RA12-200
(12V200Ah)
RA12-200 is a general purpose battery with 10 years floating
design life, meet with IEC, JIS .BS and Eurobat standard. With
heavy duty grid, thickness plates, special additives, RA series
battery have long and reliable standby service life. Our RA Series
batteries keep high consistent for better performance in series
usage.
Specification
Cells Per Unit
Voltage Per Unit
12
Capacity
200Ah@10hr-rate to 1.80V per cell @25 oC
Weight
Approx. 60.0 Kg
Max. Discharge Current
2000A (5 sec)
Internal Resistance
Approx. 4 m
Operating Temperature Range
Discharge: -20 C ~60 C
Charge: 0 oC~50 oC
Storage: -20 oC~60 oC
Normal Operating Temperature Range
25 oC5 oC
Float charging Voltage
13.6 to 13.8 VDC/unit Average at 25 oC
Recommended Maximum Charging
Current Limit
60 A
Equalization and Cycle Service
14.6 to 14.8 VDC/unit Average at 25 oC
Self Discharge
RITAR Valve Regulated Lead Acid (VRLA) batteries can be stored
o
for more than 6 months at 25 C. Self-discharge ratio less than 3%
per month at 25 oC. Please charge batteries before using.
Terminal
Terminal F10
Container Material
A.B.S. (UL94-HB), Flammability resistance of UL94-V1
can be available upon request.
Dimensions
Unit: mm
Dimension: 522(L)240(W)223(H)
Terminal F10
Constant Current Discharge Characteristics: A (25 oC)
F.V/Time
5MIN
10MIN
15MIN
30MIN
1HR
2HR
3HR
4HR
5HR
8HR
10HR
20HR
9.60V
545.12
408.33
344 .69
22 5.33
130.00
77.788
53.766
4 4.064
36.067
24.844
21.006
11 .553
10.0V
529.36
388.53
337 .62
22 1.61
129.40
77.204
53.560
4 3.860
35.855
24.642
20.804
11 .343
10.2V
513.67
374.81
332 .31
21 9.65
128.20
76.619
53.148
4 3.656
35.643
24.440
20.602
11 .133
10.5V
461.25
345.86
316 .41
21 4.16
127.00
76.034
52.942
4 3.248
35.219
24.238
20.400
10 .923
10.8V
416.33
315.39
291 .66
20 4.76
124.00
74.669
51.500
4 2.228
34.582
23.834
20.198
10 .713
11.1V
355.48
281.87
261 .61
19 1.83
117.80
71.355
49.234
4 0.188
33.097
22.824
19.592
10 .083
Constant Power Discharge Characteristics: W(25 oC)
F.V/Time
5MIN
10MIN
15MIN
30MIN
1HR
2HR
3HR
4HR
5HR
8HR
10HR
20HR
9.6 V
5638.2
4348.7
379 1.6
25 68.8
1502.2
916.87
639.82
5 25.24
430.28
296.63
251 .02
13 8.52
10.0V
5527.2
4215.5
373 0.7
25 37.4
1498.6
912.01
640.04
5 24.57
429.18
295.21
249 .44
13 6.12
10.2V
5464.0
4104.2
368 8.7
25 19.4
1487.0
906.51
637.24
5 23.44
427.71
293.28
247 .22
13 3.60
10.5V
4974.3
3821.8
351 8.4
24 60.7
1473.7
899.92
634.77
5 18.54
422.62
290.85
244 .80
13 1.08
10.8V
4530.6
3522.9
325 2.0
23 58.8
1446.5
888.45
617.49
5 06.74
414.98
286.00
242 .38
12 8.56
11.1V
3979.4
3185.1
292 7.4
22 15.6
1384.6
855.45
590.81
4 82.26
397.16
273.89
235 .10
12 0.99
All mentioned values are average values.
RA12-200
12V200Ah
Storage characteristic
15
100
12
80
Supplementary charge required
(Carry out supplementary charge
before use if 100% capacity is
requires)
Capacity (%)
L ife E xp e cta ncy (years)
10
60
Supplementary charge required
before use.
This supplementary charge will help
to recover the capacity and should
be made as early as possible.
20
40
30
40
Supplementary charge may often
fail to recover the capacity.
The battery should never be left
standing till this state is reached
20
3
0
2
0
0
10
20
30
40
10 12 14 16 18 20 22 24
Supplementary charge and storage
guidelines
Storage Time (months)
50
Battery Temperature
Discharge characteristic Curve
Charge characteristic Curve for standby use
15
7.5
5.0
0.24
120
4.7
13
6.5
4.3
12
11
6.0
5.5
80
Discharge
100%0.05CA20h
50%0.05CA10h
Charge
Chcrge Voltage2.275V/C
Charge Current0.1CA
Temperature 25
4.0
3.7
60
40
13
6.5
4.3
12
6.0
4.0
11
5.5
3.7
0.20
100
Chcrge Voltage
0.16
0.12
0.08
Terminal Voltage (V)
7.0
Charge Current (CA)
14
Charge Volume (%)
Charge VoltageV
Chcrge Volume
0.05C
0.16C 0.093C
10
5.0
0.35C
3.3
0.62C
1C
3C
10
5.0
3.3
20
0.04
4.5
3.0
Charge Current
4.5
3.0
0
0.6
1.2
12
30
Charge Timeh
10
20
24
Hr
min
10 12 14 16 18 20 24 28
Discharge Time
Capacity Factors With Different Temperature
Battery Type
-20
-10
10
20
25
30
40
45
GEL
6V&12V
Battery
2V
50%
70%
83%
85%
90%
98%
100%
102%
104%
105%
60%
75%
85%
88%
92%
99%
100%
103%
105%
106%
AGM
6V&12V
Battery
2V
46%
66%
76%
83%
90%
98%
100%
103%
107%
109%
55%
70%
80%
85%
92%
99%
100%
104%
108%
110%
Discharge Current VS. Discharge Voltage
Final Discharge
Voltage V/cell
1.75V
Discharge
Current (A)
A0.2C
Maintenance & Cautions
1.60V
1.70V
Float Service:
Every month, recommend inspection every battery voltage.
0.2CA1.0C
A1.0C
Every three months, recommend equalization charge for one time.
Equalization charge method:
Charge the batteries at least once every six months,
if they are stored at 25 oC.
Discharge: 100% rate capacity discharge.
Charging Method:
Charge: Max. current 0.3CA, constant voltage 2.4-2.45V/Cell charge 24h.
Effect of temperature on float charge voltage: -3mV//Cell.
Constant Voltage
-0.2Cx2h+2.4-2.45V/cellx24h,Max. Current 0.3CA
Constant Current
-0.2Cx2h+0.1CAx12h
Fast
-0.2Cx2h+0.3CAx4.0h
Length of service life will be directly affected by the number of discharge
.
cycles, depth of discharge, ambient temperature and charging voltage.
SHENZHEN RITAR POWER CO.,LTD.