This document provides information on circuit breakers and switch disconnectors for selection including: - The MasterPact MTZ2 circuit breaker ranges from 800 to 4000 amps and the MasterPact MTZ3 ranges from 4000 to 6300 amps. - It lists the types and amperage ratings for each model. - The MicroLogic X control unit provides protections like long-time overcurrent, short-time overcurrent, and instantaneous overcurrent. It lists the settings and characteristics for these protections.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
147 views2 pages

MasterPact MTZ Circuit Breakers Guide

This document provides information on circuit breakers and switch disconnectors for selection including: - The MasterPact MTZ2 circuit breaker ranges from 800 to 4000 amps and the MasterPact MTZ3 ranges from 4000 to 6300 amps. - It lists the types and amperage ratings for each model. - The MicroLogic X control unit provides protections like long-time overcurrent, short-time overcurrent, and instantaneous overcurrent. It lists the settings and characteristics for these protections.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

[Link].

com
Select your circuit breakers and switch-disconnectors
Selection guide
Circuit breakers

PB115951_80.eps
PB115943_85.eps

MasterPact MTZ2 MasterPact MTZ3


From 800 to 4000 A From 4000 to 6300 A
Type N1 H1 H2 H2V [8] H3 L1 H10 [6] Type H1 H2

MTZ2 08 800 800 800 800 800 800


MTZ2 10 1000 1000 1000 1000 1000 1000
MTZ2 12 1250 1250 1250 1250 1250 1250
MTZ2 16 1600 1600 1600 1600 1600 1600
MTZ2 20 2000 2000 2000 2000 2000 2000 2000
MTZ2 25 2500 2500 2500 2500 2500
MTZ2 32 3200 3200 3200 3200 3200
MTZ2 40 4000 4000 4000 4000 4000 MTZ3 40 4000 4000
MTZ3 50 5000 5000
MTZ3 63 6300 6300
B B B B B B B B B
42 66 100 100 150 150 - 100 150
- - - - - - 50 - -
42 66 100 100 150 150 - 100 150
- - - - - - 50 - -
42 66 66 85 85 100 65 30 50 100 100
42 66 66 85 85 100 65 30 50 100 100
22 36 66 50 75 75 65 30 50 100 100
Yes Yes Yes Yes Yes Yes No Yes Yes
[5] [5] [5] [5] [5]
L L or R L or R L or R L L L L or R L or R
[7]

N1 H1 H2 H2V H3 L1 H10 H1 H2

[3] [3] [3] [3]

[4] [4]

[3] [3] [3]

[4] [4]

439 x 441 x 403 479 x 786 x 403


439 x 556 x 403 479 x 1016 x 403
352 x 422 x 300 352 x 767 x 300
352 x 537 x 300 352 x 997 x 300

90/120 225/300
50/65 120/160

A-3
Select your MicroLogic X control unit [Link]

Protections
Functions of protections

The MicroLogic X control unit is suitable for different systems of voltage, three or four wires up to 690 V AC, 50/60 Hz
and for all earthing systems as defined per IEC or North American standards (TNC, TNS, TT, IT, HRG).

MicroLogic 2.0 X
Long-time ANSI 49RMS/51
Current setting (A) Ir = In x … Ir = 0.4 In to In, step 1 A
B
[Link]

Tripping between 1.05 and 1.20 Ir


Time setting tr = 0.5 s to 24 s, step 0.5 s for 6 Ir
Time setting exemple: Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
time delay (s) Accuracy: 0 to -20 % 6 x Ir 0.5 [1] 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.34 [2] 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory After tripping
Instantaneous ANSI 50
Pick-up (A) Isd = Ir x … Isd = 1.5 to 10 Ir, step 0.5 Ir [4]
Accuracy: ±10 %
Operating time (ms) Non tripping time: 20
Max breaking time: 80

MicroLogic 5.0 X - 6.0 X - 7.0 X


Long-time ANSI 49RMS/51
Current setting (A) Ir = In x … Ir = 0.4 In to In, step 1 A
[Link]

Tripping between 1.05 and 1.20 x Ir


Time setting tr = 0.5 s to 24 s, step 0.5 s for 6 Ir
Time setting exemple: Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
time delay (s) Accuracy: 0 to -20 % 6 x Ir 0.5 [1] 1 2 4 8 12 16 20 24
Accuracy: 0 to -20 % 7.2 x Ir 0.34 [2] 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
Thermal memory After tripping
Short-time ANSI 50TD/51
Pick-up (A) Isd = Ir x … Isd = 1.5 Ir to 10 Ir, step 0.5 Ir [4]
Accuracy: ±10 %
Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Operating time at 10 x Ir non tripping time (ms) 20 80 140 230 350
I2t Off or I2t On max breaking time (ms) 80 140 200 320 500
Instantaneous ANSI 50
Pick-up (A) Ii = In x … Ii = 2 In to 15 In, step 0.5 In [4] and OFF protection
Accuracy: ±10 %
Ii tripping mode Standard Fast
Operating time non tripping time (ms) 20 0
max breaking time (ms) 50 30

MicroLogic 6.0 X
Earth fault ANSI 50N-TD/51N
Pick-up (A) Ig = In x … Ig = 0.2 [3] In to In, step 0.1 In [4] and OFF protection
[Link]

Accuracy: ±10 %
Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4
I2t On - 0.1 0.2 0.3 0.4
Operating time non tripping time (ms) 20 80 140 230 350
max breaking time (ms) 80 140 200 320 500

MicroLogic 7.0 X
Residual earth ANSI 50G-TD
leakage (Vigi)
Sensitivity (A) IΔn 0.5 A to 30 A, step 0.1 A
[Link]

Accuracy complies with IEC/EN 60947-2 Annex B


Time delay Δt (ms) Settings 60 150 230 350 800
non tripping time (ms) 60 150 230 350 800
max breaking time (ms) 140 230 320 500 1000
[1] 0 to -40 % [4] F
 iner resolution settings are possible with EcoStruxure Power Commission
[2] 0 to -60 % software and Ecostruxure Power Device App app.
[3] 0.3 In to In for In y 400 A

B-8