CABLE DESIGN & CONSTRUCTION
PARTY/CLIENT: FOCUS AUTO BRICKS & CERAMICS LIMITED.
Manufacturer: SQ Wire & Cables Co. Ltd.
Date: 15/06/2019
26). ZR-KVVP: 19x0.75 rm (300/500 V)
1. Conductor (Annealed Copper): Circular Stranded (26/0.193 mm)
2. Insulation (PVC): Thickness= 0.6 mm,
Core Color: All Core black with white numbering print
3. Laid Up: Nineteen Core laid up together
4. Binder (Double Layer with Overlap): Polyester Tape
5. Shield/Braiding: Copper Wire Braiding
6. Sheath (PVC-FR): Thickness =1.5 mm, Color: Black
7. Printing/Embossing: SQ CABLES BANGLADESH ISO 9001 CERTIFIED 19x0.75 RM ZR-KVVP
300/500 V
27). ZR-KVVP: 16x0.75 rm (300/500 V)
1. Conductor (Annealed Copper): Circular Stranded (26/0.193 mm)
2. Insulation (PVC): Thickness= 0.6 mm,
Core Color: All Core black with white numbering print
3. Laid Up: Sixteen Core laid up together
4. Binder (Double Layer with Overlap): Polyester Tape
5. Shield/Braiding: Copper Wire Braiding
6. Sheath (PVC-FR): Thickness =1.4 mm, Color: Black
7. Printing/Embossing: SQ CABLES BANGLADESH ISO 9001 CERTIFIED 16x0.75 RM ZR-KVVP
300/500 V
28). ZR-KVVP: 8x0.75 rm (300/500 V)
1. Conductor (Annealed Copper): Circular Stranded (26/0.193 mm)
2. Insulation (PVC): Thickness= 0.6 mm,
Core Color: All Core black with white numbering print
3. Laid Up: Eight Core laid up together
4. Binder (Double Layer with Overlap): Polyester Tape
5. Shield/Braiding: Copper Wire Braiding
6. Sheath (PVC-FR): Thickness =1.2 mm, Color: Black
7. Printing/Embossing: SQ CABLES BANGLADESH ISO 9001 CERTIFIED 8x0.75 RM ZR-KVVP
300/500 V
29). ZR-KVVP: 4x0.75 rm (300/500 V)
1. Conductor (Annealed Copper): Circular Stranded (26/0.193 mm)
2. Insulation (PVC): Thickness= 0.6 mm,
Core Color: Red, Yellow, Blue & Black
3. Laid Up: Four Core laid up together
4. Binder (Double Layer with Overlap): Polyester Tape
5. Shield/Braiding: Copper Wire Braiding
6. Sheath (PVC-FR): Thickness =1.0 mm, Color: Black
7. Printing/Embossing: SQ CABLES BANGLADESH ISO 9001 CERTIFIED 4x0.75 RM ZR-KVVP
300/500 V
30). ZR-KVVRP: 16x0.75 rm (300/500 V)
1. Conductor (Annealed Copper): Circular Stranded (26/0.193 mm)
2. Insulation (PVC): Thickness= 0.6 mm,
Core Color: All Core black with white numbering print
3. Laid Up: Sixteen Core laid up together
4. Binder (Double Layer with Overlap): Polyester Tape
5. Shield/Braiding: Copper Wire Braiding
6. Sheath (PVC-FR): Thickness =1.4 mm, Color: Black
7. Printing/Embossing: SQ CABLES BANGLADESH ISO 9001 CERTIFIED 16x0.75 RM ZR-KVVRP
300/500 V
31). ZR-KVVRP: 3x0.75 rm (300/500 V)
1. Conductor (Annealed Copper): Circular Stranded (26/0.193 mm)
2. Insulation (PVC): Thickness= 0.6 mm,
Core Color: Red, Yellow & Blue
3. Laid Up: Three Core laid up together
4. Binder (Double Layer with Overlap): Polyester Tape
5. Shield/Braiding: Copper Wire Braiding
6. Sheath (PVC-FR): Thickness =0.9 mm, Color: Black
7. Printing/Embossing: SQ CABLES BANGLADESH ISO 9001 CERTIFIED 3x0.75 RM ZR-KVVRP
300/500 V
32). ZR-KVVRP: 2x0.75 rm (300/500 V)
1. Conductor (Annealed Copper): Circular Stranded (26/0.193 mm)
2. Insulation (PVC): Thickness= 0.6 mm,
Core Color: Red & Black
3. Laid Up: Two Core laid up together
4. Binder (Double Layer with Overlap): Polyester Tape
5. Shield/Braiding: Copper Wire Braiding
6. Sheath (PVC-FR): Thickness =0.9 mm, Color: Black
7. Printing/Embossing: SQ CABLES BANGLADESH ISO 9001 CERTIFIED 2x0.75 RM ZR-KVVRP
300/500 V
33). ZR-KVVRP: 8x0.75 rm (300/500 V)
1. Conductor (Annealed Copper): Circular Stranded (26/0.193 mm)
2. Insulation (PVC): Thickness= 0.6 mm,
Core Color: All Core black with white numbering print
3. Laid Up: Eight Core laid up together
4. Binder (Double Layer with Overlap): Polyester Tape
5. Shield/Braiding: Copper Wire Braiding
6. Sheath (PVC-FR): Thickness =1.2 mm, Color: Black
7. Printing/Embossing: SQ CABLES BANGLADESH ISO 9001 CERTIFIED 8x0.75 RM ZR-KVVRP
300/500 V
34). NH-ZR-VV: 3x16 rm + 1x10 rm (600/100 V)
1. Conductor (Annealed Copper): Circular Stranded (7/1.71 mm) & (7/1.35 mm)
2. Fire Proof Layer (Overlap): Mica Tape
2. Insulation (PVC): Thickness= 1.0 mm & 1.0 mm
Core Color: Red, Yellow, Blue & Black
3. Laid Up: Four Core laid up together
4. Inner Covering (PVC): Thickness= 1.0 mm
5. Sheath (PVC-FR): Thickness =1.8 mm, Color: Black
6. Printing/Embossing: SQ CABLES BANGLADESH ISO 9001 CERTIFIED 3x16 rm + 1x10
rm (600/100 V)
35). NH-ZR-VV: 3x10 rm + 1x6 rm (600/100 V)
1. Conductor (Annealed Copper): Circular Stranded (7/1.35 mm) & (7/1.05 mm)
2. Fire Proof Layer (Overlap): Mica Tape
2. Insulation (PVC): Thickness= 1.0 mm & 1.0 mm
Core Color: Red, Yellow, Blue & Black
3. Laid Up: Four Core laid up together
4. Inner Covering (PVC): Thickness= 1.0 mm
5. Sheath (PVC-FR): Thickness =1.8 mm, Color: Black
6. Printing/Embossing: SQ CABLES BANGLADESH ISO 9001 CERTIFIED 3x10 rm + 1x6
rm (600/100 V)
36). NH-ZR-VV: 3x6 rm + 1x4 rm (600/100 V)
1. Conductor (Annealed Copper): Circular Stranded (7/1.05 mm) & (7/0.85 mm)
2. Fire Proof Layer (Overlap): Mica Tape
2. Insulation (PVC): Thickness= 1.0 mm & 1.0 mm
Core Color: Red, Yellow, Blue & Black
3. Laid Up: Four Core laid up together
4. Inner Covering (PVC): Thickness= 0.6 mm
5. Sheath (PVC-FR): Thickness =1.8 mm, Color: Black
6. Printing/Embossing: SQ CABLES BANGLADESH ISO 9001 CERTIFIED 3x6 rm + 1x4
rm (600/100 V)
36). NH-ZR-VV: 3x2.5 rm + 1x1.5 rm (600/100 V)
1. Conductor (Annealed Copper): Circular Stranded (7/0.67 mm) & (7/0.52 mm)
2. Fire Proof Layer (Overlap): Mica Tape
2. Insulation (PVC): Thickness= 0.8 mm & 0.8 mm
Core Color: Red, Yellow, Blue & Black
3. Laid Up: Four Core laid up together
4. Inner Covering (PVC): Thickness= 0.6 mm
5. Sheath (PVC-FR): Thickness =1.8 mm, Color: Black
6. Printing/Embossing: SQ CABLES BANGLADESH ISO 9001 CERTIFIED 3x2.5 rm + 1x1.5
rm (600/100 V)
DESIGN BY CHECKED BY
(MD. JAMIL SHARIF) (MD. IQBAL HASAN)