BUILDING SERVICES ENGINEERING’13
RITESH G. AMBADKAR(123)
AKASH (118)
ROSHAN (129)
ABHIJIT BISWAS (124)
MANOJ PIKLE (121)
HARSHAL DEKATE (125)
(ELECTRICAL ENGG. DEPT)
} Ramteke
 Most domestic premises receive a single-
phase supply of electricity from an area
electricity board at a rating of 240 volts and
frequency of 50 hertz.
 The area electricity board's cable, from which
the domestic supply is taken, consists of four
lines, three lines each carrying a 240 volt
supply and the fourth is the common return
line or neutral
25-Apr-13 2
 Neutral is connected to earth at the
transformer or substation as a safety
precaution should a fault occur on the
electrical appliance.
 Each line or phase is tapped in turn together
with the neutral to provide the single-phase
240V supply
25-Apr-13 3
 The supply or intake cable may enter
building in two ways
I. Underground duct
II. Overhead supply.
 An underground supply is preferred since all
of the electrical service is hidden.
25-Apr-13 4
25-Apr-13 5
 From the sealing chamber the supply passes
through the meter, which records the
electricity consumed in units of
kilowatt/hours, to the consumer unit which
has a switch controlling the supply to
the circuit breakers or circuit fuses
 These fuses are a protection against excess
current or overload, the fuse or circuit
breaker will isolate the circuit from the source
of the problem.
25-Apr-13 6
 The consumer unit should be fitted close to
the point of service entry and from here the
service is divided into a number of sub-
circuits.
 It is normal in a domestic installation to
separate power circuits and lighting circuits
so that if a fault occurs then not all socket
outlets or lights are isolated.
25-Apr-13 7
 Sometimes an external cabinet is used for
easy meter reading.This is located in an
outside wall as shown below.
EXTERNALCABINET
25-Apr-13 8
 When deciding on the number of circuits for a
house, a useful rule is; one power circuit for
every 100m2 of floor area.
 In larger houses this means that two circuits
can be used for power socket outlets, in a
two-storey house this would be one circuit for
upstairs and one for downstairs.
 In some larger houses a separate power
circuit is also installed for the garage / utility
area
25-Apr-13 9
 In all domestic installations a separate power
circuit is required for the cooker since the
electrical demand is likely to be high.The
immersion heater in the hot water cylinder
can also be supplied from a separate circuit
since a 3kW load is quite high.
 Ring circuits are used as a safe and economic
method of distribution of electricity to socket
outlets.
 Many consumer unit manufacturers produce
8 way and 12 way units.
25-Apr-13 10
25-Apr-13 11
25-Apr-13 12
 Protection against electric shock is provided
by insulating and placing live parts out of
reach in suitable enclosures, earthing and
bonding metal work and providing fuses or
circuit breakers.
 A fuse or miniature circuit breaker (MCB) will
disconnect the supply automatically before
the overload current can cause a rise in
temperature which would damage the
installation.
25-Apr-13 13
 An isolator is a mechanical device, which is
opened manually and is provided so that the
whole of the installation, one circuit or one
piece of equipment may be cut off from the
live supply.
 In addition, a means of switching off for
maintenance or emergency switching must
also be provided.
 In practice it is the aim to bring the Electrical
supply to the appliance with as small a loss of
voltage through the conductor as possible.
 This means that the wiring must have the
smallest resistance that is economical
25-Apr-13 14
 The electrical distribution system in high rise
flats and office buildings uses a busbar system.
 A busbar is a solid copper bar that carries the
electrical current.
 The busbars run vertically inside trunking and
are supported by insulated bars across the
trunking chamber.
 The electrical supply to each floor is connected
to the rising main by means of tap-off units.
25-Apr-13 15
 To balance electrical distribution across the
phases, connections at each floor should be
spread between the phase bars.
 To prevent the spread of fire and smoke, fire
barriers are incorporated with the busbar
chamber at each compartment floor level.
 The chamber must also be fire stopped to the
full depth of the floor.
25-Apr-13 16
 The types of light fitting that we use in modern
buildings can be divided into five sections.
1. Decorative lighting
2. Commercial lighting
3. Industrial lighting
4. Outdoor lighting
5. Emergency lighting
25-Apr-13 17
Quantity of light
 The amount of light emitted from a light
fitting is given in lumens (lm).
 A lumen is the unit of luminous flux.
 The amount of light falling on a surface is
measured in lux.
 One lux is equal to 1 lumen per square metre
…….. 1 lux = 1 lm/m2.
25-Apr-13 18
Illuminance (lux) Activity Area
100 Casual seeing Corridors, changing rooms, stores
150 Some perception of detail Loading bays, switch rooms, plant rooms
200 Continuously occupied Foyers, entrance halls, dining rooms
300 Visual tasks moderately easy Libraries, sports halls, lecture theatres.
500 Visual tasks moderately difficult
General offices, kitchens, laboratories, retail
shops.
750 Visual tasks difficult Drawing offices, meat inspection, chain stores.
1000 Visual tasks very difficult
General inspection, electronic assembly,
paintwork, supermarkets.
1500 Visual tasks extremely difficult Fine work and inspection, precision assembly.
2000 Visual tasks exceptionally difficult
Assembly of minute items, finished fabric
inspection.
25-Apr-13 19
ND PHTGRPHY25-Apr-13 20
25-Apr-13 21

More Related Content

PPTX
Electrical services
PPTX
Electrical services
PDF
Electrical services design ppt pdf
PPTX
Electrification of multistore building
PPTX
Building Services Electrical (MEP)
PPTX
Electrical Systems: Designing electrical rooms
PDF
BUILDING SERVICES-II (ELECTRICAL)
PPTX
MEP & Construction Package
Electrical services
Electrical services
Electrical services design ppt pdf
Electrification of multistore building
Building Services Electrical (MEP)
Electrical Systems: Designing electrical rooms
BUILDING SERVICES-II (ELECTRICAL)
MEP & Construction Package

What's hot (20)

PPTX
Electrical services
PPTX
Electrical services of bs by krt
PPTX
Electrical Systems in a Building
PPTX
Building Services
PPTX
electrical lighting calculation
PPTX
Electrical wiring system
PPTX
Wiring system building services
PDF
Building Electrical Systems Design
PPTX
ELECTRICAL LAYOUT SYSTEM
PPTX
Fire fighting system in buildings
PPTX
Electrical Installation in Buildings
PPTX
Lighting Design - Theory and Calculations
PPTX
Electrical installation for commercial & public building
PPTX
MEP- Building services
PDF
Electrical system design of garden project at belhaven (10 Storey High Rise B...
PPTX
Electrical wiring
PDF
Introduction To Building Services
PPT
Distribution board
PPTX
Electrical lighting design and calculations
PPTX
NBC NORMS FOR HVAC SYSTEMS
Electrical services
Electrical services of bs by krt
Electrical Systems in a Building
Building Services
electrical lighting calculation
Electrical wiring system
Wiring system building services
Building Electrical Systems Design
ELECTRICAL LAYOUT SYSTEM
Fire fighting system in buildings
Electrical Installation in Buildings
Lighting Design - Theory and Calculations
Electrical installation for commercial & public building
MEP- Building services
Electrical system design of garden project at belhaven (10 Storey High Rise B...
Electrical wiring
Introduction To Building Services
Distribution board
Electrical lighting design and calculations
NBC NORMS FOR HVAC SYSTEMS
Ad

Viewers also liked (20)

PPSX
Building services
PPT
Introduction to building services part 2
DOC
ELECTRICAL WIRING
PDF
GIT Model Paper
PDF
Wastewater Generation and Management in Underground Utility Vaults and Manholes
PPT
Heat emitters
PDF
Home electrical installations
PPTX
Slide: Types of Heating Systems
PPTX
Sewer Appurtenances
PPT
Domestic electrical systems
PDF
Telecommunication Services for High Rise Buildings
PPTX
Design of staircases
PPTX
electricity supply ppt
PPTX
Luminance and Illuminance
PPSX
Illumination
PPT
Illumination
PPSX
Illumination - Types of lamps
PPT
Electrical Wiring Practices and Diagrams
Building services
Introduction to building services part 2
ELECTRICAL WIRING
GIT Model Paper
Wastewater Generation and Management in Underground Utility Vaults and Manholes
Heat emitters
Home electrical installations
Slide: Types of Heating Systems
Sewer Appurtenances
Domestic electrical systems
Telecommunication Services for High Rise Buildings
Design of staircases
electricity supply ppt
Luminance and Illuminance
Illumination
Illumination
Illumination - Types of lamps
Electrical Wiring Practices and Diagrams
Ad

Similar to Building Services Engg. (Electrical installations) (20)

PPTX
buildinggroupppt-130512115915-phpapp02.pptx
PPTX
buildinggroupppt-130512115915-phpapp02.pptx
PPTX
Residential Electrical Equipments and Services.pptx
PPTX
Slide Presentation of Electrical System.
PPS
Electrical wiring domestic and industries
PPTX
MODULd. Fdcc. FffffffrrE 2 UNIT 1.pptx
PPTX
ELECTRICAL SERVICES IN BUILDING - Basics regarding electricity and electrical...
PPT
Building electric circuit
PPTX
electric sheet and its uses the of electric
PDF
Lighting Presentation about designing.pdf
PPTX
electric and sanitary.pptx
PPTX
UNII II ELECTRICAL SYSTEMS IN BUILDINGS
PPTX
UNIT-2.pptx
PPTX
P13 Electrical Installtions.pptx
PPTX
illumination scheme
PDF
Residential Electrical Wiring Systems Basics
DOCX
PDF
Building services project2
DOCX
Module 5 module 3 draft electrical and electronic layout and details
DOCX
Module 5 module 3 draft electrical and electronic layout and details
buildinggroupppt-130512115915-phpapp02.pptx
buildinggroupppt-130512115915-phpapp02.pptx
Residential Electrical Equipments and Services.pptx
Slide Presentation of Electrical System.
Electrical wiring domestic and industries
MODULd. Fdcc. FffffffrrE 2 UNIT 1.pptx
ELECTRICAL SERVICES IN BUILDING - Basics regarding electricity and electrical...
Building electric circuit
electric sheet and its uses the of electric
Lighting Presentation about designing.pdf
electric and sanitary.pptx
UNII II ELECTRICAL SYSTEMS IN BUILDINGS
UNIT-2.pptx
P13 Electrical Installtions.pptx
illumination scheme
Residential Electrical Wiring Systems Basics
Building services project2
Module 5 module 3 draft electrical and electronic layout and details
Module 5 module 3 draft electrical and electronic layout and details

Building Services Engg. (Electrical installations)

  • 1. BUILDING SERVICES ENGINEERING’13 RITESH G. AMBADKAR(123) AKASH (118) ROSHAN (129) ABHIJIT BISWAS (124) MANOJ PIKLE (121) HARSHAL DEKATE (125) (ELECTRICAL ENGG. DEPT) } Ramteke
  • 2.  Most domestic premises receive a single- phase supply of electricity from an area electricity board at a rating of 240 volts and frequency of 50 hertz.  The area electricity board's cable, from which the domestic supply is taken, consists of four lines, three lines each carrying a 240 volt supply and the fourth is the common return line or neutral 25-Apr-13 2
  • 3.  Neutral is connected to earth at the transformer or substation as a safety precaution should a fault occur on the electrical appliance.  Each line or phase is tapped in turn together with the neutral to provide the single-phase 240V supply 25-Apr-13 3
  • 4.  The supply or intake cable may enter building in two ways I. Underground duct II. Overhead supply.  An underground supply is preferred since all of the electrical service is hidden. 25-Apr-13 4
  • 6.  From the sealing chamber the supply passes through the meter, which records the electricity consumed in units of kilowatt/hours, to the consumer unit which has a switch controlling the supply to the circuit breakers or circuit fuses  These fuses are a protection against excess current or overload, the fuse or circuit breaker will isolate the circuit from the source of the problem. 25-Apr-13 6
  • 7.  The consumer unit should be fitted close to the point of service entry and from here the service is divided into a number of sub- circuits.  It is normal in a domestic installation to separate power circuits and lighting circuits so that if a fault occurs then not all socket outlets or lights are isolated. 25-Apr-13 7
  • 8.  Sometimes an external cabinet is used for easy meter reading.This is located in an outside wall as shown below. EXTERNALCABINET 25-Apr-13 8
  • 9.  When deciding on the number of circuits for a house, a useful rule is; one power circuit for every 100m2 of floor area.  In larger houses this means that two circuits can be used for power socket outlets, in a two-storey house this would be one circuit for upstairs and one for downstairs.  In some larger houses a separate power circuit is also installed for the garage / utility area 25-Apr-13 9
  • 10.  In all domestic installations a separate power circuit is required for the cooker since the electrical demand is likely to be high.The immersion heater in the hot water cylinder can also be supplied from a separate circuit since a 3kW load is quite high.  Ring circuits are used as a safe and economic method of distribution of electricity to socket outlets.  Many consumer unit manufacturers produce 8 way and 12 way units. 25-Apr-13 10
  • 13.  Protection against electric shock is provided by insulating and placing live parts out of reach in suitable enclosures, earthing and bonding metal work and providing fuses or circuit breakers.  A fuse or miniature circuit breaker (MCB) will disconnect the supply automatically before the overload current can cause a rise in temperature which would damage the installation. 25-Apr-13 13
  • 14.  An isolator is a mechanical device, which is opened manually and is provided so that the whole of the installation, one circuit or one piece of equipment may be cut off from the live supply.  In addition, a means of switching off for maintenance or emergency switching must also be provided.  In practice it is the aim to bring the Electrical supply to the appliance with as small a loss of voltage through the conductor as possible.  This means that the wiring must have the smallest resistance that is economical 25-Apr-13 14
  • 15.  The electrical distribution system in high rise flats and office buildings uses a busbar system.  A busbar is a solid copper bar that carries the electrical current.  The busbars run vertically inside trunking and are supported by insulated bars across the trunking chamber.  The electrical supply to each floor is connected to the rising main by means of tap-off units. 25-Apr-13 15
  • 16.  To balance electrical distribution across the phases, connections at each floor should be spread between the phase bars.  To prevent the spread of fire and smoke, fire barriers are incorporated with the busbar chamber at each compartment floor level.  The chamber must also be fire stopped to the full depth of the floor. 25-Apr-13 16
  • 17.  The types of light fitting that we use in modern buildings can be divided into five sections. 1. Decorative lighting 2. Commercial lighting 3. Industrial lighting 4. Outdoor lighting 5. Emergency lighting 25-Apr-13 17
  • 18. Quantity of light  The amount of light emitted from a light fitting is given in lumens (lm).  A lumen is the unit of luminous flux.  The amount of light falling on a surface is measured in lux.  One lux is equal to 1 lumen per square metre …….. 1 lux = 1 lm/m2. 25-Apr-13 18
  • 19. Illuminance (lux) Activity Area 100 Casual seeing Corridors, changing rooms, stores 150 Some perception of detail Loading bays, switch rooms, plant rooms 200 Continuously occupied Foyers, entrance halls, dining rooms 300 Visual tasks moderately easy Libraries, sports halls, lecture theatres. 500 Visual tasks moderately difficult General offices, kitchens, laboratories, retail shops. 750 Visual tasks difficult Drawing offices, meat inspection, chain stores. 1000 Visual tasks very difficult General inspection, electronic assembly, paintwork, supermarkets. 1500 Visual tasks extremely difficult Fine work and inspection, precision assembly. 2000 Visual tasks exceptionally difficult Assembly of minute items, finished fabric inspection. 25-Apr-13 19