Panasonic AC H11 Error Code Guide

The document describes various error codes and fault conditions for an air conditioner. It provides the malfunction decision conditions, potential causes, and suggested troubleshooting steps for 22 different error codes related to issues like abnormal indoor/outdoor communication, temperature sensor faults, fan motor locks, refrigerant shortage, high pressure conditions and overheating of components. Each error code section consists of 3 parts: malfunction decision conditions, possible causes, and troubleshooting steps.

Uploaded by

Sebayan
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
36K views24 pages

Panasonic AC H11 Error Code Guide

The document describes various error codes and fault conditions for an air conditioner. It provides the malfunction decision conditions, potential causes, and suggested troubleshooting steps for 22 different error codes related to issues like abnormal indoor/outdoor communication, temperature sensor faults, fan motor locks, refrigerant shortage, high pressure conditions and overheating of components. Each error code section consists of 3 parts: malfunction decision conditions, possible causes, and troubleshooting steps.

Uploaded by

Sebayan
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • 15.4.1 H11 (Indoor/Outdoor Abnormal Communication): Describes conditions where communication between indoor and outdoor units fails and outlines troubleshooting methods.
  • 15.4.2 H14 (Indoor Intake Air Temperature Sensor Abnormality): Covers issues with the indoor air temperature sensor and provides steps for troubleshooting.
  • 15.4.3 H15 (Compressor Temperature Sensor Abnormality): Discusses the compressor temperature sensor malfunctions and shows how to address them.
  • 15.4.4 H16 (Outdoor Current Transformer Open Circuit): Details how to check for an open circuit in the outdoor current transformer and possible solutions.
  • 15.4.5 H19 (Indoor Fan Motor - DC Motor Mechanism Locked): Explains issues with the DC motor mechanism in the fan motor and how to troubleshoot them.
  • 15.4.6 H23 (Indoor Pipe Temperature Sensor 1 Abnormality): Outlines errors with the indoor pipe temperature sensor 1 and provides corrective actions.
  • 15.4.7 H24 (Indoor Pipe Temperature Sensor 2 Abnormality): Covers malfunction scenarios for the indoor pipe temperature sensor 2 and troubleshooting guidelines.
  • 15.4.8 H25 (e-ion Air Purifying System Abnormal): Addresses errors in the e-ion air purifying system with steps for resolution.
  • 15.4.9 H27 (Outdoor Air Temperature Sensor Abnormality): Describes outdoor air temperature sensor issues and how to troubleshoot them.
  • 15.4.10 H28 (Outdoor Pipe Temperature Sensor Abnormality): Details complications with the outdoor pipe temperature sensor and remedial actions.
  • 15.4.11 H30 (Compressor Discharge Temperature Sensor Abnormality): Discusses discharge temperature sensor issues in the compressor and troubleshooting advice.
  • 15.4.12 H33 (Unspecified Voltage between Indoor and Outdoor): Explains voltage mismatches between indoor and outdoor units and how to address them.
  • 15.4.13 H58 (Patrol Sensor Abnormality): Covers issues related to the patrol sensor and outlines troubleshooting methods.
  • 15.4.14 H97 (Outdoor Fan Motor - DC Motor Mechanism Locked): Discusses locking issues with the outdoor fan motor's DC mechanism and solutions.
  • 15.4.15 H98 (Indoor High Pressure Protection): Defensive measures and troubleshooting for high pressure protection errors in indoor units.
  • 15.4.16 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry): Outlines procedures for dealing with freeze prevention issues in cooling and dry modes.
  • 15.4.17 F11 (4-way Valve Abnormality): Details malfunctions of the 4-way valve and steps for rectification.
  • 15.4.18 F90 (Power Factor Correction Protection): Addresses protection issues related to power factor correction and troubleshooting methods.
  • 15.4.19 F91 (Refrigeration Cycle Abnormality): Identifies refrigeration cycle issues and provides solutions for troubleshooting.
  • 15.4.20 F93 (Compressor Rotation Failure): Explains compressor rotation failure and offers troubleshooting advice.
  • 15.4.21 F95 (Cooling High Pressure Abnormality): Covers high pressure issues during cooling and methods to correct them.
  • 15.4.22 F96 (IPM Overheating): Discusses overheating issues in integrated power modules and outlines troubleshooting steps.
  • 15.4.23 F97 (Compressor Overheating): Addresses overheating issues in compressors and steps for resolution.
  • 15.4.24 F98 (Input Over Current Detection): Details detection of overcurrent inputs in systems and provides troubleshooting guidance.

15.4.

Self-diagnosis Method
15.4.1. H11 (Indoor/Outdoor Abnormal Communication)
Malfunction Decision Conditions During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused Faulty indoor unit PCB. Faulty outdoor unit PCB. Indoor unit-outdoor unit signal transmission error due to wrong wiring. Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor units. Indoor unit-outdoor unit signal transmission error due to disturbed power supply waveform. Troubleshooting

53

15.4.2. H14 (Indoor Intake Air Temperature Sensor Abnormality)


Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting

54

15.4.3. H15 (Compressor Temperature Sensor Abnormality)


Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting

55

15.4.4. H16 (Outdoor Current Transformer Open Circuit)


Malfunction Decision Conditions A current transformer (CT) is detected by checking the compressor running frequency ( rated frequency) and CT detected input current (less than 0.65A) for continuously 20 seconds. Malfunction Caused CT defective Outdoor PCB defective Compressor defective (low compression) Troubleshooting

56

15.4.5. H19 (Indoor Fan Motor - DC Motor Mechanism Locked)


Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550rpm or < 50rpm) Malfunction Caused Operation stops due to short circuit inside the fan motor winding. Operation stops due to breaking of wire inside the fan motor. Operation stops due to breaking of fan motor lead wires. Operation stops due to Hall IC malfunction. Operation error due to faulty indoor unit PCB. Troubleshooting

57

15.4.6. H23 (Indoor Pipe Temperature Sensor 1 Abnormality)


Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor 1 are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting

58

15.4.7. H24 (Indoor Pipe Temperature Sensor 2 Abnormality)


Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor 2 are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting

59

15.4.8. H25 (e-ion Air Purifying System Abnormal)


Malfunction Decision Conditions During standby of cooling and heating operation, e-ion breakdown occurs and air conditioner stops operation. Malfunction Caused Faulty indoor main PCB. Faulty indoor e-ion power module. Troubleshooting

60

15.4.9. H27 (Outdoor Air Temperature Sensor Abnormality)


Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting

61

15.4.10. H28 (Outdoor Pipe Temperature Sensor Abnormality)


Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting

62

15.4.11. H30 (Compressor Discharge Temperature Sensor Abnormality)


Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor. Faulty PCB. Troubleshooting

63

15.4.12. H33 (Unspecified Voltage between Indoor and Outdoor)


Malfunction Decision Conditions The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused Wrong models interconnected. Wrong indoor unit and outdoor unit PCBs used. Indoor unit or outdoor unit PCB defective. Troubleshooting

64

15.4.13. H58 (Patrol Sensor Abnormality)


Malfunction Decision Conditions If Patrol sensor feedback is 0V or 5V continuous for 6 hours. Error will display only when the Patrol operation is ON. Malfunction Caused Faulty connector connection. Faulty Patrol sensor. Troubleshooting

65

15.4.14. H97 (Outdoor Fan Motor - DC Motor Mechanism Locked)


Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor. Malfunction Caused Operation stops due to short circuit inside the fan motor winding. Operation stops due to breaking of wire inside the fan motor. Operation stops due to breaking of fan motor lead wires. Operation stops due to Hall IC malfunction. Operation error due to faulty outdoor unit PCB. Troubleshooting

66

15.4.15. H98 (Indoor High Pressure Protection)


Error Code will not display (no Timer LED blinking) but store in EEPROM Malfunction Decision Conditions During heating operation, the temperature detected by the indoor pipe temperature sensor is above 60C. Malfunction Caused Clogged air filter of the indoor unit Dust accumulation on the indoor unit heat exchanger Air short circuit Detection error due to faulty indoor pipe temperature sensor Detection error due to faulty indoor unit PCB Troubleshooting

67

15.4.16. H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)


Error code will not display (no TIMER LED blinking) but store in EEPROM Malfunction Decision Conditions Freeze prevention control takes place (when indoor pipe temperature is lower than 2C) Malfunction Caused Clogged air filter of the indoor unit Dust accumulation on the indoor unit heat exchanger Air short circuit Detection error due to faulty indoor pipe temperature sensor Detection error due to faulty indoor unit PCB Troubleshooting

68

15.4.17. F11 (4-way valve Abnormality)


Malfunction Decision Conditions When heating operation, when indoor pipe temperature is below 10C When cooling operation, when indoor pipe temperature is above 45C Malfunction Caused Connector in poor contact Faulty sensor Faulty outdoor unit PCB 4-way valve defective Troubleshooting

69

15.4.18. F90 (Power Factor Correction Protection)


Malfunction Decision Conditions During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at the outdoor unit main PCB senses abnormal high DC voltage level. Malfunction Caused DC voltage peak due to power supply surge. DC voltage peak due to compressor windings not uniform. Faulty outdoor PCB. Troubleshooting

70

15.4.19. F91 (Refrigeration Cycle Abnormality)


Malfunction Decision Conditions During cooling, compressor frequency = Fcmax. During heating, compressor frequency > Fhrated. During cooling and heating operation, running current: 0.65A < I < 1.65A. During cooling, indoor intake - indoor pipe < 4C During heating, indoor pipe - indoor intake < 5C Multi Models Only - Gas shortage detection 1: A gas shortage is detected by checking the CT-detected input current value and the compressor running frequency. During startup and operating of cooling and heating, input current < 8.78/256 (A/Hz) x compressor running frequency + 0.25. - Gas shortage detection 2: A gas shortage is detected by checking the difference between indoor pipe temperature and indoor intake air temperature during cooling and heating. Malfunction Caused Refrigerant shortage (refrigerant leakage) Poor compression performance of compressor. 2/3 way valve closed. Detection error due to faulty indoor intake air or indoor pipe temperature sensors. Troubleshooting

71

15.4.20. F93 (Compressor Rotation Failure)


Malfunction Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused Compressor terminal disconnect Outdoor PCB malfunction Troubleshooting

72

15.4.21. F95 (Cooling High Pressure Abnormality)


Malfunction Decision Conditions During operation of cooling, when outdoor unit heat exchanger high temperature data (61C) is detected by the outdoor pipe temperature sensor. Malfunction Caused Outdoor pipe temperature rise due to short circuit of hot discharge air flow. Outdoor pipe temperature rise due to defective of outdoor fan motor. Outdoor pipe temperature rise due to defective outdoor pipe temperature sensor. Outdoor pipe temperature rise due to defective outdoor unit PCB. Troubleshooting

73

15.4.22. F96 (IPM Overheating)


Malfunction Decision Conditions During operating of cooling and heating, when IPM temperature data (100C) is detected by the IPM temperature sensor. Multi Models Only Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated. Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90C) is detected by the heat sink temperature sensor.

Malfunction Caused IPM overheats due to short circuit of hot discharge air flow. IPM overheats due to defective of outdoor fan motor. IPM overheats due to defective of internal circuitry of IPM. IPM overheats due to defective IPM temperature sensor. Multi Models Only - Compressor OL connector poor contact. - Compressor OL faulty. Troubleshooting

74

15.4.23. F97 (Compressor Overheating)


Malfunction Decision Conditions During operation of cooling and heating, when compressor tank temperature data (112C) is detected by the compressor tank temperature sensor. Malfunction Caused Refrigerant shortage (refrigerant leakage). 2/3 way valve closed. Detection error due to faulty compressor tank temperature sensor. Troubleshooting

75

15.4.24. F98 (Input Over Current Detection)


Malfunction Decision Conditions During operation of cooling and heating, when an input over-current (14.98A) is detected by checking the input current value being detected by current transformer (CT) with the compressor running. Malfunction Caused Over-current due to compressor failure. Over-current due to defective outdoor unit PCB. Over-current due to defective inverter main circuit electrolytic capacitor. Over-current due to excessive refrigerant. Troubleshooting

14.98A?