NCM Installation Document
Network Communications Module NCM-W, NCM-F
PN 51533:A 06/29/01 ECN 01-245
1 Product Overview
The Network Communications Module (NCM) provides a means for connecting specific Notifier fire
alarm control products to NOTI•FIRE•NET™. There are two types of NCMs available: NCM-W for
connecting nodes with twisted-pair wire, and NCM-F for connecting nodes with fiber-optic cable.
1.1 The Network Communications Module for Wire (NCM-W)
Ground Fault • Supports twisted-pair wire medium.
Detection • NFPA Style 4 (Class B) operation or NFPA Style 7 (Class
Channel
Switches
A&B A) operation.
and
Connections
E F B TE RM B E F A TE RM A
• Two programmable data thresholds.
O FF
O FF
S W 101
S W 1 02
S W 103
S W 1 00
Network
ON
ON
End-of-Line • Transformer coupling provides electrical isolation
Termination between nodes.
Resistor • Pluggable terminal wiring with strain relief.
Switches J3 J2
Network • Pluggable service connector (feeds signal directly
LED 101 LED 100
A HI B HI
LED 6 LED 7
Connection
N U P2
N U P1
RCD A RCD B
through) in the event that power must be removed from a
LED 4 LED 2
STATA STATB
LED 3 LED 5
RECON PULS E1
LED 1 LED 8 Ports
node.
LC M A
RESET POW ER
(NUP)
Diagnostic • 312.5 Kbaud transmission rate.
LEDs • Data is regenerated at each node.
LC M B
• Two network ports to allow simultaneous connection to
L C M TE R M
A A
fire alarm control panel and to programming computer
[Link]
O FF
ON
SW 1
SW2
• Enables software and database upload/download over
Not used NOTI•FIRE•NET™.
• Refer to the NOTI•FIRE•NET™ manual for wiring
Figure 1 NCM-W length and threshold information.
1.2 The Network Communications Module for Fiber (NCM-F)
Channel • Supports fiber-optic medium.
A&B • NFPA Style 4 (Class B) or Style 7 (Class A) operation.
Connections • Data is immune to all environmental noise.
• Optical isolation prevents ground loops.
J 2 02
J 2 01
J 2 00
NOTI•FIRE•NET™ fiber optic medium.
RX TX RX TX
J 20 3
•
Network
J3 J2
• Fiber type:
LED 6 LED 7
Connection
N U P2
N U P1
• 62.5/125 micrometers (multimode)
RCDA RCDB
LED 4 LED 2
STATA
LED 3
STATB
LED 5
RECON PULSE 1
Ports
• 50/125 micrometers (multimode)
LED 1 LED 8
(NUP)
LCM A
RESET POW ER
Diagnostic • Wavelength (1): 820 nanometers. (Use standard 850 nm
LEDs fiber.)
LCM B
L C M TE R M
• Connectors: ST® Style (ST® is a registered trademark of
A A
AT&T).
[Link]
O FF
ON
SW 1
SW2
• 312.5 Kbaud transmission rate.
Not used • Data is regenerated at each node.
• Two network ports to allow simultaneous connection to
Figure 2 NCM-F fire alarm control panel and to programming computer.
• Enables software and database upload/download over
NOTI•FIRE•NET™.
NCM Installation PN 51533:A 06/29/01
2 Installing the NCM
2.1 Interconnecting the NCM-W
When wiring consecutive NCM-W boards, note that wiring may enter or exit at Port A or Port B as
shown in Figure 4. NCM-W port-to-port wiring is not polarity sensitive. The use of Port A or Port B is
arbitrary. An NCM-W may be connected to any of the following devices:
• MIB-W
• MIB-WF
• NAM-232W
• NCM-W (in another panel)
• NCS-W network connection
• RPT-W
• RPT-WF
For information regarding these devices, refer to the documentation listed in Table 4 “Supplemental
Documentation”.
From last node, To next node,
Port A Port B
B A
B A
[Link]
EF B T ER M B EF A T ER M A EF B T ER M B EF A T ER M A
O FF
O FF
O FF
O FF
S W 101
S W 10 2
S W 103
S W 10 0
S W 101
S W 10 2
S W 103
S W 10 0
ON
ON
ON
ON
Note: Wiring from the NCM-W that is installed outside the building:
• Cannot exceed 1000m (3280 ft.).
• Must be in conduit and is to be buried in a trench separate from any power lines.
• Cannot cross any power lines.
Figure 3 The NCM-W
TB100-1 CH-A (+) Channel-A Driver/Receiver
TB100-2 CH-A (-) Channel-A Driver/Receiver
TB100-3 CH-B (+) Channel-B Driver/Receiver
TB100-4 CH-B (-) Channel-B Driver/Receiver
TB100-5 Earth Ground
Table 1 NOTI•FIRE•NET™ Connections: NCM-W
Switch Functions: Ground Fault Detection and Line Termination
The NCM-W provides two sets of switches to simplify
EF B TER M B EF A TE R M A
network setup; in Figure 4 all are in the “off” position.
OFF
OFF
S W 1 01
S W 1 03
S W 102
S W 100
• Enable ground fault detection by setting
ON
ON
switches “on”: SW103 for Channel A, and
[Link]
SW101 for Channel B.
• Activate on-board end-of-line resistors by
setting switches “on”: SW100 for Channel A;
SW102 for Channel B.
Figure 4 NCM-W Switches
Note: Correct configuration depends on your network
design; refer to the NOTI•FIRE•NET™ manual.
2 NCM Installation PN 51533:A 06/29/01
2.2 Interconnecting the NCM-F
When connecting consecutive nodes/repeaters, note that fiber cable must exit one board on transmit
(TX) and enter the next node/repeater on receive (RX). Also, note that the fiber-optic pair (RX, TX)
from port A of one Node/Repeater may be connected to either Port A or Port B of another node/repeater
(refer to Figure 5). An NCM-F may be connected to any of the following devices:
• MIB-F
• MIB-WF
• NAM-232F
• Another NCM-F
• Network connection for NCS-F
• RPT-F
• RPT-WF
For information regarding these devices, refer to the NAM-232 and Repeater manuals listed in
Table 4 “Supplemental Documentation”.
Note: See the NOTI•FIRE•NET™ Network Version 4.0 Manual for maximum fiber-optic cable
attenuation.
[Link]
J20 2
J20 1
J20 0
J20 2
J20 1
J20 0
RX TX RX TX RX TX RX TX
J 203 J 203
RxB TxB RxA TxA RxB TxB RxA TxA
Channel Channel Channel Channel
B A B A
Figure 5 NCM-F Connection
J200 CH A Transmit
J201 CH A Receive
J202 CH B Transmit
J203 CH B Receive
Table 2 NOTI•FIRE•NET™ Connections: NCM-F
2.3 Mixing Wire & Fiber on One Network
In some networks, it may be necessary to mix twisted-pair wire and fiber-optic cable. There are two
solutions for this situation.
1. In any network, an RPT-WF may be used as an interface between wire and fiber.
2. In a network that uses an AFP1010 or AM2020, a MIB-WF may also be used as the interface
between wire and fiber.
See 1.2 “The Network Communications Module for Fiber (NCM-F)” for requirements and restrictions
on the use of fiber optic cable. See the NOTI•FIRE•NET™ Manual (Network Version 4.0) for a
discussion of all compatible configurations.
NCM Installation PN 51533:A 06/29/01 3
3 Diagnostic Indicators
The NCM has LEDs that serve as diagnostic indicators to help in troubleshooting and system
connection. Refer to Table 3 for a list of diagnostic indicators and their descriptions. Refer to Figure 6
for location of the diagnostic indicators.
A HI (NCM-W only) B HI (NCM-W only)
RCD A RCD B
A HI B HI
STATA PULSE1
RCD A RCD B
RECON STATB
STATA STATB
RESET POWER
RECO N PULSE1
[Link]
RESET POW ER
Figure 6 Diagnostic Indicator Locations
LED Indicator LED Color LED Description
A HI Green Illuminates to indicate the NCM-W Port A is set for high threshold.
(NCM-W only)
B HI Green Illuminates to indicate the NCM-W Port B is set for high threshold.
(NCM-W only)
RCD A Green Illuminates when the NCM is receiving data from
NOTI•FIRE•NET™ on Port A.
RCD B Green Illuminates when the NCM is receiving data from
NOTI•FIRE•NET™ on Port B.
STATA Yellow Illuminates when the NCM has not received valid data from
NOTI•FIRE•NET™ on Port A for at least 16 seconds.
STATB Yellow Illuminates when the NCM has not received valid data from
NOTI•FIRE•NET™ on Port B for at least 16 seconds.
RECON Yellow Illuminates when a reconfiguration on NOTI•FIRE•NET™ is in
progress.
PULSE1 Green Illuminates when the NCM is transmitting data to
NOTI•FIRE•NET™.
RESET Yellow Illuminates when the microcontroller fails.
POWER Green Illuminates when +5 VDC is available
Table 3 Diagnostic Indicator Functions and Colors
4 NCM Installation PN 51533:A 06/29/01
4 Door-Mounting
Both NCM-W and NCM-F can be installed in any panel circuit module position; see your control panel
installation manual. Additionally, the NCM-W can be door-mounted on the ADP-4B Dress Panel on a
single-space blank plate (BMP-1) for mounting in a CAB-4 Series cabinet.
Note: The module cannot be mounted in the ADP-4B Dress Panel when a front slot of the CHS-4 or
CHS-4N is occupied, or when either of the two front right positions of the CHS-M2 is occupied.
Always be certain there is enough clearance to close the cabinet door when this installation is used.
[Link]
Single-space
blank plate
Mount a single-space blank
plate onto the ADP-4B Dress
Panel.
Fasten module to the plate
with four screws (included).
5 Supplemental Documentation
The table below provides a list of document sources (manuals) containing additional information
regarding the NCM and products that it can connect to. The NOTIFIER document (DOC-NOT) chart
provides the current document revision.
For information on… Refer to… Part No.
Networking NOTI•FIRE•NET™ Manual: Network Version 4.0 51584
NCS Network Control Station: Network Version 4.0 51585
NFS-640 Installation 51332
Operations 51333
Programming 51334
NCA Network Control Annunciator 51482
Media Interface Board (MIB) Manual 50255
NAM-232 Network Adaptor Module 50038
RPT - W/WF/F Repeaters for NOTI•FIRE•NET™ 50256
Off-line Programming Utility Veri•Fire Tools CD on-line help file Veri•Fire-TCD
Compatible Devices Device Compatibility Document 15378
Cabinets & Chassis CAB-3/CAB-4 Series Installation Document 15330
BMP-1 Product Installation Document 51119
Table 4 Supplemental Documentation
Note: For module mounting instructions, refer to the documentation for your control panel