"ASCE705W.
xls" Program
Version 1.0
WIND LOADING ANALYSIS - Main Wind-Force Resisting System
Per ASCE 7-05 Code for Enclosed or Partially Enclosed Buildings
Using Method 2: Analytical Procedure (Section 6.5) for Buildings of Any Height
J ob Name: Subject:
J ob Number: Originator: Checker:
Input Data:
Wind Direction = Normal (Normal or Parallel to building ridge)
Wind Speed, V = 150 mph (Wind Map, Figure 6-1)
Bldg. Classification = II (Table 1-1 Occupancy Cat.)
Exposure Category = C (Sect. 6.5.6)
Ridge Height, hr = 37.00 ft. (hr >=he)
Eave Height, he = 21.67 ft. (he <=hr)
Building Width = 100.00 ft. (Normal to Building Ridge)
Building Length = 80.00 ft. (Parallel to Building Ridge)
Roof Type = Gable (Gable or Monoslope)
Topo. Factor, Kzt = 1.00 (Sect. 6.5.7 & Figure 6-4)
Direct. Factor, Kd = 0.85 (Table 6-4)
Enclosed? (Y/N) Y (Sect. 6.2 & Figure 6-5)
Damping Ratio, = 0.050 (Suggested Range =0.010-0.070)
Period Coef., Ct = 0.0250 (Suggested Range =0.020-0.035)
(Assume: T =Ct*h^(3/4) , and f =1/T)
Resulting Parameters and Coefficients:
Roof Angle, = 17.05 deg.
Mean Roof Ht., h = 29.34 ft. (h =(hr+he)/2, for roof angle >10 deg.) L =100 ft.
Windward Wall Cp = 0.80 (Fig. 6-6) B =80 ft.
Leeward Wall Cp = -0.45 (Fig. 6-6)
Side Walls Cp = -0.70 (Fig. 6-6)
Windward Roof Cp = -0.45 (Fig. 6-6) (Condition #1)
Windward Roof Cp = 0 05 (Fig 6 6) (Condition #2)
o
L
B
hr
he
h
Plan
Elevation
L
Wind
1 of 4 5/28/2014 3:17 AM
Windward Roof Cp = 0.05 (Fig. 6-6) (Condition #2)
Leeward Roof Cp = -0.54 (Fig. 6-6)
+GCpi Coef. = 0.18 (Figure 6-5) (positive internal pressure)
-GCpi Coef. = -0.18 (Figure 6-5) (negative internal pressure)
If z <=15 then: Kz =2.01*(15/zg)^(2/) , If z >15 then: Kz =2.01*(z/zg)^(2/) (Table 6-3, Case 2a)
= 9.50 zg = 900 (Table 6-2)
Kh = 0.98 (Kh =Kz evaluated at z =h)
I = 1.00 (Table 6-1) (Importance factor)
Velocity Pressure: qz =0.00256*Kz*Kzt*Kd*V^2*I (Sect. 6.5.10, Eq. 6-15)
qh = 47.86 psf qh =0.00256*Kh*Kzt*Kd*V^2*I (qz evaluated at z =h)
Ratio h/B = 0.293 freq., f = 3.173 hz. (f >=1, Rigid structure)
Gust Factor, G = 0.850 (Sect. 6.5.8)
Design Net External Wind Pressures (Sect. [Link]):
p =qz*G*Cp - qi*(+/-GCpi) for windward wall (psf), where: qi =qh (Eq. 6-17, Sect. [Link].1)
p =qh*G*Cp - qi*(+/-GCpi) for leeward wall, sidewalls, and roof (psf), where: qi =qh (Sect. [Link].1)
1 of 4 5/28/2014 3:17 AM
"[Link]" Program
Version 1.0
Normal to Ridge Wind Load Tabulation for MWFRS - Buildings of Any Height
Surface z Kz qz Cp p =Net Design Press. (psf)
(ft.) (psf) (w/ +GCpi) (w/ -GCpi)
Windward Wall 0 0.85 41.56 0.80 19.65 36.88
15.00 0.85 41.56 0.80 19.65 36.88
20.00 0.90 44.16 0.80 21.41 38.64
25.00 0.95 46.28 0.80 22.85 40.09
30.00 0.98 48.09 0.80 24.09 41.32
35.00 1.01 49.68 0.80 25.16 42.40
For z =hr: 37.00 1.03 50.26 0.80 25.56 42.79
For z =he: 21.67 0.92 44.91 0.80 21.92 39.15
For z =h: 29.34 0.98 47.86 0.80 23.93 41.16
Leeward Wall All - - -0.45 -26.92 -9.69
Side Walls All - - -0.70 -37.10 -19.86
Roof (windward) cond. 1 - - - -0.45 -26.75 -9.52
2 of 4 5/28/2014 3:17 AM
oo ( d a d) co d 0 5 6 5 9 5
Roof (windward) cond. 2 - - - 0.05 -6.61 10.62
- - -
Roof (leeward) - - - -0.54 -30.62 -13.39
- - -
Notes: 1. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces.
2. Per Code Section [Link], the minimum wind load for MWFRS shall not be less than 10 psf.
3. References : a. ASCE 7-02, "Minimum Design Loads for Buildings and Other Structures".
b. "Guide to the Use of the Wind Load Provisions of ASCE 7-02"
by: Kishor C. Mehta and J ames M. Delahay (2004).
2 of 4 5/28/2014 3:17 AM
"[Link]" Program
Version 1.0
Determination of Gust Effect Factor, G:
Is Building Flexible? No f >=1 Hz.
1: Simplified Method for Rigid Building
G = 0.850
Parameters Used in Both Item #2 and Item #3 Calculations (from Table 6-2):
^= 0.105
b^= 1.00
(bar) = 0.154
b(bar) = 0.65
c = 0.20
l = 500 ft.
(bar) = 0.200
z(min) = 15 ft.
Calculated Parameters Used in Both Rigid and/or Flexible Building Calculations:
z(bar) = 17.60 =0.6*h , but not <z(min) , ft.
Iz(bar) = 0.222 =c*(33/z(bar))^(1/6) , Eq. 6-5
Lz(bar) = 440.94 =l*(z(bar)/33)^((bar)) Eq. 6-7
gq = 3.4 (3.4, per Sect. [Link])
gv = 3.4 (3.4, per Sect. [Link])
gr = 4.456 =(2*(LN(3600*f)))^(1/2)+0.577/(2*LN(3600*f))^(1/2) , Eq. 6-9
Q = 0.890 =(1/(1+0.63*((B+h)/Lz(bar))^0.63))^(1/2) , Eq. 6-6
2: Calculation of G for Rigid Building
G = 0.868 =0.925*((1+1.7*gq*Iz(bar)*Q)/(1+1.7*gv*Iz(bar))) , Eq. 6-4
3: Calculation of Gf for Flexible Building
= 0.050 Damping Ratio
Ct = 0.025 Period Coefficient
3 of 4 5/28/2014 3:17 AM
Ct 0.025 Period Coefficient
T = 0.315 =Ct*h^(3/4) , sec. (Approximate fundamental period)
f = 3.173 =1/T , Hz. (Natural Frequency)
V(fps) = N.A. =V(mph)*(88/60) , ft./sec.
V(bar,zbar) = N.A.
=b(bar)*(z(bar)/33)^((bar))*V*(88/60) , ft./sec. , Eq. 6-14
N1 = N.A. =f*Lz(bar)/(V(bar,zbar)) , Eq. 6-12
Rn = N.A. =7.47*N1/(1+10.3*N1)^(5/3) , Eq. 6-11
h = N.A. =4.6*f*h/(V(bar,zbar))
Rh = N.A.
=(1/h)-1/(2*h^2)*(1-e^(-2*h)) for h>0, or =1 for h=0 ,Eq. 6-13a,b
b = N.A. =4.6*f*B/(V(bar,zbar))
RB = N.A. =(1/b)-1/(2*b^2)*(1-e^(-2*b)) for b>0, or =1 for b=0,Eq. 6-13a,b
d = N.A. =15.4*f*L/(V(bar,zbar))
RL = N.A. =(1/d)-1/(2*d^2)*(1-e^(-2*d)) for d>0, or =1 for d=0 ,Eq. 6-13a,b
R = N.A. =((1/)*Rn*Rh*RB*(0.53+0.47*RL))^(1/2) , Eq. 6-10
Gf = N.A. =0.925*(1+1.7*Iz(bar)*(gq^2*Q^2+gr^2*R^2)^(1/2))/(1+1.7*gv*Iz(bar)) ,
Use: G = 0.850 Eq. 6-8
3 of 4 5/28/2014 3:17 AM
"[Link]" Program
Version 1.0
Figure 6-9 - Design Wind Load Cases of MWFRS for Buildings of All Heights
Case 1: Full design wind pressure acting on the projected area perpendicular to each principal axis of
the structure, considered separately along each principal axis.
Case 2: Three quarters of the design wind pressure acting on the projected area perpendicular to each
principal axis of the structure in conjunction with a torsional moment as shown, considered
4 of 4 5/28/2014 3:17 AM
p c pa a s o t e st uctu e co ju cto t a to s o a o e t as s o , co s de ed
separately for each principal axis.
Case 3: Wind pressure as defined in Case 1, but considered to act simultaneously at 75% of the
specified value.
Case 4: Wind pressure as defined in Case 2, but considered to act simultaneously at 75% of the
specified value.
Notes: 1. Design wind pressures for windward (Pw) and leeward (PL) faces shall be determined in
accordance with the provisions of Section [Link].1 and [Link].3 as applicable for buildings
of all heights.
2. Above diagrams show plan views of building.
3. Notation:
Pwx, Pwy =Windward face pressure acting in the X, Y principal axis, respectively.
PLx, PLy =Leeward face pressure acting in the X, Y principal axis, respectively.
e (ex, ey) =Eccentricity for the X, Y principal axis of the structure, respectively.
MT =Torsional moment per unit height acting about a vertical axis of the building.