0%(1)0% found this document useful (1 vote) 1K views46 pagesBoiler MISSION OC Burner System
Boiler MISSION OC Burner System
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
AALBORG TABLE OF CONTEN
Table of contents
System concept (vol. 1)
Technical data. Ms 1
Flow cagrans see 2
MISSION™ OC boiler/accessories (vol.1)
Descriptions
Operation and maintenance
Feed and boiler water
Water level gauge.
Safety valves.
Feed water system
Feed water pump _ : ln io 9
Chemical dosing pump wl
Salinity equipment....[Link] semen ee u
il detection equipment. a 12
Observation and hot well tank. oe
Steam dump equipment sn A
‘Condenser. AS
Drawings.... . se ssn - 16
Data sheets. sist 7
WH MS8Z burner/accessories (vol.2)
Descriptions . eT
‘Operation and maintenance ... 2
Fuel oil supply pumps. 3
Drawings... 4
Data sheets. v vs vs . 5
Control system/electrical eq
ment (vol.2)
Boiler control system,
Burner sequence controller.
Flame safeguard...
Process controller
[Language UK Page 122coscre QQ ED
Alarm panel sn : a
Electric drawings for boiler control panet on . 1
Settings list . : se 12
Data sheets . 13
Spare Parts (vol.2) 7
Spare parts for boiler a ome wld
Spare parts for burner . : se 14
Spare parts for the control panel. old
Page 272
[Language UKAALBORG
TABLE OF CONTENTS
Table of contents
Descriptions
‘Two stage pressure atomising burner
Gas/air separator and filter unit
Language UK
Page Wtailili
AALBORG
THOUSTRIES
Two stage pressure atomising burner
1 Burner description
The bumer is a pressure atomising burner with two nozzles for two-stage operation.
It is capable of burning both diesel oil (DO) and heavy fuel oil (HFO).
The design of the burner makes installation, adjustment and servicing easy. The
burner housing is mounted on the boiler front with side hinges, enabling the bummer
to be swung out. In this case a switch immediately stops the burner.
‘The electrical fan motor is fitted on the side of the housing and is directly connected
to the fan wheel. Via coupling the same motor is connected to the oil pump which is,
a gear-wheel pump providing an operating pressure up to 30 ber.
Mlustra
n of a two-stage pressure atomising burner
lame tube incl. differ,
ignition elecrodes and nozzles
Solenoid valves
Fan bow
il pump
Servomotor
\
Air damper intake Safety valves
Figure 1 ms_OLedr
‘The oil pipes leading the oil from the gas/air separator and the filter to and from the
burner fuel oi! pump are made of flexible hoses.
The burner nozzles are chosen in such a way that the nozzles each deliver approx.
half of the total oil quantity. This means that the boiler is producing half of the
totally rated steam amount when the boiler is running on nozzle 1
Language UK Page 1/2alll
AALBORG
‘Language UK
Se)
To ignite the oil, two ignition electrodes are mounted just above the nozzles. In case
of flame failure in the starting and running mode, a photo cell immediately stops the
burner.
Electric signals corresponding to the pressure gauge board signals open and close
the solenoid valves to the nozzles, and a servo motor regulates the air quantity in
proportion to the oil quantity fired. Adjustment is made by means of a motor driven
‘camshaft on which a number of mechanical cam switches are placed, activating the
same number of electrical switches.
‘The cams can be pre-adjusted, but final adjustment has to be done after measuring
the flue gas contents (CO2 and soot spots).
A diffuser and a combustion head are placed in front of the nozzles with the purpose
of mixing air and oil mist to a suitable mixture.
‘The burner is controlled by a control unit which controls all start/stop sequences,
and in the event of fault conditions the oil supply is always interrupted immediately.
The bumer unit is equipped with a fuel heating system consisting of an oil pre-heater
and heating cartridges. One of the heating cartridges is placed in the nozzle head in
order to keep a sufficiently high temperature close to the nozzles. The nozzle head is
of the re-circulating type which means that fuel oil is circulated in the nozzle head
from the time where the burner is released to start until it begins operation,er Re
TOTNES Ue) 2 Neg
Gas/air separator and filter unit
Description
The gas/air separator and filter unit is mounted on the boiler foundation next to the
burner. The unit is placed in the fuel oil ring line to remove gas or air from the oil
and to avoid abrasive materials to enter the oil pump and burner nozzle(s). A sketch
of the unit is shown in Figure 1
Sketch of the gas/air separator and filter unit
2 Presse regulatng va
From Barer ——+ (C 02 Quek cont wae
ot Tremont
05 remus page
06 Pree Sith auto tnd
OF Presure sich fw ol presore
Tepunery gf 03 Hesing end
. =)
Drsinvalves—{]
astu_Ola.tif
The pressure regulating valve (02) is to be used when adjusting the pressure set
point of the fuel oil system. The pressure switches (07) and (06) are for safety shut
down in case of low oil pressure and start of stand-by pump respectively.
The quick closing valve is equipped with an interlock micto switch used for
stopping of the bumer, thereby preventing the bumer fuel oil pump from sucking oil
when the valve is closed, which will cause cavitation damages in the oil pump.
Further the valve serves as an emergency quick closing valve,
The temperature and pressure of the fuel oil main ring line can be read on the unit
via the mounted instruments.
Language UK Page 1/1alll.
PYIETLIMME TAGLE OF CONTENTS)
Table of contents
OMs560#02
‘Two stage oil burner...
Handling fuel oil. : 7 OM9280#02
Burner fue! oil pump, OMSS60#10
Electric oil pre-heater .usmnnnnnne E cee OMSS60#13
Heating cartridges....:mnssunnnnnnnnnnninnnnnsnnnasnnnnenen OMS5OOEI6
Servomotor.. OMSS60#19
Ignition electrodes eee : : OMss60#22
Combustion head.. . snnnnnnnnnnsnnsenns OMSSOORIS
PhO Cell ssn OM8630#01
Burner housing .aennnnsnnnn . sms OMS560428
Nozzle head . OM5560#30
Nozzle selection...nnmnnn . .»OMSS60#34
Nozzles. a eee snnnennnee OMSSOOH3T
Viscosity-temperature chart. . . oM9280#01
Oil system... OMs560#41
Preservice oon : : OMSS60#50
Start of the bummer... ee OMSS60IS5
Start on diesel oil. —— OM5560#61
Change to heavy fel Off... snes OMSSOORES
Manual operation (OMS560#70
OMS560#90
Page W/talli
AALBORG
Two stage oil burner
General
‘The two stage oil bumer is a pressure atomising bumer capable of burning both
diesel oil (DO) and heavy fuel oil (IFO),
As the burner is a very vital component of the boiler plant, the operating staff should
be thoroughly instructed with regard to the operation of the equipment and the safety
regulations. This is due to the fact that burner problems are often caused by incorrect,
burner operation. With frequently occurring burner faults, the nearest service centre
should be consulted.
‘To ensure a safe and reliable function of the burner it must be inspected at least once
‘a year by a representative of the supplier or by another competent and qualified
person.
4.1 Safety regulations
: To ensure safe burner operation, the burner has to be
commissioned by qualified personnel, and all guidelines in these
instruetions have to be followed.
All safety equipment such as flame sensor equipment and correcting elements may
only be replaced by qualified personnel, which can be ordered by contacting
Aalborg Industries.
‘Warning: Repair of any of the safety components is NOT permitted. Failure to
comply may result in serious injury or death and may cause
considerable damages to the boiler plant.
4.2 Qualified personnel
Qualified personnel according to these operating instructions are persons, who are
confident in installing, regulating and commissioning the burner, and who have
qualifications to carry out this work ic.
+ Persons who are trained to operate electric circuits and units according to the
safety standards,
* Persons who are qualified in the use of dangerous fuel according to the relevant
Jaws and regulations.
Language UK
Page W/tailddllis
AALBORG
HANDLING FUEL OIL
Handling fuel oil
Precautions tol be taken with fuel oil
Fuel oil is usually the residue of crude oil after the removal by
‘most volatile oils and gasses. Fuel oil in its liquid state is very difficult to ignite in
bulk and not capable of spontaneous combustion. However, the vapour is explosive
‘when mixed with air, and being heavier than air, it tends to accumulate in low levels,
‘such as bilges and bottoms of tanks where it may remain undiscovered until ignited
bby a naked light or spark. It is always present in a partly filled oil tank or in a tank
which has contained fuel oil and is given off through the vents from tanks in the
process of being filled
If allowed to continue, a leak in any part of the oil burning system may result in an
accumulation of this explosive vapour.
Ignition of the vapour can be caused by an open light, electric spark, smoking, spark
caused by striking metal, heat from the filament of a broken electric lamp, sparks
from funnel or can be communicated from galley or fires under boilers.
Note: An oil fire cannot be extinguished by water, but may be extinguished by
sand, steam or chemical fire extinguishers.
An intelligent appreciation of the properties of fuel oil as described above is a better
prevention of accident than adherence to any set of rules that may be pre-deseribed,
However, the following detailed precautions should be rigidly enforced:
‘+ When oil is being received, no naked light or electric apparatus liable to spark
should be permitted within 20 meters of the oil hose, tank or compartment,
containing the tank or the vent from the tank, except when special arrangements
are cartied out,
‘© While receiving fuel oil, the storage tank must be closely watched for leaks, and
care must be taken that all outlets from the tank, except the vents, are closed.
‘+ No naked lights or electric apparatus liable to spark should be permitted at any
time in 2 compartment containing a fuel oil tank. Electric lamps used in such
compartments should have a wire protector around the bulb or be of a type that
will ensure the breaking of a circuit through the lamp in the event of the lamp
being broken,
‘* No one should be allowed to enter a fuel oil tank until it has been gas-freed, and
any person then entering the tank must have a properly tended life line around
his body in order to be hauled out if overcome by gas.
‘* Electric fuses and switches, unless the enclosed type, should not be permitted in
compartments containing fuel oil pumps or piping.
© Care must be taken that the wire.
tanks are intact at all times,
gauze protectors in vent pipes from fuel oil
Language UK’
Page 172ailitis
AALBORG
Ua
Dampers, where fitted in the uptakes of the boilers, must be kept fully open
while burning oil. Otherwise, this may result in dangerous accumulation of gas
in the furnace with a resultant blowing out into the boiler or engine room.
The valves on glass gauges in fuel oil storage or settling tanks should be kept
habitually shut, When a reading of the gauge is desired, the valves may be
‘opened, but must be shut again at once.
In each boiler or engine room fitted for oil burning there should be fire
extinguishing apparatus in accordance with the requirements/rules from the
authorities and classification societies in question such as, e.g.: Fire hose,
permanently coupled and of sufficient length to reach all parts of the boiler or
engine room, and either:
(a) a box containing at least 85 litres (2 cubic ft) of dry sand with a large scoop
(b) a chemical fire extinguisher of the tank type
When the fuel oil system has not been in use for a long period, or after joints in
the piping have been re-made, the system should be tested “cold” under a
pressure at least equal to the working pressure before fires are ignited. During
the test a careful inspection for leaks should be carried out,
Fuel oil should not be habitually heated above 65°C for light oils and 120°C for
heavy oils and never above its flash point in any part of the system except in the
bumers.
Care must be taken to prevent accumulation of oil or vapour in any place outside
the system and in ships particularly in bilges under the furnace. This can be
accomplished by rigid cleanliness,
Language UK
Page 22ailidilis
AALBORG
110] aa
Burner fuel oil pump
Language UK
Fuel oi] pump
‘The fuel oil pump is a gear-wheel pump which provides an operating pressure up to
30 bar. The fuel oil pump is equipped with a built-in pressure regulator with a fast
working valve to keep a constant pressure. In order to protect the pump against
impurities in the oil a filter is built-in, An illustration of the burner fuel oil pump is
shown in Figure t
Attention: Please note that the pump is not of the self-priming type. During
commissioning the fuel oi! pump and oil lines must be filled with oil
and properly vented before the burner motor is started. Failure to
comply may cause cavitation damage to the fuel oil pump.
Illustration of a burner fuel oil pump _
Suction ing connection
Oilto nozzle
Return line connection
Pressure regulation
Protective cap
ilinlet pressure, measuring connection
ilpressure gauge port to nzzleair venting
Figure t [Link]
‘The oil line on the suction side of the pump must be primed and the pump vented
before commissioning, otherwise the pump will be damaged due to cavitation, For
cil pump venting, loosen the gauge connection/venting plug (7) after which the
bumer should operate for a while. Air comes out of the hole in bubbles. Retighten
the plug carefully when there are no more bubbles (do not remove the plug from the
hole).
The viscosity of the ofl to the pump should be between 4 — 70 cSt. The diagram in
Figure 2 shows the required oil inlet pressure and temperature to the pump.
Page 1Sauld
AALBORG
NER FUEL OIL PUMP
Diagram for oil inlet pressure and temperature
[Link]
1.1.1 Testing the suetion pressure
Step As Insert a pressure gauge into the suction gauge conneetion (6) to measure the
supply pressure.
1.1.2 Adjust the fuel oil pump pressure
In order to make the final adjustment of the oil pressure the burner must be running,
in normal operation.
Step A: A pressure gauge must be connected into the pressure gauge connection (7)
to measure the oil pump pressure, Do not use hemp or oakum as sealing
material
Step B: Remove the protective cap (5) and set the required oil pressure on the
pressure regulating screw (4)
Step C: Adjust the oil pressure by turning the pressure regulating serew. The
pressure increases by turning the screw clockwise and decreases counter-
clockwise.
‘Step D: When firing diesel oil (DO) the oil must be atomised at a pressure of 14 —
16 bar and on heavy fuel oil (HFO) at a pressure of 18 — 27 bar.
Step E: The final pressure setting can be seen in the “Technical data” section.
1.13 Restart after prolonged burner stop
If the boiler plant has been shut down for a period of time and the plant is started
from cold conditions the following procedures must be taken into consideration:
Step A: The fuel oil transfer pump should be started in order to circulate oil in the
ring-Line system
Step B: Remove the pressure gauge connection (6) and add some oil fo protect the
fuel oil pump from cavitating
Language UK’
Page 2/5alll
AALBORG
Step C: Start the burner and wait until air-free oil appears. Remount the pressure
‘gauge connection again.
Ll Filter
The pump filter requires cleaning at intervals, depending on the condition of the oil
In the event of the filter becoming blocked, excessive vacuum will be the result
Step A: To remove the filter for cleaning extract the eight screws on the fuel oil
pump cover.
Note: After replacing the filter ensure that the pump cover
1.1.5 Pump coupling
A flexible coupling is fitted between the fan rotor and oil pump. When adjusting the
coupling, ensure that there is no axial tension on the pump drive shaft. The coupling
element on the pump should have an axial play of 1 ~ 2 mm, Figure 3 illustrates the
pump coupling.
Ilustration of the oil pump coupling
Figure 3 [Link]
1.1.6 Exchange of the fuel oil pump
If the fuel oil pump breaks down, it should be exchanged with a new fuel oil pump
alternatively with an overhauled spare pump. Aalborg Industries cannot recommend
that the user repairs it. The defective pump should be sent for repair. However, itis
possible to exchange the shaft seal locally by performing the following work steps:
Step A: Unscrew the seal assembly (1) with a lug spanner, see Figure 4,
Step B: Remove the seal assembly (1) without dismantling the parts.
Step C: Remove the shaft (A)
Step D: Clean the hub and shaft (A) without scratching the parts.
Language UK
Page 3/5ailldidis
AALBORG
INDUSTRIES
Language UK
EN page) se) Oi
Step E: Check the surface of the bronze seal face on the shaft (A). If it is damaged
or worn, replace the shaft assembly.
Step F: Refit the shaft (A) in the pump, taking care to engage the slot at the end of
the shaft with the drive key in the gear pinion inside the pump.
Step G: Fit the new seal assembly (1) as illustrated in Figure 4
Step Hi
ighten the assembly.
Milustration of the shaft seal
[Link]
Figure +
Exchanging the fuel oil pump:
Step A: Close the quick closing valve.
Step B: Disconnect the oil hoses and other oil pipes on the fuel oil pump.
Step C: Remove the plastic cover of the observation hole which is found above the
air intake over the fuel oil pump.
Step D: Unscrew the two bolts in the fuel oil pump flange:
Not
The coupling centre piece, between the fuel oil pump and fan wheel is
Joose and may be taken out through the air intake for inspection,
Step E: Place the coupling crosses into the coupling centre piece and draw out the
fuel oil pump. The flexible coupling crosses must be renewed if necessary.
Step F: Remount the coupling part from the fuel oil pump shaft, and place the
coupling part on the new fuel oil pump shaft.
‘Step G: Remount the pressure gauge with cock on the new fuel oil pump.
Page 4/5ailliili
AALBORG
Language UK
Step H: Mount the new fuel oil pump together with the coupling centre piece.
Ensure that the engagement of the two coupling crosses is done correctly
Step I: Screw in the two bolts in the fuel oil pump flange and adjust the tolerance
(gab) between the coupling parts to approximately 1.5 mm.
Step J: Remount pipe and hose connections and open the quick closing valve. Fill
the system with oil and vent it before starting up.
Page S/Saildlilis
AALBORG
Electric oil pre-heater
1 Electric oil pre-heater
‘The electric oil pre-heater, illustrated in Figure 1, is placed on the burner housing
and is used for preheating the fuel oil.
‘The pre-heater is provided with electric heating elements. The produced heat is
conducted to the oil pipes on both sides of the elements via a copper plate. No liq
medium is used for the heat transfer.
The pre-heater has a large heat exchange surface and contains a relatively small
amount of fuel oil. Therefore, it is possible to heat the fuel oil to the necessary
atomizing temperature very quickly. The quick heat transfer equalizes the
temperatures and therefore prevents local overheating, i.e. the fuel oil does not
carbonize.
Fluctuations in oil temperature are minimised by thermostat sensors placed directly
on the heating plate,
‘The pre-heater can handle HFO with viscosity up to 380 cSt. at S0°C.
The maximum obtainable oil temperature is approx. 150°C. Please note that this
temperature depends on the throughput and the supply temperature of the fuel oil.
Mlustrat
\n of the electric oil pre-heater
4 - Regulating thermostat
2.- Temperature limit thermostat
3 - Reset for temperature limit thermostat
4 - Oil release thermostat
Figure 1 ‘[Link]
‘Language UK Page 12ailllilis
AALBORG
ELECTRIC OIL PRE-HEATER
1.1 Setting the pre-heater set point
‘An adjustment of the temperature set point of the pre-heater unit is simple, as only
the regulating thermostat has to be adjusted. Please note that the thermostat has to be
set 10- 15°C higher than the desired preheating temperature on account of the heat
Joss between the oil pre-heater and the nozzle head.
1.2 Safety thermostats
‘The pre-heater is equipped with safety thermostats with a fixed temperature setting,
which is higher than the maximum temperature of the regulating thermostat. If the
oil temperature becomes too high, the safety thermostats shuts down the bumer and
actuates an alarm, e.g, if the regulating thermostat has failed.
‘A signal lamp on the control panel “High oil temperature” indicates this situation.
In case of failure the fault has to be repaired. Before the pre-heater can be taken into
service again, the reset button on the safety thermostat must be activated.
4.3 Release thermostat
The release thermostat or “low temperature thermostat” contacts close and allow the
bummer to start when the fixed minimum temperature setting is reached. The pre-
purge then commences. When starting from cold condition, the release thermostat
will operate several times before the conducted heat will enable the release
thermostat to respond.
A signal lamp on the control panel “Low oil temperature” indicates that the release
thermostat has not yet reached the fixed temperature.
If the oil temperature becomes too low during operation, e.g. if the regulating
thermostat fails to respond or if the heater elements are faulty, the release thermostat,
shuts down the bumer and actuates an alarm.
1.4 Test of the functions
The function of the safety thermostat can be tested by short-circuiting the terminals
to the regulating thermostat. The oil temperature will rise and when the limit of the
safety thermostat is reached, the burner shuts down,
‘The function of the release thermostat can be tested by removing the fuses for the
pre-heater, When the oil temperature drops below the limit of the release thermostat,
the burner shuts down,
Language
Page 272ails
AALBORG
Heating cartridges
Heating units
‘The bumer is provided with a number of heating cartridges used to ensure a
sufficiently low viscosity
The heating cartridges are placed in the fuel oil pump, on the supply and retum
solenoid valves, on the solenoid valve block and in the nozzle head.
4.1 Nozzle head heating
The nozzle head heating system consists of a heating cartridge placed in the nozzle
head, a thermostat also placed in the nozzle head and an electronic P type controller.
The controller is a ROB regulator which can be set between 65°C and 130°C. The
ROB regulator is placed behind the terminal box inside the burner housing.
The release thermal switch in the regulating control is connected in series with the
electric oil pre-heater release thermostat, The system only allows a bumer start after
the selected nozzle head temperature and the minimum oil pre-heater temperature
reached
Language UK
Page 1/1ailidis
AALBORG
Servomotor
Senometar
Air quantity regulation
The air intake is provided with two air dampers which are interconnected. The
servomotor operates the air dampers which regulate the air quantity for the
combustion, Figure 1 shows an illustration of the servomotor and the electric,
connections.
The servomotor is equipped with four cam switches which can be adjusted
individually.
__ Bottom of housing
‘Swish aeration
Swi acter
“cy Sate
focmanta agjesnen)
contol cans
sux enten Parl Lose
aun awich Stage 2
imi etn Full Long
Figure 1 [Link]
‘The setting of the cam switches is as described below. Please consider the degree of
settings only as guidelines as the final settings have to take place afler measuring the
flue gas.
Operating nozzle No. 1
Cam switch No. 2 controls the air dampers when the bumer operates on nozzle 1
The switch should be set between 0° - 50° depending on the bumer size, the nozzle
size, the furnace pressure, etc. It is recommended to set cam switch No. 2 to 25° as a
preliminary setting,
Operating nozzle Nos. 1 +2
Cam switch No, 3 controls the air dampers when the burner operates on both nozzle
No, 1 and nozzle No. 2. The switch should be set between 20° - 90° depending on
the bumer size, the nozzle size, the furnace pressure, etc. It is recommended to set,
cam switch No. 3 to 60° as a preliminary setting.
Language UK
Page 12wlll,
AALBORG
Language UK
Operating the solenoid valve for nozzle No. 2
Cam switch No. | controls the air dampers when the burner control system operates
the solenoid valve for nozzle No. 2. The switch should be set in the area between the
setting for nozzle No. 1 and the setting for nozzle No. 2. This will prevent flame lift
off due to the high air flow when the burner operation changes from one nozzle to
two nozzles. It is recommended to set cam switch No. 1 to approximately 75% of
the setting for cam switch No. 3.
Burner stop
Cam switch No. 4 controls the air dampers when the burner is stopped. The switch
should be set to 0°, This will prevent the boiler from unnecessary cooling.IGNITION ELECTROL
Ignition electrodes
Ignition electrode settings
The ignition electrodes are shown in Figure 1 together with the adjustment
dimensions. As the conditions may vary from boiler to boiler, the indicated
dimensions should only be considered as guidelines. If ignition problems emerge, &
more favourable adjustment of the electrodes, suitable for the present conditions,
must be found by experiments.
Illustration of ignition electrode settings
_Tantion tctoe,
Sloane
Figure 1 [Link]
‘When the ignition electrodes are adjusted, the following must be observed:
‘© The distance of the ignition electrodes to the nozzle and diffuser should be
checked.
+ The ignition electrodes must not be touched by the atomising oil spray.
* The distance of the ignition electrodes to the diffuser and the nozzle must
always be lager than the distance of the spark gap.
If a nozzle with a larger spray angle is fitted, the electrodes must be adjusted
backwards, or perhaps be bend slightly upwards,
Language UK.
Page WtAALBORG
INDUSTRIES
Combustion head
1 Distser
2 Oilzonte
3. Combustion need
Adjustment of the combustion head and
the diffuser
‘The combustion head and the diffuser are marked with their type designation. ‘The
identification of the flame tube is stamped on the neck, and the external diameter of
the diffuser is stamped on the side towards the burner
The oil burner is delivered with a combustion head and an air diffuser dise that suit
the specified boiler type and oil quantity in the best way.
If further adjustment is needed to obtain the best possible combustion performance,
this is done by moving the combustion head and/or the air diffuser disc. Doing this,
make sure not to change the position of the ignition electrodes and thereby
disturbing a proper spark formation: It should also be noted that it is important that
the air diffuser disc is placed in a small distance in front of the nozzle(s) in order to
keep a sufficient cooling on the nozzle(s).
Figure | and Table | shows the different combustion heads, types, dimensions and
‘measurements.
[Link]
[Language UK
Page 1/2ail,
AALBORG
Combustion heads
Combustion head type
Diffuser dise [
MS/2a
125 x40
125% 40
13x40
155x530
Mala f
Mei
Malla
Moria t 165 x 50
NOVI i 185x50
ccemmeaiD 185% 50
200% 50
220% 50_
Mit L 24570
MI I Ei
Ga { 165 x 50
Ga { 175x50
165 x 50
‘Language UK
Page 22alll,
AALBORG
Photo cell
1 Description
The RAR7 detector is used for supervision of yellow burning oil flames. If the photo
cell detects a missing flame, the burner stops instantaneously. It is not possible to
start the burner before the control system has been reset.
With this type of detector, the radiation of the oil flame in the visible band of the
light spectrum is used to generate a flame signal. The light-sensitive element is a
selenium photo cell. When illuminated, it generates DC voltage which causes a
current to flow to the input of the flame signal amplifier in the control unit. Hence,
the selenium photo cell is an active detector.
The cell is insensitive to infrared radiation. If the bumer is started with an
itluminated combustion chamber, e.g. due to glowing firebrick, the start sequence of
the burner commences, but an alarm for flame failure will be indicated
‘The number of photo cells for automatic operation and emergency operation depend
‘on the classification society.
4.4 Commissioning
‘The intensity of the light radiation can be checked by measuring the detector current
by means of a DC ammeter (internal resistance 5000 W). Figure 1 shows the
‘measuring cireuit. The photo cell is adjusted by changing the position in proportion
to the oil flame in order to obtain the maximum detector current,
Note: If the wiring of the photo cell is connected incorrectly, it is not possible to
start the oil burner.
‘Measuring cireuit
9 10 LAEIO
2 24_LAL2.., LOKIG,
Ammetor |
‘connection
ADC
Figure 1 [Link]
Language UK Page 1/1alll
AALBORG
Burner housing
1 Burner swing out
‘The bumer swing out switch breaks the interlock circuit to the burner if the burner is.
opened at the hinged flange. Before the burner can be started, the burner control
system must be reset.
A cover for inspection and cleaning of the air duct is fitted on the top of the burner
housing. The electric terminals and the ignition transformer are located on the left
side behind the cover
3 Inspection of the oil flame
‘The boiler is provided with an inspection hole for manual supervision of the oil
flame. The sight glass is air-cooled. The fan motor on the burner supplies the sight
lass with the necessary cooling air through a tapping in the air duct.
Language UK Page 1/1iil,
AALBORG
Nozzle head
1 Re-circulating nozzle head
A basic piping diagram of the fuel oil system at the nozzle head is shown in Figure
1. The system is constructed with a return line and a recirculating nozzle head,
‘When the fuel oil has been heated to the minimum oil temperature, the burner start is,
released, and the oil system at the nozzle head is filled with oil. The shut-off device
in the nozzle heed remains closed preventing the fuel oil from flowing through the
nozzle.
‘After pre-purge the solenoid valve (5) in the return line from nozzle 1 is closed
causing the pressure in the nozzle shut-off device to raise, and at a pressure of
approx. 12 bar the shut-off device opens to commence burner operation in stage one.
For burner operation in stage two the solenoid valve (6) is opened after a certain
time delay, and the pressure is applied to the shut-off device in nozzle 2.
‘Subsequently the burner is operating in stage two.
‘The pressure in the return line is checked by the pressure switch (7). Ifthe pressure
is too high, the burner shuts down, e.g. due to a faulty solenoid valve. The shut-off
devices (4), (4a) and (6) will close, and at the same time the solenoid valve (5)
opens.
‘The closure around the two nozzles shut-off devices will prevent oil from dripping
from the nozzles,
Basic piping diagram of the oil system at the nozzle head
1-01 pump [
2-01 preeaer
4 Saf cleo wae (nona ces)
Salty scent va rt oe)
fori aie (raaloer
8: Seon vate raat aoe)
7 bree out
‘Figure 1 noz_systedr
‘Language UK age Wtailili
AALBORG d eh)
Nozzle selection
1 Description
On the two stage bumer the total bumer capacity must be divided between the two
nozzles. Usually nozzle | is sized to have sufficient capacity for approximately half
Of the load, and of course nozzle 2 is sized to have a capacity for the other half of the
load. A different nozzle ratio may be required depending upon the heat demand and
design of the heating appliance, e.g, boilers with high or low chamber resistance
If the nozzles have to be changed, e.g. due to change in the wanted boiler
performance, the size of the new nozzles can be selected by means of the charts,
shown in Figure 1
The nozzles are of the semisolid type with a spray angel of 60°.
Please note that a change in the oil pressure causes a change in the oil throughput as
shown in the nozzle capacity chart.
Page 172
‘Language UKalll
AALBORG
Nozzle capacity charts
Pressure bar
{at the nozzle)
6 + Z
2 suet nosttgiins © 2 70 8 8 1D Hao ND,
Disa ony = 086 Lag hint
So perry TEE TT
ie 20 258 303 4 as 50 GD. 70 BD WO 100110
Luasium oy = 0:83 [saiam Tigi
Medium oi : oe
2 25. 30 a5 40 45 80 B70 BD 9 100 120
Heavy oi" 8.97 [satan | tes
Oil throughput RS eee epee pee
a S070 IHD | HO HO
Pressure bar
{at the nozzle)
00 120140180 180 200 20 © 300-30 400,
00
Diatilate 0 y= 0.84 (Agi) in
a ee epee per ey
9 100 120, 140 160 180 200 280 300 360.40. 500
Magia oi y= 0.85 fsa? } ing
eg weet
wo” 10140” 160 tbo 200 280 300-380” 400 480 GO
Hea oily = 0.87 [hatin
Oil throughput ee pe ‘eqn
+ mo 140180" 180 200.” 250" 300380" "400" 450" 500 580
ikon
Figure 1 nozsizestif
‘Language UK Page 2/2li,
AALBORG
Nozzles
NOZZLES Ot Ae)
Fitting and removal of nozzles
‘A nozzle can be replaced without affecting the function of the hydraulic nozzle shut-
off valves,
Inspection and change of the nozzles are easily done as the bumer is constructed
with a swing flange.
Exchanging of an oil nozzle:
‘© Unscrew the fock-nut, and the casing can be swung out,
‘© For mounting/dismounting use a spanner and keep the nozzle head fixed by
means of another spanner
‘© After replacing the nozzle ensure that itis tight
‘0 prevent entry of air into the oil system it is advisable to close the stop valves in
the suction intake and return line during exchange of the nozzle.
As a general rule a nozzle should always be exchanged if it is dirty or worn out. A
good bumer performance can only be guaranteed with a new and/or a clean nozzle.
‘The nozzles should only be cleaned due to a shortage of nozzles.
‘The nozzles should be dismantled into individual parts and washed in a suitable
fluid such as benzine or petrol. If available, compressed air is the most suitable
cleaning medium.
Note: Solid objects such as steel needles are completely unusable, and they are
under NO circumstances to be used as cleaning tools,
Note: Nozzles cannot be returned for credit or exchange.
When extra oil nozzles are ordered please state the through-put in US Gal’h and the
spray angle.
Language UK|
Page W/1ills,
AALBORG
yaa
VISCOSITY - TEMPERA’
Viscosity - temperature chart
‘Language UK
Description
‘The preheating temperature can be determined by means of the viscosity -
temperature chart shown in Figure 1. In order to use the chart, the viscosity of the
fuel oil must be known ata reference temperature.
Tt should be noted that the preheating temperature should be set somewhat higher
than the temperature shown in the chart due to the heat loss between pre-heater and
nozzle/eup,
4.4 Example
‘The example is based on a pressure jet burner.
Know!
Oil viscosity: 380 eSt, at 50°C
Required:
Preheating temperature in
Procedure to be followed:
Step A: Follow the reference temperature line at 50°C vertically down to the
intersection with the 380 cSt. viscosity line.
Step B: From this point move parallel down with the nearest fuel grade line.
Step C: When the line meets the
up to the temperature axis
commended nozzle viscosity line, go vertically
Step D: At this point read the desired preheating temperature of 150°C.
Page 12a gu eee
Saeeeige tsetse
Reoanentet v0
cosy fr ese somiingbumere
‘Figure 1
Language UK,
Page 22ailddidis
AALBORG
ole) 1]
Oil system
Language UK
Description
This section describes the oil system in general terms together with some of the
requirements needed to have a safe and reliable burner operation.
The fuel oil transfer pumps draw either diesel oil (DO) or heavy fuel oil (HFO) from
the oil tanks and pump it in the fuel oil ring line via a gas/air separator unit including
a quick closing valve and a filter to the burner.
From the bumer excess oil is, via the return line, led to the gas/air separator unit
from where the oil transports the separated gases back to the fuel tank. Before the
mixture reaches the oil tank, a pressure regulating valve also located on the gas/air
separator unit ensures that the oil pressure in the ring line is between 1.0 and 5.0 bar.
‘A three-way ball valve leads the oil to the correct tank (DO or HFO).
From the oil pump, the oil is forced through a safety solenoid valve, which is open
when the burner is running. Then through the electric oil preheater where the oil is
preheated to the desired temperature suitable for a proper atomisation.
From the pre-heater, the oil is lead to the nozzle head. When the burner is started,
the oil is forced to circulate through the nozzle head before being ignited to ensure a
sufficiently high temperature of the oil, This period is called the pre-purge time
because the furnace is ventilated at the same time. After ignition, a flame will be
established, and the bumer is now running in normal operation.
In general it is recommended that the pipe lines to and from the fuel oil transfer
pumps are dimensioned so that the velocity inside the suction pipe does not exceed 1
m/s and so that the velocity inside the pressure pipe does not exceed 3 mis.
Whenever a boiler plant is intended to operate on heavy fuel oil, all pipes carrying
fuel oil must be insulated and traced in order to keep a sufficiently low viscosity of
the oil.
The tracing can be done either by means of steam heating or by means of electric
heating cables. The fuel oil must be prebeated to a temperature which secures the oil
pumps suitable operating conditions.
The oil pipes to the burner are made of flexible hoses. This enables the burner to be
swung out for service. During work on the oil system or the burner, the quick
closing valves should always be closed.
Page Wtallltdlis
AALBORG
Pre-service
UK
Pre-service inspection
These pre-service instructions imply that the previous paragraphs describing the
individual parts of the burner have been studied very thoroughly. The necessary
adjustments of the oil pump, the electric pre-heater, the combustion head, the
servomotor and the ignition electrodes must be made before proceeding further with
this instruction
Before the burner is started, the special instructions for the boiler and the contro!
system shoutd be consulted.
Step A: Switch on the “MAIN SWITCH”, and reset the switch for “CONTROL,
VOLTAG
Step B: The water level indicator alarm and “Water level low low” should be tested
by raising and lowering the water level in the boiler. It might be necessary
to make adjustments
It should also be checked that the start/stop signals are given to the feed water pump
unit
Step C: The set points for the pressure switches listed below should be adjusted:
“Steam pressure high”
“Steam pressure low”
‘© Set point for “NOZZLE 1” (start/stop)
‘© Set point for “NOZZLE 2” (start/stop)
‘¢ “Fuel oil pressure Low” in the ring line
‘* “Fuel return line pressure high” (only burners capable of burning HFO)
¢ “Start stand-by oil pump”
Step D: The functions and set points should be checked after remounting,
Step E: The burner swing out alarm and funetion are tested by opening the burner
flange.
4.2 Fuel Oil transfer pump
Tho fuel oil transfer pump can now be started, but before doing this, please consult
the instructions for the fuel pump.
age 13AALBORG
INousTRies
Note: Before the fuel oil transfer pump is started, make sure that the oil system
has been flushed and is free of foreign objects which can damage the
pump unit.
Step
Vent the fuel oil transfer pump.
Step B: Open the valves for the diesel oil tank, and close the quick closing valves to
‘the oil burner. Start the fuel oil transfer pump.
Step C: Check that the fuel oil transfer pump is running with the correct direction of
rotation,
Step D: Adjust the oil pressure in the ring line at the pressure regulating valve to
min. 1.0 bar and max. 5.0 bar.
Step E: Check for leakage.
4.3 Check of the burner motor and the control system
‘The burner motor and control system should now be checked.
Step
Disconnect the electric power to the burner motor
Step B: Set the switch for oil type in position “DIESEL O1L”
Step C: Adjust aux. switches in the servo motor roughly according to the following
proposals:
* Cam-switch No. L 10.30°
© Cam-switch No. 2: send?
© Cam-switeh No. 3: san sen OO?
© Cam-switch No. 4: 0°
‘Step D: Switch to burner mode: “REDUCED LOAD AUTO”.
The bumer sequence control box will give a signal to the servomotor, and the air
damper opens for purge. After the fixed purge time is expired, the servomotor will
‘get a signal from the sequence control box to close the air damper and commence
the ignition load.
‘The ignition transformer will be energised.
After the pre-purge time, the solenoid valve for nozzle 1 will be energised, The
photo-cell is now waiting for illumination from the flame. As the burner motor is not
running due to the disconnected power, the control box will cut out after max. five
seconds. The control panel will give an alarm for "Flame Failure"
‘heck and simulate a flame
the photo cell.
Step
ignal by using a flash light pointed directly at
If the simulated flame is not present, reverse the two photo cell wires for the correct
polarisation and repeat the flame failure check.
Before checking nozzle 2 make sure that nozzle | is simulated to run by the use of a
flash light as described above.
Language UK
Page 2/3ailiidls
AALBORG
INDUSTRIES
Language UK
Step F: Switch to burner mode: “FULL LOAD AUTO”.
When the servo motor has reached the cam switch opening for operation with nozzle
1 and nozzle 2, the solenoid valve for nozzle 2 will be energised
When the flash light is switched off, the control panel will shut off the power to the
solenoid valves and initiate a “lame failure” alarm,
‘Step G: Open the quick closing valves.
‘Step Hi: Close the isolating valve for the pressure gauge at the burner fuel oil pump
and unscrew the pressure gauge,
Step I: Open the isolating valve for the pressure gauge very slowly and ventilate the
pump and oil hoses.
‘A mixture of diesel oil and air is led out.
Step J: When the diesel oil is free from air close the isolating valve and mount the
pressure gauge,
Step K: Mount the burner motor fuses.
‘Step Li Set the bumer mode to “MANUAL MOTOR” and let the burner run for
approximately five seconds before stopping it
Step M: Open the bumer flange, and check that the nozzles have not sprayed oil
into the furnace.
Step N: Close the burner again.
Step O: Start the bumer, and check that the oil pump pressure is within the limits
listed below.
© Diesel oil: 14-16 bar
# Heavy fel off: on nnnnnnnennn oF 18-27 bar
Final setting of the oil pump pressure should be done when the burner is running in
normal operation,
Step P: Open the burner flange again, and check that the furnace is free from oil
‘The burner is now ready for start-up,
Page 33ails
AALBORG
START
Start of the burner
Description
This section describes the necessary testing actions during start of the burner.
Note: Before the burner is started the set points for the safety device and the
water level controller should be checked according to the separate
instructions.
Before the burner is started be sure that the water level is around “NORMAL
WATER LEVEL”
Step A: Set the burner mode to “REDUCED LOAD AUTO”, and the burner will
start automatically
The servomotor will move to maximum position (pre-purge position) and after the
pre-purge time back to ignition position. The ignition takes place, the solenoid valve
1 is actuated and the flame is established.
IF the flame is not established, it may be necessary to adjust the ignition electrodes.
1.2 Check of the cam switch settings
If the combustion does not receive enough air, it will emit smoke. In this case:
Step A: Stop the bumer, and adjust the position of cam switch No. 2 on the
servomotor.
Step B: Now restart the burner.
When the burner is running correctly on nozzle 1, then:
Step A: Switch to “FULL LOAD AUTO”, and the bumer will run on both nozzle 1
and nozzle 2.
If the combustion emits smoke running on both nozzle 1 and nozzle 2, then:
Step A: Stop the bumer, and adjust the position of cam switch No, 3 on the
servomotor,
‘Step B: Now restart the bumer.
Note: Cam switeh No. 1 should be set in the area between the setting for cam
switch No. 2 and the setting for cam switch No. 3.
Language UK.
Pege 13aillili,
AALBORG
STS SO] gana ecient
1.3 Manual operation functions
‘Test the manual operation functions:
Step A:
et the bumer operation switch in position “MANUAL MOTOR’
‘The burner motor should run approximately 100 seconds to ensure that the furnace
is free of oil gases
Step B: Set the burner operation switch in position “MANUAL IGNITION”
After the purge period (approximately 100 seconds), a spark will appear between the
two electrodes.
Step C: Check that the spark is visual
Step D: Set the burner operation switch in position “REDUCED LOAD
MANUAL", and a flame will be established.
Caution: The safety device for flame failure does only fan automatic
operation. This means that the operator has to control the flame at all
times. The burner can be equipped with a cut out device for manual
operation, but this depends on the classification socie
Step B: Set the burner operation switch to position "FULL LOAD MANUAL" in
‘order to run on both nozzle | and nozzle 2.
Not
In manual operation the pressure switches for startstop nozzle 1 and
start/stop nozzle 2 are interrupted. This means that the burner does not
stop until the set point for the high steam pressure switch is reached.
1.4 Check of the fuel oil system
Step A: Check the “STAND-BY PUMP STARTED” function, Stop the fuel oil
transfer pump in operation while the other pump is kept in stand-by mode.
‘When the pressure (see pressure gauge) drops to the set point for start of the stand-
by fuel oil pump, an alarm will appear and the stand-by pump will start.
Step B: Check the “Low oil pressure” in the fuel oil ring line. Stop the fuel oil
transfer pump in operation while the other pump is in off position.
When the oil pressure (see pressure gauge) drops to the set point of the pressure
switch in the fuel oil ring line, an alarm will appear and the oil burner will stop,
The following only applies for burners capable of running on HFO.
Check the alarm for high pressure in the fuel oil return tine, ie. “Fuel return fine
Pressure high”. The following should be done:
Step C: Open the rod connection between the quick closing valves at the bumer and
observe the burner cut out when the oil pressure raises to the set point.
[Language UK
Page 2/3ailliiis
AALBORG
SUA Rema ey (ois,
Step D: Open the return valve again and refit the rod connection.
4.5 Check of the steam pressure alarms
‘Step A: Check the low steam pressure alarm by lowering the steam pressure below
the set point.
‘Step B: Check the high steam pressure alarm by raising the steam pressure to the set
point, and observe if the burner cuts out,
1.6 Check the pressure switches for start/stop of the burner
‘The bumer functions must be tested together with the control panel even if the
pressure switches are adjusted and the functions are tested in a testing unit
‘Test of the pressure switches in a testing unit can only be considered as a rough test,
and therefore all the set points should be checked again by running the burner in
automatic mode, i.e, “REDUCED LOAD AUTO”.
1.7 Check of the flame detection and burner swing-out
‘The bumer must be running in automatic mode.
Step A: The flame detector is checked by removing the photo cell from the burner
housing and covering the sensor.
‘The burner will cut out after two seconds and give an alarm for flame failure, Ifthe
bummer is running in ignition mode, the cut out time will be five seconds.
‘The burner swing-out should be checked when the burner is running, This is done as
follows:
Step B: Screw out the screw which holds the bumer flanges together and very
carefully open the burner.
‘When the burner is opened a few mm, it will cut out for burner swing out.
Language UK
Page 3/3aillillis
AALBORG
Start on diesel oil
Line of procedure
Usually the burner is operated on diesel oil (DO) when the boiler/steam system is
cold and heating is required.
Note: Please refer to the boiler instructions for information about heating up a
cold boiler.
‘The following briefly describes how the bumer is started on DO.
Step A: Check that DO is available in the DO tank.
Step B: Switch on the “Main switch’.
Step C: Reset the switch for “Control voltage”.
Step D: Change fo “Diesel oil” position.
The alarms for “Water level low low”, “Steam pressure low", and "Low oil Pressure
in ring line" are on.
Step E: Open the air valve on top of the boiler
Step F: Check all other valves on the boiler.
Step G: Start the feed water pump.
Step H: Start the fuel oil transfer pump and check that the oil pressure in the ring
line is between 1.0 and 5.0 bar, normally 2.0 bar.
Step I: If necessary, adjust the oil pressure by use of the pressure regulating valve.
Step J: When the water level is normal, reset the alarms at the reset switch. Only the
alarm “Steam pressure low” should be visible.
Step K: Check that the quick closing valves between the gas/air separator and
burner are opened.
Step L: Switch the burner on “REDUCED LOAD AUTO”, and the bumer motor
will start,
oi
to the pre-p
now circulating through the burner system, and the servomotor moves
ge position. After the pre-purge time, the servomotor moves to ignition
ition takes place, and after 2.5 s the solenoid valve for nozzle 1 is
actuated, This closes the re-circulation line, and diesel oil will be sprayed into the
furnace. The atomised diesel oil will be ignited, and the flame will be established.
Language UK
Page 172aililis
AALBORG
START ON DIESEL OIL
When the boiler is cold and depres
“REDUCED LOAD AUTO"
‘When the steam pressure rises above the low steam pressure set point, the burner
mode can be changed to “FULL LOAD AUTO",
surised, the burner must only operate on nozzle 1
Caution: The main steam valve should always to be opencd very slowly to
avoid water and steam shocks.
Note: Never mix heavy fuel oil and diesel oil.
Language UK
Page 22ails
AALBORG
INDUSTRIES
(ora c =ena Nae
Change to heavy fuel oil
Line of procedure
Language UK
When heavy fuel oil (HFO) is to be used, the fuel oil must be pumpable. This is
done by turning on the tracing system on the fuel oil pipe lines. The temperature of
the HFO should be approximately 75°C. Then the fuel is heated in the pre-heater.
‘The pre-heater temperature set point can be read from the temperature-viscosity
diagram
——
thermostat for regulating the set point is placed behind the cover of the pre-heater.
At bumer installations with the pre-heater type WEV (high viscosity HFO), the set
point is adjusted on the CROw regulator placed in control panel.
‘When the burner mode is changed from DO to HFO, the following should be done:
Step A: Open the oil valves to the heavy fuel oil tank,
Step B: Change position of the three-way valve at the fuel oil tanks to operate on
HFO instead of DO.
The limit switch on the three-way valve will connect the electrical pre-heater with
the tracing system on the bumer (i.e. heating of nozzle head, solenoid valve, bumer
il pump, efc.). Furthermore, this action connects the low oil temperature alarm,
which causes the burner to shut down due to low oil temperature alarm.
Step C: Check that the oil pressure in the fuel oil ring line is around 3.0 bar, and
adjust it, if necessary.
Step D: Reset the alarm on the boiler control panel.
+: Set the burner mode to “MANUAL MOTOR” and let the burner motor run
until the HFO is heated to a service temperature of approximately 75°C at
the fuel oil supply pump.
Step
‘Step F: Switch the burner mode to “AUT” when the HFO service temperature has
been reached.
After about 50 seconds, the pre
flame is established
If the oil is t00 cold, the burner may cut out after about 50 seconds. In this case reset
and try a new start. The oil temperature should be high enough at this point.
urge period begins, and about 25 seconds later a
Step G: When the boiler has been heated, the burer mode can be change to “FULL
LOAD AUTO".
Page U2ailddidis
AALBORG
CHANGE TO HEAVY FUEL OIL
1.2 Start on cold HFO
However, if the burner has been stopped while running on HFO and has been out of
service for a long period, the fuel oil ring line is filled with cold oil. It is important
that the bumer is started very carefully as described below
Step A: Switch on the power for the control panel with the burner in off position.
Step B: Start the tracing on the fuel oil ring line, and start the fuel oil transfer pump.
Set the bumer mode to “MANUAL MOTOR” and let the burner motor run
until the HFO is heated to a service temperature of approximately 75°C at
the fue! oil supply pump.
Step
‘Step D: Set the burner in “MANUAL IGNITION” mode and let it run for a few
seconds when the HFO service temperature has been reached
Step E: Stop the bumer again,
Step F: Switch the bumer mode to “AUT” if the pump has no difficulties in
circulating the oil
If the oil is too cold, the burner may cut out after about 50 seconds. In this case reset
and try a new start, The oil temperature should be high enough at this point.
Step
‘When the boiler has been heated, the burner mode can be change to “FULL
LOAD AUTO”
Language UK
Page 222alll
AALBORG
felt
Manual operation
General
In the rare event of a total break down of the control system, the bumer unit with
belonging systems can be operated in manual operation (also called emergency
operation). Due to the fact that the majority of the safety interlock trips and alarms
are overruled in emergency mode, the safety precautions for the plant must be
observed very carefully
Please note that in emergency operation mode the safety interlocks are reduced to:
* Too low water level
© Flame failure
© High steam pressure
© Burner swing out
© Overload burner motor
© High oil pressure in burner return line (if provided)
Warning: When the burner operates in emergency mode, it is very important
that the boiler plant is carefully and continuously supervised by the
ship engineering personnel. Pay special attention to the steam
pressure and water level.
In emergency mode, the bumer unit and supply systems are operated from the
control panel. Various operating switches are provided on the panel for operating
purposes.
Before emergency operation of the burner is initiated, attempts to restart the control
system must be performed, If restart of the control system is impossible, the work
steps of the following sections must be followed.
Manual operation of the burner
The following instructions must be observed step by step during manual operation of
the burner:
Step A: Start one of the fuel oil pumps on the operating switch.
Step B: Switch the burner operation switch to position “MANUAL MOTOR" to
start the burner fan motor and commence the pre-purge period.
Step C: The pre-purge time should be approximately 60 seconds,
Language UK,
Page 172AALBORG
Inpustetes
Insufficient purging may cause danger of furnace explosions. If the
operator suspects that there is a risk of an oil spillage in the furnace,
it must be completely dried out before start of the burner is
attempted.
Step
Switch the burner operation switch to position “MANUAL IGNITION” to
energise the ignition transformer. ‘The electrodes will ignite after
approximately 30 seconds,
Step E: Check that the oil pressure is correct and that the ignition is on,
Step F: Switch the burner operation switch to position “REDUCED LOAD
MANUAL” to open the solenoid valve for nozzle 1
Step G: When the flame is established, the bumer will be firing with nozzle 1 in
operation. If the flame does not appear within five seconds, immediately
return to step B.
Step He If full load is required switch the burner operation switch to position
“FULL LOAD MANUAL”
Not
: If the burner operation switch is switched directly from position “OFF”
to position “REDUCED LOAD MANUAL, the minimum start time will
be 30 seconds. The fixed minimum start time ensures the boiler against
potential furnace explosions.
Note: The automatic water level regulation is not operational in emergency
mode. This means that the water level in the boiler must be adjusted
manually.
Step I: In boiler plants with on/off regulation of the water level, one of the feed
‘water pumps should be started and stopped according to the water level in
the boiler.
Step J: In boiler plants with modulating control of the water level, one of the feed
‘water pumps should be started. The water level can then be regulated on the
feed water control valve by means of the manually operated hand wheel on
the actuator.
Language UX
Page 272AALBORG
INDUSTRIES
Faults and rectifying faults
1 Trouble shooting
If faults oceur, the basic necessary conditions for operation must be checked:
‘* _Iselectric power supply available?
© Is oil available in the tanks?
‘© Are all the regulating controls, such as boiler pressure controls, low water
switches, safety cut out, etc. correctly adjusted?
If the cause of the fault is not due to any of these conditions, the functions connected
with the individual bumer parts must be tested according to the fault finding chart in
Table 1
Fault Finding Chart
Obse ‘Case Elimination of fale
‘Ignition —
‘No ignition ] Ignition electrodes short - circuited Adjust ~
Ignition elstodes oo far apart ‘Adjust
| Hlecwodes diy or damp Clean
Ignition transformer detective Exehange
Insulator cracked Exchange
| ignition cable charted Exchange, find and climate ense
jee Burner contol defective Exchange =
3 Mou — — =
Does not rar Fuses dcecive Exchange
Onerload ay elesed Aust
nase deseo eee peer
30 Paap — —
Feeds no oil Gear daiagst Tachange
Coupling damaged Exchange
Suction valve leaking Remove and clan or exchange
Oil ines leaking Tighten
Stop valves shit Open
Fier clogged Clean
Filter faking Exchange
Quick scion valve leaking Exchange pump
Capacity as decreased Exchange pump
Toad mechani wae Pup sucks at Tighten treads
‘Vacum in the ol inet high Cea ier, open valves completely
a Cold Heat up the
Sones =
Tineven atomization Sop se Remove noade ighien Swit pag
Bare partly clogasd Exchange nozzle
Filer heavily contaminated Exchange nozae
‘Nozzle wor out on account of age Exchange nozzle
Neate at Tozzi shut off efetve 7 Brechange nozzle
Nol pasage ‘Noval logged sian eae
5 Burner Coniral with Flame Detector
Does nt respond [ Flame dior diy Can
Language UK Page 1/2alll,
AALBORG
FAUI
TESyAN ORS ent ache ALC]
[ Motordoes nornam T Burner sontoh dea T Exchange
____| sevomotor detest Chock lini switches =
No inion Burner coneol deat Exchange
aa Servomotor defect = Check imi switches =
Lock ow lamp lights up] Flame faut The
© Combustion Head —
cil, oF ha he
Wis intemally heavily fouled by
avy catbon deposit
Wrong adjustment
Wrong combustion head
Nozzle tas big of too small
Combustion ae quantity to large or too small
Boiler room not suficently ventilated
Low oil emperatre
] Canect adjustment dimensions
| Exchange
Exchange
Readjst bummer
Start blowing fan in the engine room
| Heat up tho oi,
Does not open
[Burmer control defective
Relay defective
| Exchange coil
| Exchange bumer control
Exchange
Does not cess Wehily
~] Contaminating particles on the sealing surace—
‘1
| Seat at valve desta _
Exchangs
‘Open valve, clean set
‘Burner does
ot siare
| Reteass thermostat doesnot Tass
Release thermostat defective
Release thermostat not wtached tightly
Therease the oil isaperalare adjustment on the
regulating thermostat,
Exchange release thermostat
Atach release thermostat
Language UK
Table 1
Page 2/2