0% found this document useful (0 votes)
368 views20 pages

Cable Inspection Checklist

The document provides inspection reports for cable splicing, termination, and testing works. It lists areas to be inspected, including checking material types and sizes, installation practices, labeling, protection, and testing. Inspection criteria are indicated as accept, reject, or not applicable. Signatures and dates are included to verify completion.

Uploaded by

Reynante Alim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
368 views20 pages

Cable Inspection Checklist

The document provides inspection reports for cable splicing, termination, and testing works. It lists areas to be inspected, including checking material types and sizes, installation practices, labeling, protection, and testing. Inspection criteria are indicated as accept, reject, or not applicable. Signatures and dates are included to verify completion.

Uploaded by

Reynante Alim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd

PAG 3 420MWCFPP

CABLE SPLICING WORKS(FIBER OPTIC)


INSPECTION REPORT NUMBER INSPECTION DATE & TIME DISCIPLINE SHEET NO

JOB DESCRIPTION AREA DESCRIPTION

ENGINEERING DOCUMENT NUMBER CODES & STANDARDS NUMBER SUBCONTRACTOR/SUPPLIER

RESUNT
NO. Area to be inspected
ACCEPT REJECT N/A.

1 Check splicing material type, size

2 No damage of cable has found and maintain insulation resistance

3 Cable route to the designated location and correctly identified

4 Cable installed with sufficient separation and layer

5 Cable installed with sufficient bending radius

6 Cable pulling tension and use proper pulling tools

7 Cable tie, markers, clamps installed properly as per specification

8 Cable Numbering System & Labeling

9 Cable support on raceway installed properly

10 Check Splicing kits

11 Splicing shall be done correctly

12 Cable protection and sealing

REMARKS:

SUBCONTRACTOR QC CONTRACTOR QC COMPANY


NAME NAME NAME

SIGNATURE SIGNATURE SIGNATURE


SIGNATURE SIGNATURE SIGNATURE

DATE DATE DATE

EL-008-F01
Project Name
Project No. : OOOO
LV/CONTROL CABLE TERMINATION
INSPECTION REPORT NUMBER INSPECTION DATE & TIME DISCIPLINE SHEET NO

JOB DESCRIPTION AREA DESCRIPTION

ENGINEERING DOCUMENT NUMBER CODES & STANDARDS NUMBER SUBCONTRACTOR/SUPPLIER

RESUNT
NO. Area to be inspected
ACCEPT REJECT N/A.

1 Correct cable type/size/ installed as per approved IFC drawings

2 Cable / wire marker identified

3 Arrangement and dressing of cables correctly

4 Cable glands / shrouds & fittings are securely fitted

5 Earthing / bonding installed correctly

6 Check the equipment terminals for any damages

7 Check the crimping of the cable lugs

Check the tightness of the cable connection to the terminals of


8
the equipment.

9 Check no damage to the terminated cable

10 Cables are correctly terminated in accordance with diagram

11 Coninuiy and insulation resistance test shall be done correctly

REMARKS:

SUBCONTRACTOR QC CONTRACTOR QC COMPANY


NAME NAME NAME

SIGNATURE SIGNATURE SIGNATURE


SIGNATURE SIGNATURE SIGNATURE

DATE DATE DATE

EL-008-F02
DONG GWANG BUSINESS
PROJECT

KWM
RFI No:
POWER CABLE TERMINATION
INSPECTION DATE & TIME DISCIPLINE SHEET NO

INDU
JOB DESCRIPTION AREA:

RESULT

STRIE
NO. Area to be inspected
ACCEPT REJECT N/A.

1 Correct cable type/size/ installed

S
2 Cable / wire marker identified

PHILI
3 Arrangement and dressing of cables correctly

4 Cable glands / shrouds & fittings are securely fitted

PPIN
5 Earthing / bonding installed correctly

ES,
6 Check the equipment terminals for any damages

7 Check the crimping of the cable lugs

INC.
Check the tightness of the cable connection to the terminals of
8
the equipment.

9 Check no damage to the terminated cable

10 Cables are correctly terminated in accordance with diagram

11 Coninuiy and insulation resistance test shall be done correctly

REMARKS:

KWM QC FILHIGH QC DONG GWANG


NAME: Reynante T. Alim NAME: Arnel F. Ramirez NAME: Brendo E. Quilop

SIGNATURE: SIGNATURE: SIGNATURE:

DATE: DATE: DATE:


DONG GWANG BUSINESS
PROJECT

KWM
RFI No:
POWER CABLE TERMINATION
INSPECTION DATE & TIME DISCIPLINE SHEET NO

INDU
JOB DESCRIPTION AREA:

RESULT

STRIE
NO. Area to be inspected
ACCEPT REJECT N/A.

1 Correct cable type/size/ installed

S
2 Cable / wire marker identified

PHILI
3 Arrangement and dressing of cables correctly

4 Cable glands / shrouds & fittings are securely fitted

PPIN
5 Earthing / bonding installed correctly

ES,
6 Check the equipment terminals for any damages

7 Check the crimping of the cable lugs

INC.
Check the tightness of the cable connection to the terminals of
8
the equipment.

9 Check no damage to the terminated cable

10 Cables are correctly terminated in accordance with diagram

11 Coninuiy and insulation resistance test shall be done correctly

REMARKS:

KWM QC FILHIGH QC DONG GWANG


NAME: Antonio C. Pangon NAME: Arnel F. Ramirez NAME: Brendo E. Quilop

SIGNATURE: SIGNATURE: SIGNATURE:

DATE: DATE: DATE:


Project Name
Project No. : OOOO
HV / MV CABLE TERMINATION
INSPECTION REPORT NUMBER INSPECTION DATE & TIME DISCIPLINE SHEET NO

JOB DESCRIPTION AREA DESCRIPTION

ENGINEERING DOCUMENT NUMBER CODES & STANDARDS NUMBER SUBCONTRACTOR/SUPPLIER

RESUNT
NO. Area to be inspected
ACCEPT REJECT N/A.

1 Correct cable type/size/ installed as per approved IFC drawings

2 Cable / wire marker identified

3 Arrangement and dressing of cables correctly

4 Cable glands / shrouds & fittings are securely fitted

5 Earthing / bonding installed correctly

6 Check the equipment terminals for any damages

7 Check the crimping of the cable lugs

Check the tightness of the cable connection to the terminals of


8
the equipment.

9 Check no damage to the terminated cable

10 Cable temination kit installed without any damage

11 Cables are correctly terminated in accordance with diagram

Check HV/MV cable joint / termination materials are complete for


12
installation and correct in according to drawings

13 Coninuiy and insulation resistance test shall be done correctly

REMARKS:

SUBCONTRACTOR QC CONTRACTOR QC COMPANY


NAME NAME NAME

SIGNATURE SIGNATURE SIGNATURE


SIGNATURE SIGNATURE SIGNATURE

DATE DATE DATE

EL-008-F03
Project Name
Project No. : OOOO
LV/CONTROL CABLE CONTINUITY / INSULATION RESISTANCE TEST
INSPECTION REPORT NUMBER INSPECTION DATE & TIME DISCIPLINE SHEET NO

JOB DESCRIPTION AREA DESCRIPTION

ENGINEERING DOCUMENT NUMBER CODES & STANDARDS NUMBER SUBCONTRACTOR/SUPPLIER

Insulation Resistance(MΩ)
Cable No. Continuity
Applied L1L2
L1-L2 L2-L3 L3-L1 L1-G L2-G L3-G
voltage(d.c) L3 -G

REMARKS:

SUBCONTRACTOR QC CONTRACTOR QC COMPANY


NAME NAME NAME

SIGNATURE SIGNATURE SIGNATURE


SIGNATURE SIGNATURE SIGNATURE

DATE DATE DATE

EL-008-F04
Project Name
Project No. : OOOO
HV / MV CABLE CONTINUITY / INSULATION RESISTANCE TEST(1/2)
INSPECTION REPORT NUMBER INSPECTION DATE & TIME DISCIPLINE SHEET NO

JOB DESCRIPTION AREA DESCRIPTION

ENGINEERING DOCUMENT NUMBER CODES & STANDARDS NUMBER SUBCONTRACTOR/SUPPLIER

Installatio
Cable Cable Termination Terminator
Location Name/Signature
Certificate n Remark
No. Type Date
Instruction

Note (If any):

SUBCONTRACTOR QC CONTRACTOR QC COMPANY


NAME NAME NAME
SIGNATURE SIGNATURE SIGNATURE

DATE DATE DATE

EL-008-F05
UITY / INSULATION RESISTANCE TEST(1/2)
SHEET NO

AREA DESCRIPTION

SUBCONTRACTOR/SUPPLIER

Remark

COMPANY
NAME
SIGNATURE

DATE

EL-008-F05
Project Name
Project No. : OOOO
HV / MV CABLE CONTINUITY / INSULATION RESISTANCE TEST(2/2)
INSPECTION REPORT NUMBER INSPECTION DATE & TIME DISCIPLINE SHEET NO

JOB DESCRIPTION AREA DESCRIPTION

ENGINEERING DOCUMENT NUMBER CODES & STANDARDS NUMBER SUBCONTRACTOR/SUPPLIER

Insulation Resistance(MΩ)
Cable No. Continuity
Applied L1L2
L1-L2 L2-L3 L3-L1 L1-G L2-G L3-G
voltage(d.c) L3 -G

REMARKS:

SUBCONTRACTOR QC CONTRACTOR QC COMPANY


NAME NAME NAME

SIGNATURE SIGNATURE SIGNATURE


DATE DATE DATE

EL-008-F06
Project Name
Project No. : OOOO
HV & MV CABLE HIGH - POTENTIAL TEST
INSPECTION REPORT NUMBER INSPECTION DATE & TIME DISCIPLINE SHEET NO

JOB DESCRIPTION AREA DESCRIPTION

ENGINEERING DOCUMENT NUMBER CODES & STANDARDS NUMBER SUBCONTRACTOR/SUPPLIER

Insulation resistance test (before high potential test)


Applied Insulation Resistance (MΩ)
Cable No. Continuity voltage
(d.c) L1-E/L1/L2 L2-E/L1/L3 L3-E/L1/L2 L1/L2/L3-E

1. Insulation resistance tested before high potential test : □ Yes / □ No

2. Cable to be isolated at both ends during test : □ Yes / □ No

3. Cable termination correct : □ Yes / □ No

4. Inspection both ends of cable for safety : □ Yes / □ No


Applied Test Results
Leakage Current
Phase voltage Time
in mA Pass Fail
(d.c)
L1-L2/L3/E mA s

L2-L1/L2/E mA s

L3-L1/L2/E mA s

Note : After Hi-Potential Test cable must be discharged

Insulation resistance test (after high potential test)


Applied Insulation Resistance (MΩ)
Cable No. Continuity voltage
(d.c) L1-E/L1/L2 L2-E/L1/L3 L3-E/L1/L2 L1/L2/L3-E

REMARKS:

SUBCONTRACTOR QC CONTRACTOR QC COMPANY


NAME NAME NAME

SIGNATURE SIGNATURE SIGNATURE


SIGNATURE SIGNATURE SIGNATURE

DATE DATE DATE

EL-008-F07

You might also like