E = Voltage / I = Amps /W = Watts / PF = Power Factor / Eff = Efficiency / HP =
Horsepower
AC/DC Formulas
To Find Direct AC / 1phase AC / 1phase AC 3 phase
Current 115v or 120v 208,230, or All Voltages
240v
Amps when HP x 746 HP x 746 HP x 746 HP x 746
Horsepower is E x Eff E x Eff X PF E x Eff x PF 1.73 x E x Eff x PF
Known
Amps when kW x kW x 1000 kW x 1000 kW x 1000
Kilowatts is known 1000 E x PF E x PF 1.73 x E x PF
E
Amps when kVA x 1000 kVA x 1000 kVA x 1000
kVA is known E E 1.73 x E
Kilowatts IxE I x E x PF I x E x PF I x E x 1.73 PF
1000 1000 1000 1000
Kilovolt-Amps IxE IxE I x E x 1.73
1000 1000 1000
Horsepower I x E x Eff I x E x Eff x I x E x Eff x I x E x Eff x 1.73 x
(output) 746 PF PF PF
746 746 746
Three Phase Values
For 208 volts x 1.732, use 360
For 230 volts x 1.732, use 398
For 240 volts x 1.732, use 416
For 440 volts x 1.732, use 762
For 460 volts x 1.732, use 797
For 480 Volts x 1.732, use 831
E = Voltage / I = Amps /W = Watts / PF = Power Factor / Eff = Efficiency / HP =
Horsepower
AC Efficiency and Power
Factor Formulas
Single Three
To Find
Phase Phase
746 x 746 x HP
Efficienc HP E x I x PF
y E x I x x 1.732
PF
Input Input
Power Watts Watts
Factor VxA ExIx
1.732
Power - DC Circuits
Watts = E xI
Amps = W / E
Ohm's Law / Power
Formulas
P = watts
I = amps
R=
ohms
E = Volts
Voltage Drop Formulas
2 x K x I x K = ohms per mil foot
Single VD L
Phase = CM (Copper = 12.9 at 75°)
(2 or 3 CM 2K x L x I
wire) = (Alum = 21.2 at 75°)
VD Note K value changes with temperature.
: See Code chapter 9, Table 8
VD 1.73 x K x
IxL
= CM L = Length of conductor in feet
Three
Phase CM 1.73 x K x I = Current in conductor (amperes)
LxI