absorbers
for RCC building.
4. REFERENCE
1] Milton Fernandes 1, Swane Rodrigues 2, Suraj Sharma3,
Smit Raut 4, Mr. Shreeshail Heggond 5, “Comparative
Study of Seismic Behavior of High-Rise Building with
and Without Use of FluidViscousDamperUsingE-Tabs”,
International Journal of Innovations in Engineering and
Science, www.ijies.net, e-ISSN: 2456-3463 Vol. 6, No. 5,
2021, PP. 22 -30
2] Daniel C, Arunraj E, Vincent Sam Jebadurai S,Joel Shelton
J, Hemalatha G, “Dynamic Analysis of Structure using
Fluid Viscous Damper for Various Seismic Intensities”,
International Journal of Innovative Technology and
Exploring Engineering (IJITEE) ISSN: 2278-3075,
Volume-9 Issue-1, November 2019
3] Vibha More, Dr. Vikram Patil, Somanagouda Takkalaki,
“Dynamic Analysis of RCC Frame Structures with and
Without ViscousDamperHavingDifferentAspectRatio”,
IJISET - International Journal of Innovative Science,
Engineering & Technology,Vol.6Issue10,October2019
ISSN (Online) 2348 – 7968 | Impact Factor (2019) –
6.248
4] N. Priyanka, Dr. J. Thivya, J. Vijayaraghavan, “SEISMIC
STUDY OF MULTI-STOREY STRUCTURE WITH FLUID
VISCOUS DAMPERS USING ETABS”, International
Research Journal of Engineering and Technology
(IRJET), Volume: 06 Issue: 04 | Apr 2019.
5] Madhuri S L, Lakshmi P S, “Seismic Performance
Evaluation of Fluid viscous Damper”, International
Journal of Advances in Engineering and Management
(IJAEM), Volume 4, Issue 7 July 2022.
6] IS 1893 Part 1 (2016)
7] IS 875 Part 1 (1987)
8] IS 875 Part 2 (1987)
© 2024, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 37

More Related Content

PDF
Seismic Analysis of Multi Storey RC Building with and Without Fluid Viscous D...
PDF
IRJET- Performance Analysis of High Rise RCC Frame Structure using Various Ty...
PDF
Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...
PDF
IRJET- Seismic Study of Multi-Storey Structure with Fluid Viscous Dampers...
PDF
Optimization of Placing Viscous Dampers on 3D RC Frame Subjected to Seismic L...
PDF
IRJET- A Review of Seismic Analysis of Different Shape of RC Building by usin...
PDF
Seismic Analysis of Reinforced Concrete Building Using Fluid Viscous Damper
PDF
IRJET - Seismic Analysis of Different Shape of RC Building by using the Visco...
Seismic Analysis of Multi Storey RC Building with and Without Fluid Viscous D...
IRJET- Performance Analysis of High Rise RCC Frame Structure using Various Ty...
Analysis of Moment Resisting Reinforced Concrete Frames for Seismic Response ...
IRJET- Seismic Study of Multi-Storey Structure with Fluid Viscous Dampers...
Optimization of Placing Viscous Dampers on 3D RC Frame Subjected to Seismic L...
IRJET- A Review of Seismic Analysis of Different Shape of RC Building by usin...
Seismic Analysis of Reinforced Concrete Building Using Fluid Viscous Damper
IRJET - Seismic Analysis of Different Shape of RC Building by using the Visco...

Similar to A Review on Influence of Fluid Viscous Damper on The Behaviour of Multi-storey Building Under Different Seismic Zones (20)

PDF
Study of Viscous Fluid Damper 6 Different Pattern on 12 Story Structure And C...
PDF
Comparative Study on Seismic Behavior of Different Shape of RC Structure with...
PDF
SEISMIC EVALUATION OF MULTISTORIED BUILDING WITH FLOATING COLUMNS USING ETABS
PDF
Comparative Study on Seismic Behavior of Different Shapes of RC Structure wit...
PDF
Seismic Analysis of I Shaped and Plus Shaped Building with and without damper
PDF
Seismic Performance of Reinforced Cement Concrete Structures with and Without...
PDF
IRJET- Comparative Analysis of Effects of Base Isolator & Fluid Viscous Dampe...
PDF
SEISMIC RESPONSE STUDY OF MULTI-STORIED REINFORCED CONCRETE BUILDING WITH FLU...
PDF
IRJET- Seismic Analysis of Asymmetric RCC Buildings using Passive Energy Diss...
PDF
Optimization of Seismic Response by Steel Framed Structures on Sloping Ground
PPTX
Study on the effect of viscous dampers for RCC frame Structure
PDF
STRUCTURAL RESPONSE CONTROL OF RCC MOMENT RESISTING FRAME USING FLUID VISCOUS...
PDF
Seismic performance of adjacent building using fluid viscous dampers
PDF
ADEQUACY OF BELT-TRUSS AND OUTRIGGER SYSTEMS WITH VISCOUS DAMPER IN 3D RC FRA...
PDF
IRJET- A Review Paper on Comparative Study of Fixed Base, Base Isolation & Da...
PDF
IRJET- A Review of Seismic Behaviour of Multi-Story Building using various En...
PDF
IRJET- A Review on Seismic Analysis of Buildings using Passive Energy Dis...
DOC
Technical writing on earthquake sustainable building using Fluid Viscous Damper
PDF
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
PDF
IRJET- Effect of Viscous Dampers on Response Reduction Factor for RCC Frame u...
Study of Viscous Fluid Damper 6 Different Pattern on 12 Story Structure And C...
Comparative Study on Seismic Behavior of Different Shape of RC Structure with...
SEISMIC EVALUATION OF MULTISTORIED BUILDING WITH FLOATING COLUMNS USING ETABS
Comparative Study on Seismic Behavior of Different Shapes of RC Structure wit...
Seismic Analysis of I Shaped and Plus Shaped Building with and without damper
Seismic Performance of Reinforced Cement Concrete Structures with and Without...
IRJET- Comparative Analysis of Effects of Base Isolator & Fluid Viscous Dampe...
SEISMIC RESPONSE STUDY OF MULTI-STORIED REINFORCED CONCRETE BUILDING WITH FLU...
IRJET- Seismic Analysis of Asymmetric RCC Buildings using Passive Energy Diss...
Optimization of Seismic Response by Steel Framed Structures on Sloping Ground
Study on the effect of viscous dampers for RCC frame Structure
STRUCTURAL RESPONSE CONTROL OF RCC MOMENT RESISTING FRAME USING FLUID VISCOUS...
Seismic performance of adjacent building using fluid viscous dampers
ADEQUACY OF BELT-TRUSS AND OUTRIGGER SYSTEMS WITH VISCOUS DAMPER IN 3D RC FRA...
IRJET- A Review Paper on Comparative Study of Fixed Base, Base Isolation & Da...
IRJET- A Review of Seismic Behaviour of Multi-Story Building using various En...
IRJET- A Review on Seismic Analysis of Buildings using Passive Energy Dis...
Technical writing on earthquake sustainable building using Fluid Viscous Damper
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
IRJET- Effect of Viscous Dampers on Response Reduction Factor for RCC Frame u...
Ad

More from IRJET Journal (20)

PDF
Enhanced heart disease prediction using SKNDGR ensemble Machine Learning Model
PDF
Utilizing Biomedical Waste for Sustainable Brick Manufacturing: A Novel Appro...
PDF
Kiona – A Smart Society Automation Project
PDF
DESIGN AND DEVELOPMENT OF BATTERY THERMAL MANAGEMENT SYSTEM USING PHASE CHANG...
PDF
Invest in Innovation: Empowering Ideas through Blockchain Based Crowdfunding
PDF
SPACE WATCH YOUR REAL-TIME SPACE INFORMATION HUB
PDF
Wireless Arduino Control via Mobile: Eliminating the Need for a Dedicated Wir...
PDF
Explainable AI(XAI) using LIME and Disease Detection in Mango Leaf by Transfe...
PDF
BRAIN TUMOUR DETECTION AND CLASSIFICATION
PDF
The Project Manager as an ambassador of the contract. The case of NEC4 ECC co...
PDF
"Enhanced Heat Transfer Performance in Shell and Tube Heat Exchangers: A CFD ...
PDF
Advancements in CFD Analysis of Shell and Tube Heat Exchangers with Nanofluid...
PDF
Breast Cancer Detection using Computer Vision
PDF
Auto-Charging E-Vehicle with its battery Management.
PDF
Analysis of high energy charge particle in the Heliosphere
PDF
A Novel System for Recommending Agricultural Crops Using Machine Learning App...
PDF
Auto-Charging E-Vehicle with its battery Management.
PDF
Analysis of high energy charge particle in the Heliosphere
PDF
Wireless Arduino Control via Mobile: Eliminating the Need for a Dedicated Wir...
PDF
FIR filter-based Sample Rate Convertors and its use in NR PRACH
Enhanced heart disease prediction using SKNDGR ensemble Machine Learning Model
Utilizing Biomedical Waste for Sustainable Brick Manufacturing: A Novel Appro...
Kiona – A Smart Society Automation Project
DESIGN AND DEVELOPMENT OF BATTERY THERMAL MANAGEMENT SYSTEM USING PHASE CHANG...
Invest in Innovation: Empowering Ideas through Blockchain Based Crowdfunding
SPACE WATCH YOUR REAL-TIME SPACE INFORMATION HUB
Wireless Arduino Control via Mobile: Eliminating the Need for a Dedicated Wir...
Explainable AI(XAI) using LIME and Disease Detection in Mango Leaf by Transfe...
BRAIN TUMOUR DETECTION AND CLASSIFICATION
The Project Manager as an ambassador of the contract. The case of NEC4 ECC co...
"Enhanced Heat Transfer Performance in Shell and Tube Heat Exchangers: A CFD ...
Advancements in CFD Analysis of Shell and Tube Heat Exchangers with Nanofluid...
Breast Cancer Detection using Computer Vision
Auto-Charging E-Vehicle with its battery Management.
Analysis of high energy charge particle in the Heliosphere
A Novel System for Recommending Agricultural Crops Using Machine Learning App...
Auto-Charging E-Vehicle with its battery Management.
Analysis of high energy charge particle in the Heliosphere
Wireless Arduino Control via Mobile: Eliminating the Need for a Dedicated Wir...
FIR filter-based Sample Rate Convertors and its use in NR PRACH
Ad

Recently uploaded (20)

PPTX
Real Estate Management PART 1.pptxFFFFFFFFFFFFF
PDF
Lesson 3 .pdf
DOCX
An investigation of the use of recycled crumb rubber as a partial replacement...
PPTX
Unit IImachinemachinetoolopeartions.pptx
PPTX
Design ,Art Across Digital Realities and eXtended Reality
PDF
Engineering Solutions for Ethical Dilemmas in Healthcare (www.kiu.ac.ug)
PDF
[jvmmeetup] next-gen integration with apache camel and quarkus.pdf
PPTX
Environmental studies, Moudle 3-Environmental Pollution.pptx
PPTX
DATA STRCUTURE LABORATORY -BCSL305(PRG1)
PPTX
SE unit 1.pptx by d.y.p.akurdi aaaaaaaaaaaa
PPTX
INTERNET OF THINGS - EMBEDDED SYSTEMS AND INTERNET OF THINGS
PPTX
ARCHITECTURE AND PROGRAMMING OF EMBEDDED SYSTEMS
PDF
CELDAS DE COMBUSTIBLE TIPO MEMBRANA DE INTERCAMBIO PROTÓNICO.pdf
PPTX
Quality engineering part 1 for engineering undergraduates
PDF
Cryptography and Network Security-Module-I.pdf
PPTX
CS6006 - CLOUD COMPUTING - Module - 1.pptx
PPTX
chapter 1.pptx dotnet technology introduction
PDF
VTU IOT LAB MANUAL (BCS701) Computer science and Engineering
PDF
Software defined netwoks is useful to learn NFV and virtual Lans
DOCX
ENVIRONMENTAL PROTECTION AND MANAGEMENT (18CVL756)
Real Estate Management PART 1.pptxFFFFFFFFFFFFF
Lesson 3 .pdf
An investigation of the use of recycled crumb rubber as a partial replacement...
Unit IImachinemachinetoolopeartions.pptx
Design ,Art Across Digital Realities and eXtended Reality
Engineering Solutions for Ethical Dilemmas in Healthcare (www.kiu.ac.ug)
[jvmmeetup] next-gen integration with apache camel and quarkus.pdf
Environmental studies, Moudle 3-Environmental Pollution.pptx
DATA STRCUTURE LABORATORY -BCSL305(PRG1)
SE unit 1.pptx by d.y.p.akurdi aaaaaaaaaaaa
INTERNET OF THINGS - EMBEDDED SYSTEMS AND INTERNET OF THINGS
ARCHITECTURE AND PROGRAMMING OF EMBEDDED SYSTEMS
CELDAS DE COMBUSTIBLE TIPO MEMBRANA DE INTERCAMBIO PROTÓNICO.pdf
Quality engineering part 1 for engineering undergraduates
Cryptography and Network Security-Module-I.pdf
CS6006 - CLOUD COMPUTING - Module - 1.pptx
chapter 1.pptx dotnet technology introduction
VTU IOT LAB MANUAL (BCS701) Computer science and Engineering
Software defined netwoks is useful to learn NFV and virtual Lans
ENVIRONMENTAL PROTECTION AND MANAGEMENT (18CVL756)

A Review on Influence of Fluid Viscous Damper on The Behaviour of Multi-storey Building Under Different Seismic Zones

  • 1. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 11 Issue: 02 | Feb 2024 www.irjet.net p-ISSN: 2395-0072 A Review on Influence of Fluid Viscous Damper on The Behaviour of Multi-storey Building Under Different Seismic Zones Ghanshyam L. Jodhani1, Kishan Pala2 1M. Tech Student, L.J. University, Ahmedabad 2Kishan Jayswal, Assistance Professor, Civil Engineering Department, L.J. University, Ahmedabad, India. ---------------------------------------------------------------------***--------------------------------------------------------------------- Abstract - Here we implemented high rise structure construction everywhere as we have urbane designing software and due to improvement in the field of engineering and technology. As we know if we rise height of building seismic and wind load response also increase. Indianstandard codes propose that the displacements and forcesofastructure are directly relational to itsheight. Continuouslystudyis going on for reduction of response during extreme horizontal loading due to shaking and wind. Passivecontrollerdevicelike various type of dampers is used for controlling response of shaking and wind load. Key Words: Fluid viscous dampers, Displacement, Storey Drift and Storey shear, ETABS. 1. INTRODUCTION 1.1 General  Which different kind of load is acting on RC building? There are many types of loads are acting on RC building. If we discus majorly in India we consider Dead load, Live load, Seismic load and Wind load (if height if building is more than 10m, as per IS 875 part 3). ButaccordingtoIS456 table-18 while we consider earthquake effect then in given load combination wind loadissubstitute byearthquakeload.  Dead Load: Dead load is mainly caused by the individual weight of the structure and the completionofthestructure.Deadloads are carried out only in the vertical direction. We can only assume that no tipping occurred due to static properties.  Live Load: Live load is acting due to human stay in building, furniture, vehicle etc. In different type of building, we consider different value of Live load as suggested in IS 875 part 2.  Earthquake Load (Seismic load): Seismic load is the horizontal load on the building as result of the shaking of the ground during an earthquake. Earthquake loads are “dynamic load”. Other types of loads usually slowly acts on structure, but seismic load act rapidly and vibrate the structure.  What is earthquake resistant building? Earthquake resistant building is defined as there is no damage allowed in structural member andnomajordamage allowed in non-structural member in weak earthquake, Structural damage allowed but not major damage allowed it should be repairable in moderate or moderately strong earthquake, and instrongearthquakemajordamageallowed but structure should not collapse during earthquake, this type of building known as earthquake resistant building.  What is damper? “Dampers are energy dissipation system”. Dampers are device usedto disperseorabsorbvibration resulting from earthquake in the structure to increase the damping and stiffness of the structure.  Different type of damper majorly used in building. 1] Fluid Viscous Dampers (FVD) 2] Viscoelastic Dampers 3] Friction Dampers 4] Tuned Mass Damper (TMD) 5] Yielding Dampers 6] Magnetic Damper 1.2 Fluid viscous dampers: Figure 1: Schematic Detailing of Fluid Viscous Damper Components Inthefluidviscousdampers,seismicenergyabsorbed by silicon-based fluid passing through the piston-cylinder © 2024, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 34
  • 2. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 11 Issue: 02 | Feb 2024 www.irjet.net p-ISSN: 2395-0072 arrangement. Viscous dampers are used in many building in higher earthquake zone. It operatesinthetemperaturerange of 40o C to 70o C. Viscous dampers reduce vibration caused by earthquake.  Component of Fluid viscous dampers. 1] Piston Rod 2] Cylinder 3] Silicone Fluid 4] Accumulator Housing 5] Seal and Seal Retainer 6] Chamber-1 and Chamber-2 7] Piston Head with Orifices 8] Control Valve 9] Rod Make-up Accumulator  Types of connection of Fluid viscous dampers. There are three ways to connect dampers, 1] In floor or foundation 2] In stern pericardial braces 3] In diagonal braces Figure 2: stern pericardial braces Figure 3: Diagonal Braces Figure 4: Floor or Foundation 1.3 Terminologies: Displacement: “The distance from the original position of sample point of structure to its final location of the deformed structure is known as displacement of structure.” Story Drift: “The lateral displacement of consecutive floor is known as storey drift.” And “The ratio of floor drift to the floor heightis known as storey drift ratio.” Story Shear force: “The lateral force act on the storey duo to force such as wind load or seismic load is known as storey shear force.” Building having less stiffness attracts less storey shear and buildings havingmorestiffnessattractmorestorey shear. 1.4 Objective The main objective of this study is to check the kind of performance a building can give when designed as per Indian Standards. The Analysis of the building frame is carried out by using structural analysis and design software ETABS (version21).  To analyse Storey displacement of building.  To analyse Storey drift of building.  To analyse Storey shear of building. We are use ETABS (version 21)foranalysemodel ofRCC building. Take random parameters of column, beam and other structural component. Different seismic zone and different type of soil is considered for analysis. 2. LITERATURE REVIEW [1] Milton Fernandes 1, Swane Rodrigues 2, Suraj Sharma3, Smit Raut 4, Mr. Shreeshail Heggond 5, “ComparativeStudyofSeismicBehavior ofHigh-Rise Building with and Without Use of Fluid Viscous Damper Using E-Tabs”, International Journal of Innovations in Engineering and Science. G+25 RCC commercial office buildinglocatedin Mumbai with higher height to plan dimensionratioisexaminedusing fluid viscous dampers at exterior cornerof building. Model is run in ETABS 2019 and examined model with two methods, (1) Equivalent staticmethodand(2)Responsespectrum method. For a G+ 25-storey RCC building with and without ice damper, floor displacements, floor drifts, floor shear forces and models along x and y directions, static equation method and response spectrum method time and frequency value were used. The study concluded that the floor deflection of a conventional reinforced concrete building without a tipper will have the highest deflection compared to a building with a tipper. By adding dampers to the structure, we will reduce © 2024, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 35
  • 3. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 11 Issue: 02 | Feb 2024 www.irjet.net p-ISSN: 2395-0072 the displacement factor and increase the stability of the structure. Since the displacement value increases as the height of the building increases, dampers are used to reduce ground displacement. By adding dampers to the structure, the inter-storey drift value can be reduced, and the maximum inter-storey drift value of the building does not exceed the limit specified in Indian standards. [2]Daniel C, Arunraj E, Vincent Sam Jebadurai S, Joel Shelton J, Hemalatha G, “Dynamic Analysis of Structure using Fluid Viscous Damper for Various Seismic Intensities”, International Journal of Innovative Technology and Exploring Engineering (IJITEE) Dynamic analysis done for 5 story RCC structure with fluid viscous damper with different earthquake intensity, the model is done using SAP 2000 in this research paper. Using SAP 2000, runthemodelandexaminethemodel with the dynamic analysis method. Roof displacement and base shear of RCC building with liquid viscous dampers and without liquid viscous dampers were investigated. Based on this research, it is concluded that the base shear obtained was reduced by 50% for the X-axis using FVD. The base shear obtained was reduced by 61.3% for the Y-axis using FVD. The roof drift was reduced by 50.65% for the X- axis using FVD. The roof drift was reduced by 51.35% for the Y-axis with FVD. [3]Vibha More, Dr. Vikram Patil, Somanagouda Takkalaki, “Dynamic Analysis of RCC Frame Structures with andWithoutViscousDamperHaving Different AspectRatio”,IJISET-InternationalJournal of Innovative Science, Engineering & Technology. Detailed analytical study of liquid viscous damper using ETABS version 15. The study is limited to the analysis of 20 storey and 40 storeys R.C.C. building. A total of four different structures are modelled for two different heights and two different aspect ratios. This work includes a study of the structure with and without a fluid viscous damper. The different heights to be considered for this study are 20 storeys and 40 storeys. Different aspect ratio shouldalso be considered, for example 1, 1.5. The aim of the study is to find out the differences in various parameters of the structureusingETABSsoftwareby performing response spectrum analysis. Liquid viscous dampers will be installed inthebuildingto combat the acceleration force due to the earthquake. A trial- and-error method was usedtofindtheoptimallocationofthe dampers in the building. Research indicates that up to 44% reduction in floor drift has been observed when FVD is provided to the 10th floor in a zigzag pattern, while the reduction is up to 54% when FVD is provided at all exterior corners in a zigzag pattern. Floor drift reduced by up to 78% when FVD is secured to the 10th floor in a zigzag pattern. It is also reduced byupto65%when FVD is provided at all outer corners in a zigzag pattern. Approximately 40% reduction in time-period was observed when using FVD. It was observed that the B model with aspect ratio of 1 with dampersprovidedwithazigzagpattern at all outer corners gives a satisfactory result compared to other models. [4]Madhuri S L, Lakshmi P S, “Seismic Performance Evaluation of Fluid viscous Damper”, International Journal of AdvancesinEngineeringandManagement (IJAEM). In this research, a 5-bay X-direction and 5-bay Y- direction rectangular reinforced concrete structure model for 15-story frames made of M25-grade concrete for the beam and slab and M30 for the column and Fe500-grade steel is built. A scheme with a field width of 5 m is measured. The expected floor height is 3.6 m. The total width of the frame is therefore 25 x 25 m. The support conditions are to be fixed and the reduction factor is to be 5 for soil type 2 (medium) and seismic zone V. We concluded that the offset of the floor is high on the upper floor and lower on the base,withincreasingheightthe offset increases. The displacement of the floors of the structure without the application of FVD is the maximum compared to the structure with FVD, and with the application of FVD in the corners of all floors, the maximum displacement is reduced compared to other places of the structure. The floor displacement follows a parabolic path along the floor height with a maximum value somewhere near the fourth floor. After the fourth floor, the floor displacement decreases as the height of the structure increases. The storey displacement is maximum for the structure without dampers and is reduced by 47% when FVDs are placed at the corners of all storey and by 41% when FVDs are placed at the center of all storey. [5] N. Priyanka, Dr. J. Thivya, J. Vijayaraghavan, “SEISMIC STUDY OF MULTI-STOREY STRUCTURE WITH FLUID VISCOUS DAMPERS USING ETABS”, International Research Journal of Engineering and Technology (IRJET). A seismic study of a multi-story structure resting on normal terrain with different seismic intensities with and without the use of liquid viscous dampers is performed. An RC multi-storey building in seismic zones II, III, IV andVis to be designed and the most vulnerable buildingamongthemis to be identified. Fluid viscous dampers with different strengths can also be used in different types of buildings because the modelled structure has a low height; smaller devices were used to start the analysis. The FVD is added to the structure after it is defined in the joint properties by adding a new damper exponential in the joint property data. © 2024, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 36
  • 4. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 11 Issue: 02 | Feb 2024 www.irjet.net p-ISSN: 2395-0072 From the results, we conclude that responses such as acceleration, base shear, displacement are reduced when FVD is included in the design. The seismic performance of buildings can only be improved by using energy dissipation devices (dampers) that dissipate the input energy during an earthquake. Damper placement plays a primary role in controlling structural vibration. Efficiency is greater when the dampers are placed in the corners instead of in the middle. The most vulnerable type of building is in zone V. Therefore, from this analysis, the location of the damper is very effective and recommended. 3. CONCLUSION Fluid viscous dampers are devices to absorb energy produced by earthquake or wind load or any other lateral load acting on RCC building.  Analysis of storey displacement with fluid viscous damper and without fluid viscous dampersclearlyshow that maximum displacement of building is reduced by some percentage after adding fluid viscous dampers.  Storey drift of building after adding fluid viscous dampers decrease and base shear also reduce.  Time period of building is increase so frequency of building is decrease and less frequency attract less seismic load.  Location of fluid viscous dampers also affect on displacement, storeydrift andotherseismic parameters.  Corner damping is most effective as compared to other placement of dampers. middle damping is little bit less effective as compared to corner damping.  Building in higher seismic zone getting more displacement and storey drift as compared to lower seismic zone.  If we want to decrease displacementandstoreydrift,we need to introduce some shock absorber for reduce movement of RCC building during lateral load acting during earthquake or high wind speed.  Fluid viscous dampers are the more effective absorbers for RCC building. 4. REFERENCE 1] Milton Fernandes 1, Swane Rodrigues 2, Suraj Sharma3, Smit Raut 4, Mr. Shreeshail Heggond 5, “Comparative Study of Seismic Behavior of High-Rise Building with and Without Use of FluidViscousDamperUsingE-Tabs”, International Journal of Innovations in Engineering and Science, www.ijies.net, e-ISSN: 2456-3463 Vol. 6, No. 5, 2021, PP. 22 -30 2] Daniel C, Arunraj E, Vincent Sam Jebadurai S,Joel Shelton J, Hemalatha G, “Dynamic Analysis of Structure using Fluid Viscous Damper for Various Seismic Intensities”, International Journal of Innovative Technology and Exploring Engineering (IJITEE) ISSN: 2278-3075, Volume-9 Issue-1, November 2019 3] Vibha More, Dr. Vikram Patil, Somanagouda Takkalaki, “Dynamic Analysis of RCC Frame Structures with and Without ViscousDamperHavingDifferentAspectRatio”, IJISET - International Journal of Innovative Science, Engineering & Technology,Vol.6Issue10,October2019 ISSN (Online) 2348 – 7968 | Impact Factor (2019) – 6.248 4] N. Priyanka, Dr. J. Thivya, J. Vijayaraghavan, “SEISMIC STUDY OF MULTI-STOREY STRUCTURE WITH FLUID VISCOUS DAMPERS USING ETABS”, International Research Journal of Engineering and Technology (IRJET), Volume: 06 Issue: 04 | Apr 2019. 5] Madhuri S L, Lakshmi P S, “Seismic Performance Evaluation of Fluid viscous Damper”, International Journal of Advances in Engineering and Management (IJAEM), Volume 4, Issue 7 July 2022. 6] IS 1893 Part 1 (2016) 7] IS 875 Part 1 (1987) 8] IS 875 Part 2 (1987) © 2024, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 37