8/9/2019 1:32 PM 1 / 3
Device Info
ACS580
Type
Model ACS580
Serial ASCC170x
Drive parameters
Index Name Value Unit Min Max Default
12. Standard AI
3 AI supervision function Fault NoUnit 0 4 No action
15 AI1 unit selection mA NoUnit 2 10 V
17 AI1 min 4.000 mA 0.000 20.000 0.000
18 AI1 max 20.000 mA 0.000 20.000 10.000
20 AI1 scaled at AI1 max 100.000 NoUnit -32768.000 32767.000 50.000
13. Standard AO
12 AO1 source Motor current NoUnit Output frequency
18 AO1 source max 290.0 NoUnit -32768.0 32767.0 50.0
19 AO1 out at AO1 src min 4.000 mA 0.000 22.000 0.000
22 AO2 source Motor speed used NoUnit Motor current
28 AO2 source max 100.0 NoUnit -32768.0 32767.0 30000.0
29 AO2 out at AO2 src min 4.000 mA 0.000 22.000 0.000
20. Start/stop/direction
1 Ext1 commands In1 Start NoUnit 0 14 In1 Start; In2 Dir
22. Speed reference selection
11 Ext1 speed ref1 AI2 scaled NoUnit AI1 scaled
12 Ext1 speed ref2 AI2 scaled NoUnit Zero
18 Ext2 speed ref1 AI2 scaled NoUnit Zero
19 Ext2 speed ref2 AI2 scaled NoUnit Zero
28. Frequency reference chain
11 Ext1 frequency ref1 AI2 scaled NoUnit AI1 scaled
Drive composer pro v. [Link]
8/9/2019 1:32 PM 2 / 3
Index Name Value Unit Min Max Default
30. Limits
11 Minimum speed 0.00 rpm -30000.00 30000.00 -1500.00
13 Minimum frequency 5.00 Hz -500.00 500.00 -50.00
17 Maximum current 348.10 A 0.00 498.10 498.10
30 Overvoltage control Disable NoUnit 0 1 Enable
31. Fault functions
22 STO indication run/stop Warning/Warning NoUnit 0 3 Fault/Fault
45. Energy efficiency
19 Comparison power 160.00 kW 0.00 10000000.00 0.00
46. Monitoring/scaling settings
1 Speed scaling 1000.00 rpm 0.10 30000.00 1500.00
50. Fieldbus adapter (FBA)
4 FBA A ref1 type Frequency NoUnit 0 5 Speed or frequency
6 FBA A SW sel Transparent mode NoUnit 0 1 Auto
51. FBA A settings
2 Node address 22 NoUnit 0 65535 0
3 Baud rate 1500 NoUnit 0 65535 0
4 MSG type PPO4 NoUnit 0 65535 Not detected
5 Profile ABB DRIVES NoUnit 0 65535 PROFIdrive
6 T16 scale 99 NoUnit 0 65535 0
52. FBA A data in
2 FBA A data in2 Act1 16bit NoUnit None
3 FBA A data in3 1.7[16] NoUnit None
4 FBA A data in4 1.14[16] NoUnit None
53. FBA A data out
2 FBA data out2 Ref1 16bit NoUnit None
Drive composer pro v. [Link]
8/9/2019 1:32 PM 3 / 3
Index Name Value Unit Min Max Default
95. HW configuration
1 Supply voltage 380...415 V NoUnit 0 6 Automatic / not selected
4 Control board supply External 24V NoUnit 0 1 Internal 24V
96. System
1 Language English NoUnit 0 3082 Not selected
98. User motor parameters
2 Rs user 0.05118 p.u. 0.00000 0.50000 0.00000
3 Rr user 0.00573 p.u. 0.00000 0.50000 0.00000
4 Lm user 2.24859 p.u. 0.00000 10.00000 0.00000
5 SigmaL user 0.19185 p.u. 0.00000 1.00000 0.00000
9 Rs user SI 0.04076 Ohm 0.00000 100.00000 0.00000
10 Rr user SI 0.00456 Ohm 0.00000 100.00000 0.00000
11 Lm user SI 5.70 mH 0.00 100000.01 0.00
12 SigmaL user SI 0.49 mH 0.00 100000.01 0.00
99. Motor data
6 Motor nominal current 290.0 A 0.0 726.0 352.0
9 Motor nominal speed 1488 rpm 0 30000 1486
10 Motor nominal power 160.00 kW 0.00 10000.00 200.00
Drive composer pro v. [Link]