Small Temperature Controller
microTC
SSRMAN-1P
·
· Series
Extremely Cost Effective
Super Compact Design
·Mounts with One Screw
·Reverse or Direct Acting (Heat or Cool)
·Custom Temperature Ranges
·Fixed Setpoints & Hysteresis
·-10 to 85C with +/- 0.5degC Accuracy
·Freeze Protection, Temperature Control
·On-Off or Proportional Control
·Limited Two Year Warranty
Product Description Ordering Codes MicroTC - __._ - __._ - _ - _ - _
The Micro TC is the smallest and lowest cost
temperature controller in our line. The Micro Setpoint Temperature (XX.X degC) *(E) for External
TC is factory set for your setpoints and Band or Hysteresis (XX.X degC)
hysteresis but is available with field (O) On-Off Control OR (P) Proportional Control
adjustable versions using an external ( R ) Reverse or (D) Direct Acting Control
potentiometer. Micro TC provides a 3 Amp Power Supply Voltage, (12) or (24) VDC
MOSFET output that can be used to drive an
SSR or small heater. The integral sensor *For external setpoint, specify high and low limits of adjustment. For example:
eliminates the extra cost of a thermocouple MICROTC-E(20-40) would have an adjustment range of 20-40C.
or RTD.
Input Specifications
Power Supply 12 or 24VDC +/-10%, < 1 Watt Power Consumption
Temperature Setpoint Range 0 to 85 degC
Fixed Setpoint Accuracy +/- 0.5 degC
External Setpoint Input ~0-5VDC +/-1.5V (0-100% of Potentiometer)
Setpoint Input Impedance 100K
External Potentiometer Resistance 50KOhm
Output Specifications
Control Output MOSFET, Open Drain, 26V Max, Max Sink Current:
3A@25C, Ambient (Linear Derating to 1A@85C Ambient)
Output in proportional mode is time proportioned (PWM)
[Link] 866-379-3597 REV0.3
Thermal Specifcations
Operating Temperature Range 0 to 85 degC
Storage Temperature Range -40 to 100 degC
Dimensions & Wiring Operation
Reverse Acting (Heating) Examples:
0.500" Setpoint Temp
HYSTERESIS - (O)
1.675"
Output On Output Off Output On
0.169"
Setpoint Temp
PROPORTIONAL BAND - (P)
0.375" 100%
Output Off
0%
Note:Output is pulsed PWM proprtional output
0.125"
0.062"
0.100"
Direct Acting (Cooling) Examples:
HYSTERESIS - (O)
Setpoint Temp
+12 / 24VDC PWR (+V)
Output On Output Off Output On
+5V OUT (POTCW)
+V
LOAD
OUT (OPEN DRAIN)
SETPOINT (POTW)
GND, POT CCW (G)
PROPORTIONAL BAND - (P)
Setpoint Temp
100%
Output Off
0%
Note:Output is pulsed PWM proprtional output
[Link] 866-379-3597