Notifier NCM Installation

Network Communications Module (NCM) provides a means for connecting specific Notifier fire alarm control products to NOTI fire NET(tm) There are two types of NCMs available: NCM-W for connecting nodes with twisted-pair wire, and NCM-F for connecting node with fiber-optic cable.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
6K views5 pages

Notifier NCM Installation

Network Communications Module (NCM) provides a means for connecting specific Notifier fire alarm control products to NOTI fire NET(tm) There are two types of NCMs available: NCM-W for connecting nodes with twisted-pair wire, and NCM-F for connecting node with fiber-optic cable.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

12 Clintonville Road

Northford, CT 06472-1653 USA


[Link]

NCM Installation Document


Network Communications Module NCM-W, NCM-F
PN 51533:A 06/29/01 ECN 01-245

1 Product Overview
The Network Communications Module (NCM) provides a means for connecting specific Notifier fire
alarm control products to NOTI•FIRE•NET™. There are two types of NCMs available: NCM-W for
connecting nodes with twisted-pair wire, and NCM-F for connecting nodes with fiber-optic cable.

1.1 The Network Communications Module for Wire (NCM-W)


Ground Fault • Supports twisted-pair wire medium.
Detection • NFPA Style 4 (Class B) operation or NFPA Style 7 (Class
Channel
Switches
A&B A) operation.
and
Connections
E F B TE RM B E F A TE RM A

• Two programmable data thresholds.


O FF

O FF
S W 101

S W 1 02

S W 103

S W 1 00

Network
ON

ON

End-of-Line • Transformer coupling provides electrical isolation


Termination between nodes.
Resistor • Pluggable terminal wiring with strain relief.
Switches J3 J2
Network • Pluggable service connector (feeds signal directly
LED 101 LED 100

A HI B HI
LED 6 LED 7

Connection
N U P2

N U P1

RCD A RCD B

through) in the event that power must be removed from a


LED 4 LED 2

STATA STATB
LED 3 LED 5

RECON PULS E1
LED 1 LED 8 Ports
node.
LC M A

RESET POW ER

(NUP)
Diagnostic • 312.5 Kbaud transmission rate.
LEDs • Data is regenerated at each node.
LC M B

• Two network ports to allow simultaneous connection to


L C M TE R M
A A

fire alarm control panel and to programming computer


[Link]

O FF
ON
SW 1

SW2

• Enables software and database upload/download over


Not used NOTI•FIRE•NET™.
• Refer to the NOTI•FIRE•NET™ manual for wiring
Figure 1 NCM-W length and threshold information.

1.2 The Network Communications Module for Fiber (NCM-F)


Channel • Supports fiber-optic medium.
A&B • NFPA Style 4 (Class B) or Style 7 (Class A) operation.
Connections • Data is immune to all environmental noise.
• Optical isolation prevents ground loops.
J 2 02

J 2 01

J 2 00

NOTI•FIRE•NET™ fiber optic medium.


RX TX RX TX
J 20 3


Network
J3 J2

• Fiber type:
LED 6 LED 7

Connection
N U P2

N U P1

• 62.5/125 micrometers (multimode)


RCDA RCDB
LED 4 LED 2

STATA
LED 3
STATB
LED 5

RECON PULSE 1
Ports
• 50/125 micrometers (multimode)
LED 1 LED 8

(NUP)
LCM A

RESET POW ER

Diagnostic • Wavelength (1): 820 nanometers. (Use standard 850 nm


LEDs fiber.)
LCM B

L C M TE R M
• Connectors: ST® Style (ST® is a registered trademark of
A A

AT&T).
[Link]

O FF
ON
SW 1

SW2

• 312.5 Kbaud transmission rate.


Not used • Data is regenerated at each node.
• Two network ports to allow simultaneous connection to
Figure 2 NCM-F fire alarm control panel and to programming computer.
• Enables software and database upload/download over
NOTI•FIRE•NET™.

NCM Installation PN 51533:A 06/29/01


2 Installing the NCM
2.1 Interconnecting the NCM-W
When wiring consecutive NCM-W boards, note that wiring may enter or exit at Port A or Port B as
shown in Figure 4. NCM-W port-to-port wiring is not polarity sensitive. The use of Port A or Port B is
arbitrary. An NCM-W may be connected to any of the following devices:
• MIB-W
• MIB-WF
• NAM-232W
• NCM-W (in another panel)
• NCS-W network connection
• RPT-W
• RPT-WF
For information regarding these devices, refer to the documentation listed in Table 4 “Supplemental
Documentation”.

From last node, To next node,


Port A Port B

B A
B A

[Link]
EF B T ER M B EF A T ER M A EF B T ER M B EF A T ER M A
O FF

O FF

O FF

O FF
S W 101

S W 10 2

S W 103

S W 10 0

S W 101

S W 10 2

S W 103

S W 10 0
ON

ON

ON

ON
Note: Wiring from the NCM-W that is installed outside the building:
• Cannot exceed 1000m (3280 ft.).
• Must be in conduit and is to be buried in a trench separate from any power lines.
• Cannot cross any power lines.
Figure 3 The NCM-W

TB100-1 CH-A (+) Channel-A Driver/Receiver


TB100-2 CH-A (-) Channel-A Driver/Receiver
TB100-3 CH-B (+) Channel-B Driver/Receiver
TB100-4 CH-B (-) Channel-B Driver/Receiver
TB100-5 Earth Ground

Table 1 NOTI•FIRE•NET™ Connections: NCM-W

Switch Functions: Ground Fault Detection and Line Termination


The NCM-W provides two sets of switches to simplify
EF B TER M B EF A TE R M A
network setup; in Figure 4 all are in the “off” position.
OFF

OFF
S W 1 01

S W 1 03
S W 102

S W 100

• Enable ground fault detection by setting


ON

ON

switches “on”: SW103 for Channel A, and


[Link]

SW101 for Channel B.


• Activate on-board end-of-line resistors by
setting switches “on”: SW100 for Channel A;
SW102 for Channel B.
Figure 4 NCM-W Switches
Note: Correct configuration depends on your network
design; refer to the NOTI•FIRE•NET™ manual.

2 NCM Installation PN 51533:A 06/29/01


2.2 Interconnecting the NCM-F
When connecting consecutive nodes/repeaters, note that fiber cable must exit one board on transmit
(TX) and enter the next node/repeater on receive (RX). Also, note that the fiber-optic pair (RX, TX)
from port A of one Node/Repeater may be connected to either Port A or Port B of another node/repeater
(refer to Figure 5). An NCM-F may be connected to any of the following devices:
• MIB-F
• MIB-WF
• NAM-232F
• Another NCM-F
• Network connection for NCS-F
• RPT-F
• RPT-WF
For information regarding these devices, refer to the NAM-232 and Repeater manuals listed in
Table 4 “Supplemental Documentation”.
Note: See the NOTI•FIRE•NET™ Network Version 4.0 Manual for maximum fiber-optic cable
attenuation.

[Link]
J20 2

J20 1

J20 0

J20 2

J20 1

J20 0
RX TX RX TX RX TX RX TX
J 203 J 203

RxB TxB RxA TxA RxB TxB RxA TxA


Channel Channel Channel Channel
B A B A

Figure 5 NCM-F Connection

J200 CH A Transmit
J201 CH A Receive
J202 CH B Transmit
J203 CH B Receive

Table 2 NOTI•FIRE•NET™ Connections: NCM-F

2.3 Mixing Wire & Fiber on One Network


In some networks, it may be necessary to mix twisted-pair wire and fiber-optic cable. There are two
solutions for this situation.
1. In any network, an RPT-WF may be used as an interface between wire and fiber.
2. In a network that uses an AFP1010 or AM2020, a MIB-WF may also be used as the interface
between wire and fiber.
See 1.2 “The Network Communications Module for Fiber (NCM-F)” for requirements and restrictions
on the use of fiber optic cable. See the NOTI•FIRE•NET™ Manual (Network Version 4.0) for a
discussion of all compatible configurations.

NCM Installation PN 51533:A 06/29/01 3


3 Diagnostic Indicators
The NCM has LEDs that serve as diagnostic indicators to help in troubleshooting and system
connection. Refer to Table 3 for a list of diagnostic indicators and their descriptions. Refer to Figure 6
for location of the diagnostic indicators.

A HI (NCM-W only) B HI (NCM-W only)

RCD A RCD B
A HI B HI
STATA PULSE1
RCD A RCD B
RECON STATB
STATA STATB
RESET POWER
RECO N PULSE1

[Link]
RESET POW ER

Figure 6 Diagnostic Indicator Locations

LED Indicator LED Color LED Description

A HI Green Illuminates to indicate the NCM-W Port A is set for high threshold.
(NCM-W only)
B HI Green Illuminates to indicate the NCM-W Port B is set for high threshold.
(NCM-W only)
RCD A Green Illuminates when the NCM is receiving data from
NOTI•FIRE•NET™ on Port A.
RCD B Green Illuminates when the NCM is receiving data from
NOTI•FIRE•NET™ on Port B.
STATA Yellow Illuminates when the NCM has not received valid data from
NOTI•FIRE•NET™ on Port A for at least 16 seconds.
STATB Yellow Illuminates when the NCM has not received valid data from
NOTI•FIRE•NET™ on Port B for at least 16 seconds.
RECON Yellow Illuminates when a reconfiguration on NOTI•FIRE•NET™ is in
progress.
PULSE1 Green Illuminates when the NCM is transmitting data to
NOTI•FIRE•NET™.
RESET Yellow Illuminates when the microcontroller fails.
POWER Green Illuminates when +5 VDC is available

Table 3 Diagnostic Indicator Functions and Colors

4 NCM Installation PN 51533:A 06/29/01


4 Door-Mounting
Both NCM-W and NCM-F can be installed in any panel circuit module position; see your control panel
installation manual. Additionally, the NCM-W can be door-mounted on the ADP-4B Dress Panel on a
single-space blank plate (BMP-1) for mounting in a CAB-4 Series cabinet.
Note: The module cannot be mounted in the ADP-4B Dress Panel when a front slot of the CHS-4 or
CHS-4N is occupied, or when either of the two front right positions of the CHS-M2 is occupied.
Always be certain there is enough clearance to close the cabinet door when this installation is used.

[Link]
Single-space
blank plate

Mount a single-space blank


plate onto the ADP-4B Dress
Panel.
Fasten module to the plate
with four screws (included).

5 Supplemental Documentation
The table below provides a list of document sources (manuals) containing additional information
regarding the NCM and products that it can connect to. The NOTIFIER document (DOC-NOT) chart
provides the current document revision.

For information on… Refer to… Part No.

Networking NOTI•FIRE•NET™ Manual: Network Version 4.0 51584


NCS Network Control Station: Network Version 4.0 51585
NFS-640 Installation 51332
Operations 51333
Programming 51334
NCA Network Control Annunciator 51482
Media Interface Board (MIB) Manual 50255
NAM-232 Network Adaptor Module 50038
RPT - W/WF/F Repeaters for NOTI•FIRE•NET™ 50256

Off-line Programming Utility Veri•Fire Tools CD on-line help file Veri•Fire-TCD


Compatible Devices Device Compatibility Document 15378
Cabinets & Chassis CAB-3/CAB-4 Series Installation Document 15330
BMP-1 Product Installation Document 51119
Table 4 Supplemental Documentation

Note: For module mounting instructions, refer to the documentation for your control panel

NCM Installation PN 51533:A 06/29/01 5