Syl-1512A2 Pid Temperature Controller Instruction Manual Instruction Manual
Syl-1512A2 Pid Temperature Controller Instruction Manual Instruction Manual
COM
Instruction Manual
SYL-1512A2 PID TEMPERATURE CONTROLLER
INSTRUCTION MANUAL
Version 2.11 (June, 2015)
2015.06 P1/5
AUBER INSTRUMENTS WWW.AUBERINS.COM
Note: For first time users without prior experience with PID controllers, the Table 1. System configuration parameters
following notes may prevent you from making common mistakes: Code Description Range Initial Note
Inty Inty Input Sensor Type See table 2 K 1
3.4.1 Power to the heater does not flow through terminal 1 and 2 of the controller. Outy Outy Control Output Mode 0,1,2,3,4,5,6 2 2
The controller consumes less than 2 watts of power. It only provides a control hy Hy Hysteresis Band 0~9999 3 3
signal to the relay. Therefore, 20 gauge wires are sufficient for providing power to adtu Adtu Autotune Offset 0~200(deg) 10 4
terminal 1 and 2. Thicker wires may be more difficult to install.
psb Psb Input Offset -100~100(deg) 0 5
rd Rd Control Function 0: heating, 1:cooling 0
3.4.2 The J1 relay is a “dry single pole switch”. It does not provide power by itself.
corf CorF Display Unit 0: ° C 1:° F 1
Figure 11 shows how it is wired when providing a 120V output (or when output
has the same voltage as the power for controller). If the load of J1 requires a end End Exit
different voltage than that for the controller, an additional power source will be Note 1. The controller is preset for K type thermocouple input. For any other
needed (see Figure 13).
types of sensor, the Inty value needs to be changed to the corresponding symbol
3.4.3 SSR output power does not come from the input of the SSR. The output of as shown in Table 2.
the SSR is a single pole switch between terminal 1 and 2 of the SSR. The input
of the SSR is for control, or triggering, the SSR. (Note, we are talking about the Table 2. Temperature sensor code
SSR itself, not the SSR control output of the controller). Figure 12 shows how the Code Description Working Temperature Range
SSR output should be wired. When switching a North American 240VAC power,
T t TC, Type T -200~400° C; -320~752° F
the heater will be live even when the SSR is off. Users should install a double
R r TC, Type R -50~1600° C; -58~2900° F
pole mechanical switch to the power input.
J J TC, Type J -200~1200° C; -320~2200° F
Wre WRE TC, WRe3/25 0~2300° C; 32~4200° F
4. Parameter Setting B b TC, Type B 350~1800° C; 660~3300° F
For safety reasons, the controller parameters are divided into three groups with S S TC, Type S -50~1600° C; -58~2900° F
different pass codes. You should only give the code to those who have the K K TC, Type K -200~1300° C; -320~2400° F
responsibility and knowledge of how to properly change it. Code 0089 contains E E TC, Type E -200~900° C; -320~1650° F
the parameters for system configuration that may need to change during the P10.0 P10.0 RTD, Pt100 -99.9~600.0° C; -99.9~999.9° F
initial set up. Code 0036 contains the parameters for tuning performance. Code P100 P100 RTD, Pt100 -200~600° C; -320~1100° F
0001 is for controlling temperature and alarm settings.
Cu50 Cu50 RTD, Cu50 -50.0~150.0° C; -60~300° F
4.1 System Configuration Parameters (accessed by code 0089)
Note 2. The value of outy determines the control mode. When it is set to:
The system configuration parameters are listed in table 1. To change the
parameters, press SET key, enter code “0089” press SET key again. Then, 0 - Relay J1 as alarm output; SSR output disabled.
follow the flow chart in Figure 3. 1 - Relay J1 as PID controlled relay contact output; SSR output disabled.
2 - Relay J1 as alarm output; SSR PID control output.
Parameter Display
Input Sensor Selection 3 - Relay J1 as alarm output; SSR On/off control output.
SET SET
Operation Mode Enter Code
SET SET
XXXX 4 - J1 as On/off control relay contactor output. SSR output disabled.
XXXX 0089 inty
SET
Output mode selection SET
5 - J1 as Limit control output.
outy X 6 – Relay J1 as alarm output; SSR for Limit control output.
SET
Hysteresis Band SET Note 3. Hysteresis Band (also called dead band, or differential), Hy, is used for
XXXX on/off and limit control modes. Its unit is in degrees (° C or ° F). For on/off control
HY
SET
Autotune offset SET mode, the output will be off when PV > SV and on again when PV < SV-Hy for
X
atdu heating. For cooling, the output will be off when PV < SV and on again when PV >
SET
Input offset SET SV+Hy. For limit control mode, the controller cannot be reset (to turn on the
XXXX output) when PV > SV-Hy for heating, and when PV < SV+Hy for cooling.
psb
SET
Heating/Cooling SET
X Note 4. The autotune offset will shift the SV value down by the Atdu value during
rd
Display Unit(C/F) the auto tune process. That will prevent the system from damage due to
SET SET
corf
X overheating during the autotune.
SET Note 5. Calibration offset, PSb is used to set an input offset to compensate the
end error produced by the sensor. For example, if the meter displays 5 ºC when
Figure 3. System setup flow chart probe is in ice/water mixture, setting PSb= -5 will make the controller display 0 ºC.
To set negative value, shift to the very left digit, press down key until it shows “-“.
(1) Press SET key to enter setting mode; 4.2 PID Parameters (accessed by code 0036)
(2) Press >, V and ^ keys to enter parameters; The PID parameters are listed in table 3. To change the parameters, press SET
(3) Press SET key to confirm; key, enter code “0036”, then press SET key again. The parameter flow chart is
(4) Press V or ^ keys to select the new parameter. similar to Figure 3.
2015.06 P2/5
AUBER INSTRUMENTS WWW.AUBERINS.COM
Note 6. Proportional Constant (P): P is also called the proportional band. Its unit
Table 4. Temperature and alarm parameters
is the percentage of the temperature range. e.g. For a K type thermocouple, the
control range is 1500 ° C. P=5 means the proportional band is 75 ° C (1500x5%). Code Description Initial Setting Note
SV SV Target temperature (Set Value) 800 12
Assuming the set temperature (SV) = 200. When integral, I, and derivative, d,
actions are removed - the controller output power will change from 100% to 0% AH1 AH1 Alarm 1 on temperature 800 13
when temperature increases from 125 to 200 ° C. The smaller the P value is, the AL1 AL1 Alarm 1 off temperature 900
stronger action will be for the same temperature difference between SV and PV. AH2 AH2 Alarm 2 on temperature 300
AL2 AL2 Alarm 2 off temperature 300
Note 7. Integral time (I): Brings the system up to the set value by adding to the END END Exit
output that is proportional to how far the process value (PV) is from the set value
(SV) and how long it has been there. When I decreases, the response speed is Note 12. There are two ways to set the target temperature.
faster but the system is less stable. When I increases, the response speed is a. During the normal operation mode, press ^ or V once to switch the display
slower, but the system is more stable. When I=0, the integration is turned off. It from PV to SV. The display will start to blink. Press ^ or V again to increase or
becomes to a PD controller that is useful for very slow system. decrease the SV. When finished, wait 8 seconds and the setting will take effect
Note 8. Derivative time (d): Responds to the rate of PV change, so that the automatically (the display will stop blinking).
controller can compensate in advance before |SV-PV| gets too big. A larger b. Follow the flow chart shown in Figure 5. This method is easier for large
number increases its action. Setting d-value too small or too large would temperature change. If no key is pressed after confirmation of SV, the controller
decrease system stability, causing oscillation or even non-convergence. Normally, will return to normal operation mode automatically in 1 minute.
d is set to ¼ of the I value.
Note 13. Alarm setting. When the SSR is used as the control output, the J1 relay
Note 9. Damp constant: This constant can help the PID controller further to can be used as an alarm (when outy is set to 0, 2, 3, or 6). The controller offers
improve the control quality. It uses artificial intelligence to dampen the two alarm settings for the J1 relay. One is controlled by parameters AH1 and AL1,
temperature overshot. When its value is too low, the system may overshot. When and the other is controlled by AH2 and AL2. AH1 and AH2 are the temperatures
its value is too high, the system will be over damped. to turn the J1 relay on; AL1 and AL2 are the temperatures to turn the J1 relay off.
When AH1(2) > AL1(2), the alarm is set for absolute high alarm as shown in
Figure 6 below. When AH1 (2) < AL1(2), the alarm is set for absolute low alarm
as shown in Figure 7 below. Users can press > key to temporarily turn off the
alarm. The alarm will be on again if the alarm set temperature is reached again.
SouF too low SouF acceptable SouF too high To permanently deactivate the alarm, set AH1=AL1 or AH2=AL2.
2015.06 P3/5
AUBER INSTRUMENTS WWW.AUBERINS.COM
AT start
AT calculation
AT end 8. Application Example
PV 8.1 A furnace needs to be controlled at 1200 ° F. The power source is 120VAC.
SV The heating element is 1800W/120V. It is switched on/off by a contactor. The coil
voltage of the contactor is 120VAC. A K type thermocouple is used as the
temperature sensor.
ON OFF ON OFF
ON/OFF PID a. Wiring diagram
PV Wiring the controller or heater with 240VAC is the same as with 120VAC
100 SV When heating, and outy=3 or 4,
97 SV-Hy If PV (SV-Hy), relay on Heater
If PV SV, relay off N
(SV=100, Hy=3)
120VAC L Fuse RTD
1 2
Relay On 4 3 SSR
R R W - +
Relay on
2015.06 P4/5
AUBER INSTRUMENTS WWW.AUBERINS.COM
8.3 A furnace needs to be controlled to hold a temperature. Power source is 9.3 Poor Accuracy
240VAC. Heating element is 1800W/240V. It is switched by a contactor. The coil
voltage of the contactor is 24VAC. A K type thermocouple is used as the Please make sure calibration is done by immersing the probe in liquid.
temperature sensor. Comparing with reference in air is not recommended because response time of
sensor depends on its mass. Some of our sensor has response time >10 minutes
in the air. When the error is larger than 5° F, the most common problem is
K type TC improper connection between the thermocouple and the controller. The
- + thermocouple needs to be connected directly to the controller unless a
thermocouple connector or an extension wire is used. A copper connector,
6 7 8 9 10 copper wire, or thermocouple extension wire with wrong polarity connected on
the thermocouple will cause the reading drift more than 5° F.
1 2 3 4 5
24VAC
L2
TC
- +
6 7 8 9 10
1 2 3 4 5
L Fuse
N
120VAC Small Heater
Figure 14. This is for loads that draw less than 3 Amp of current only. For
parameter settings, please refer to “example 8.1”.
2015.06 P5/5