Tesys LRD Thermal Overload Relays - 63... 80 A - Class 10A: Local Distributor Code: 381829586

The TeSys LRD thermal overload relays are designed for motor protection with a thermal overload class of 10A and a current adjustment range of 63...80 A. They are compatible with LC1D80 and LC1D95 devices, and feature a variety of mounting options and connection types. The product complies with multiple international standards and has a warranty of 18 months, with a commitment to sustainability through reduced environmental impact and recyclable materials.

Uploaded by

singhsunil2922
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
7 views4 pages

Tesys LRD Thermal Overload Relays - 63... 80 A - Class 10A: Local Distributor Code: 381829586

The TeSys LRD thermal overload relays are designed for motor protection with a thermal overload class of 10A and a current adjustment range of 63...80 A. They are compatible with LC1D80 and LC1D95 devices, and feature a variety of mounting options and connection types. The product complies with multiple international standards and has a warranty of 18 months, with a commitment to sustainability through reduced environmental impact and recyclable materials.

Uploaded by

singhsunil2922
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Product datasheet

Specifications

TeSys LRD thermal overload relays


- 63...80 A - class 10A
Local distributor code:
381829586 LRD3363

EAN Code: 3389110520002

Main
Range TeSys

Product name TeSys LRD


TeSys Deca

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product or component type Differential thermal overload relay

Device short name LRD

Relay application Motor protection

Product compatibility LC1D80


LC1D95

Network type DC
AC

Thermal overload class Class 10A conforming to IEC 60947-4-1

Thermal protection adjustment 63…80 A


range
[Ui] rated insulation voltage Power circuit: 1000 V conforming to IEC 60947-4-1
Power circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL

Complementary
Network frequency 0...400 Hz

Mounting support Plate, with specific accessories


Rail, with specific accessories
Under contactor

Tripping threshold 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1

Auxiliary contact composition 1 NO + 1 NC

[Ith] conventional free air thermal 5 A for signalling circuit


current
Permissible current 0.72 A at 500 V AC-15 for signalling circuit
0.06 A at 440 V DC-13 for signalling circuit

[Ue] rated operational voltage 1000 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1

Associated fuse rating 4 A gG for signalling circuit


4 A BS for signalling circuit

[Uimp] rated impulse withstand 6 kV conforming to IEC 60947-1


voltage
Phase failure sensitivity Tripping current 130 % of Ir on two phase, the last one at 0

Control type Red push-button: stop


Blue push-button: reset

Temperature compensation -20…60 °C

12 Aug 2025 1
Connections - terminals Power circuit: screw clamp terminals 1 cable(s) 4…35 mm² flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 4…35 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 4…35 mm² solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable
end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end

Tightening torque Control circuit: 1.7 N.m - on screw clamp terminals


Power circuit: 9 N.m - on screw clamp terminals

Height 81 mm

Width 70 mm

Depth 115 mm

Net weight 0.51 kg

Environment
Climatic withstand conforming to IACS E10

IP degree of protection IP20 conforming to IEC 60529

Ambient air temperature for -20…60 °C without derating conforming to IEC 60947-4-1
operation
Ambient air temperature for -60…70 °C
storage
Flame retardance V1 conforming to UL 94

Mechanical robustness Vibrations: 6 Gn conforming to IEC 60068-2-6


Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7

Dielectric strength 2.2 kV at 50 Hz conforming to IEC 60947-1

Standards EN/IEC 60947-4-1


EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
EN 50495

Product certifications IEC


UL
CSA
CCC
EAC
ATEX INERIS
UKCA

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 8.000 cm

Package 1 Width 9.000 cm

Package 1 Length 12.000 cm

Package 1 Weight 512.000 g

Unit Type of Package 2 S02

Number of Units in Package 2 12

Package 2 Height 15.000 cm

Package 2 Width 30.000 cm

Package 2 Length 40.000 cm

2 12 Aug 2025
Package 2 Weight 6.470 kg

Unit Type of Package 3 P06

Number of Units in Package 3 192

Package 3 Height 75.000 cm

Package 3 Width 60.000 cm

Package 3 Length 80.000 cm

Package 3 Weight 114.468 kg

Logistical informations
Country of origin FR

Contractual warranty
Warranty 18 months

12 Aug 2025 3
Environmental Data

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.

Environmental Data explained

How we assess product sustainability

Environmental footprint

Total lifecycle Carbon footprint 6

Environmental Disclosure Product Environmental Profile

Use Better

Materials and Substances

Packaging made with recycled cardboard Yes

Packaging without single use plastic Yes

EU RoHS Directive Compliant

Use Again

Repack and remanufacture

End of life manual availability End of Life Information

Take-back No

The product must be disposed on European Union


WEEE Label markets following specific waste collection and never end
up in rubbish bins