[Link] Profis Anchor 2.7.
7
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 9/08/2018
E-Mail:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-RE 500 V3 + HIT-V-R M20
Effective embedment depth: hef,act = 140 mm (hef,limit = - mm)
Material: A4
Evaluation Service Report: ESR-3814
Issued I Valid: 1/01/2017 | 1/01/2019
Proof: Design method ACI 318-14 / Chem
Stand-off installation: eb = 0 mm (no stand-off); t = 10 mm
Anchor plate: lx x ly x t = 210 mm x 105 mm x 10 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, 32MPa, fc' = 4,641 psi; h = 187 mm, Temp. short/long: 0/0 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
Seismic loads (cat. C, D, E, or F) Tension load: yes ([Link].3 (c))
Shear load: yes ([Link].3 (b))
Geometry [mm] & Loading [kN, kNm]
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
[Link] Profis Anchor 2.7.7
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 9/08/2018
E-Mail:
2 Load case/Resulting anchor forces y
Load case: Design loads
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 25.900 18.800 0.000 18.800
1 x
Tension
max. concrete compressive strain: - [‰]
max. concrete compressive stress: - [N/mm2]
resulting tension force in (x/y)=(0/0): 25.900 [kN]
resulting compression force in (x/y)=(0/0): 0.000 [kN]
3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* 25.900 111.475 24 OK
Bond Strength** 25.900 35.382 74 OK
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 25.900 32.394 80 OK
* anchor having the highest loading **anchor group (anchors in tension)
3.1 Steel Strength
Nsa = ESR value refer to ICC-ES ESR-3814
f Nsa ≥ Nua ACI 318-14 Table [Link]
Variables
Ase,N [mm2] futa [N/mm2]
245 700.00
Calculations
Nsa [kN]
171.500
Results
Nsa [kN] f steel f nonductile f Nsa [kN] Nua [kN]
171.500 0.650 1.000 111.475 25.900
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
[Link] Profis Anchor 2.7.7
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 9/08/2018
E-Mail:
3.2 Bond Strength
Na = (AA ) y
Na
Na0
ed,Na y cp,Na Nba ACI 318-14 Eq. (17.4.5.1a)
f Na ≥ Nua ACI 318-14 Table [Link]
ANa = see ACI 318-14, Section [Link], Fig. R [Link](b)
ANa0 = (2 cNa)2 ACI 318-14 Eq. (17.4.5.1c)
cNa = 10 da √ t uncr
1100
ACI 318-14 Eq. (17.4.5.1d)
( )
1
y ec,Na = e' ≤ 1.0 ACI 318-14 Eq. ([Link])
1+ N
cNa
y ed,Na = 0.7 + 0.3 ( ) ca,min
cNa
≤ 1.0 ACI 318-14 Eq. (17.4.5.4b)
y cp,Na = MAX ( )
ca,min cNa
,
cac cac
≤ 1.0 ACI 318-14 Eq. (17.4.5.5b)
Nba = l a · t k,c · aN,seis · p · da · hef ACI 318-14 Eq. ([Link])
Variables
2 2
t k,c,uncr [N/mm ] da [mm] hef [mm] ca,min [mm] t k,c [N/mm ]
16.93 20 140 250 9.44
ec1,N [mm] ec2,N [mm] cac [mm] la aN,seis
0 0 339 1.000 1.000
Calculations
cNa [mm] ANa [mm2] ANa0 [mm2] y ed,Na
297 325,638 353,850 0.952
y ec1,Na y ec2,Na y cp,Na Nba [kN]
1.000 1.000 1.000 82.828
Results
Na [kN] f bond f seismic f nonductile f Na [kN] Nua [kN]
72.578 0.650 0.750 1.000 35.382 25.900
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
[Link] Profis Anchor 2.7.7
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 9/08/2018
E-Mail:
3.3 Concrete Breakout Strength
Ncb = (AA ) y
Nc
Nc0
ed,N y c,N y cp,N Nb ACI 318-14 Eq. (17.4.2.1a)
f Ncb ≥ Nua ACI 318-14 Table [Link]
ANc see ACI 318-14, Section [Link], Fig. R [Link](b)
ANc0 = 9 h2ef ACI 318-14 Eq. (17.4.2.1c)
( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-14 Eq. ([Link])
1+
3 hef
y ed,N = 0.7 + 0.3 (ca,min
1.5hef )
≤ 1.0 ACI 318-14 Eq. (17.4.2.5b)
y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-14 Eq. (17.4.2.7b)
1.5
Nb = kc l a √fc hef
'
ACI 318-14 Eq. (17.4.2.2a)
Variables
hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm] y c,N
140 0 0 250 1.000
cac [mm] kc la f'c [psi]
339 17 1.000 4,641
Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
175,645 175,645 1.000 1.000 1.000 1.000 66.450
Results
Ncb [kN] f concrete f seismic f nonductile f Ncb [kN] Nua [kN]
66.450 0.650 0.750 1.000 32.394 25.900
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
[Link] Profis Anchor 2.7.7
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 9/08/2018
E-Mail:
4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* 18.800 49.392 39 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Concrete Breakout 18.800 93.030 21 OK
Strength controls)**
Concrete edge failure in direction y+** 18.800 41.630 46 OK
* anchor having the highest loading **anchor group (relevant anchors)
4.1 Steel Strength
Vsa,eq = ESR value refer to ICC-ES ESR-3814
f Vsteel ≥ Vua ACI 318-14 Table [Link]
Variables
Ase,V [mm2] futa [N/mm2]
245 700.00
Calculations
Vsa,eq [kN]
82.320
Results
Vsa,eq [kN] f steel f nonductile f Vsa [kN] Vua [kN]
82.320 0.600 1.000 49.392 18.800
4.2 Pryout Strength (Concrete Breakout Strength controls)
Vcp = kcp [(AA ) y
Nc
Nc0
ed,N y c,N y cp,N Nb] ACI 318-14 Eq. (17.5.3.1a)
f Vcp ≥ Vua ACI 318-14 Table [Link]
ANc see ACI 318-14, Section [Link], Fig. R [Link](b)
ANc0 = 9 h2ef ACI 318-14 Eq. (17.4.2.1c)
( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-14 Eq. ([Link])
1+
3 hef
y ed,N = 0.7 + 0.3 (
ca,min
1.5hef )
≤ 1.0 ACI 318-14 Eq. (17.4.2.5b)
y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-14 Eq. (17.4.2.7b)
1.5
Nb = kc l a √fc hef
'
ACI 318-14 Eq. (17.4.2.2a)
Variables
kcp hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm]
2 140 0 0 250
y c,N cac [mm] kc la f'c [psi]
1.000 339 17 1.000 4,641
Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
175,645 175,645 1.000 1.000 1.000 1.000 66.450
Results
Vcp [kN] f concrete f seismic f nonductile f Vcp [kN] Vua [kN]
132.900 0.700 1.000 1.000 93.030 18.800
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
[Link] Profis Anchor 2.7.7
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 9/08/2018
E-Mail:
4.3 Concrete edge failure in direction y+
Vcb = (AA ) y
Vc
Vc0
ed,V y c,V y h,V y parallel,V Vb ACI 318-14 Eq. (17.5.2.1a
f Vcb ≥ Vua ACI 318-14 Table [Link]
AVc see ACI 318-14, Section [Link], Fig. R [Link](b)
AVc0 = 4.5 c2a1 ACI 318-14 Eq. (17.5.2.1c)
( )
1
y ec,V = 2e'v ≤ 1.0 ACI 318-14 Eq. ([Link])
1+
3ca1
y ed,V = 0.7 + 0.3 ( ca2
1.5ca1 )
≤ 1.0 ACI 318-14 Eq. (17.5.2.6b)
y h,V = √1.5ca1
ha
≥ 1.0 ACI 318-14 Eq. ([Link])
' 1.5
Vb = 9 l a √fc ca1 ACI 318-14 Eq. (17.5.2.2b)
Variables
ca1 [mm] ca2 [mm] ecV [mm] y c,V ha [mm]
250 - 0 1.000 187
le [mm] la da [mm] f'c [psi] y parallel,V
140 1.000 20 4,641 1.000
Calculations
AVc [mm2] AVc0 [mm2] y ec,V y ed,V y h,V Vb [kN]
140,250 281,250 1.000 1.000 1.416 84.218
Results
Vcb [kN] f concrete f seismic f nonductile f Vcb [kN] Vua [kN]
59.472 0.700 1.000 1.000 41.630 18.800
5 Combined tension and shear loads
bN bV z Utilization bN,V [%] Status
0.800 0.452 5/3 96 OK
bNV = bzN + bzV <= 1
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
[Link] Profis Anchor 2.7.7
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 9/08/2018
E-Mail:
6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
• An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-14, Chapter 17, Section
[Link].3 (a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT
the case, the connection design (tension) shall satisfy the provisions of Section [Link].3 (b), Section [Link].3 (c), or Section [Link].3
(d). The connection design (shear) shall satisfy the provisions of Section [Link].3 (a), Section [Link].3 (b), or Section [Link].3 (c).
• Section [Link].3 (b) / Section [Link].3 (a) require the attachment the anchors are connecting to the structure be designed to undergo
ductile yielding at a load level corresponding to anchor forces no greater than the controlling design strength. Section [Link].3 (c) / Section
[Link].3 (b) waive the ductility requirements and require the anchors to be designed for the maximum tension / shear that can be
transmitted to the anchors by a non-yielding attachment. Section [Link].3 (d) / Section [Link].3 (c) waive the ductility requirements and
require the design strength of the anchors to equal or exceed the maximum tension / shear obtained from design load combinations that
include E, with E increased by w0.
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-14,
Section 17.8.1.
Fastening meets the design criteria!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
[Link] Profis Anchor 2.7.7
Company: Page: 8
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 9/08/2018
E-Mail:
7 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-RE 500 V3 + HIT-V-R M20
Profile: no profile Installation torque: 0.150 kNm
Hole diameter in the fixture: df = 22 mm Hole diameter in the base material: 22 mm
Plate thickness (input): 10 mm Hole depth in the base material: 140 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 184 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required
7.1 Recommended accessories
Drilling Cleaning Setting
• Suitable Rotary Hammer • Compressed air with required • Dispenser including cassette and mixer
• Properly sized drill bit accessories to blow from the bottom of • Torque wrench
the hole
• Proper diameter wire brush
105 105
53
53
1 x
53
53
105 105
Coordinates Anchor mm
Anchor x y c-x c+x c-y c+y
1 0 0 - - - 250
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
[Link] Profis Anchor 2.7.7
Company: Page: 9
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 9/08/2018
E-Mail:
8 Remarks; Your Cooperation Duties
• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan