STRUCTURAL ANALYSIS (1 Storey)

This document provides a structural analysis for a one-storey residential house. It analyzes and designs the following structural elements: 1. A 110mm thick one-way slab with 5 #10 reinforcing bars at 200mm spacing. 2. A 300mm square isolated footing with 7 #16 reinforcing bars to support a 180.83kN column. 3. A 300mm deep, 120mm wide reinforced concrete beam with 5 #12 bars to resist a bending moment of 6.44 kN-m. 4. A 120mm by 300mm reinforced concrete column with 6 #12 bars to support a 245kN load. 5. A wood roof structure with
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as ODT, PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
3K views12 pages

STRUCTURAL ANALYSIS (1 Storey)

This document provides a structural analysis for a one-storey residential house. It analyzes and designs the following structural elements: 1. A 110mm thick one-way slab with 5 #10 reinforcing bars at 200mm spacing. 2. A 300mm square isolated footing with 7 #16 reinforcing bars to support a 180.83kN column. 3. A 300mm deep, 120mm wide reinforced concrete beam with 5 #12 bars to resist a bending moment of 6.44 kN-m. 4. A 120mm by 300mm reinforced concrete column with 6 #12 bars to support a 245kN load. 5. A wood roof structure with
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as ODT, PDF, TXT or read online on Scribd
  • Slab Design: Discusses the design criteria, load schedule, and computations related to the slab structure.
  • Isolated Footing: Provides calculations and criteria for designing isolated footings including soil pressure and load analysis.
  • Reinforced Concrete Beam: Explains the design criteria, loads, and reinforcement requirements for concrete beams.
  • Roof Design: Analyzes roof load including dead load, live load, and wind load calculations.
  • Column Design: Includes trial design, working stress design, and load evaluations for columns.

STRUCTURAL ANALYSIS

FOR

ONE - STOREY RESIDENTIAL


HOUSE
1. SLAB

Schedule of Loads

Slab = 9.6kPa
Floor finish = 2.20kPa
Ceiling loads = 0.24kPa
Others = 1.0kPa

TOTAL DEADLOAD = 13.04kPa


TOTAL LIVELOAD = 2.40kPa

Computations:

Design Loads

wu = 1.4DL + 1.7LL
= 1.4(13.04) + 1.7(2.40)
wu = 22.336kPa

4 @ 3m = 12m

Check if one or two-way slab:

S = 3 = 0.25 < 0.50


L 12

Therefore: ONE-WAY SLAB


Moments = CwL² = C(22.336)(3)²

1/24 1/10 1/11 1/11 1/11 1/10 1/24

1/14 1/16 1/16 1/14

8.376 20.1
20.10 18.27 18.27 18.27 20.1 8.376
0 0
14.36 12.56 12.56 14.36

f’c = 28
fy = 420

ρmin = 1.4 = 1.4 = 0.00333


fy 420

Use ρmin = 0.00333 for 1m strip

As = ρbd
= 0.00333(1000)(100)
As = 333 mm²

AØ = ¶d² = ¶(10)² = 78.54 mm²


4 4

No. of bars = As = 333 = 4.24 say 5 pcs.


AØ 78.54

Spacing = 1000 = 200mm o.c.


5

ρb = 0.85f’cβ1(600)
fy (fy + 600)
= 0.85(28)(0.85)(600)
420(420 + 600)
ρb = 0.02833

Use ρ = 0.50 ρb

ρ = 0.50 ρb
= 0.50(0.02833)
ρ = 0.014
Solving for the effective depth of slab:

w = ρfy = 0.014(420) = 0.21


f’c 28

Ru = f’cw [ 1 – 0.59w ]
= [28(0.21)] – [1 – 0.59(0.21)]
Ru = 5.15

d² = Mu
ØRub
= 20,100,000
0.90 (5.15) (1000)
d = 65.85mm

Total Slab Thickness:

t = 65.85 + 40 + 5
t = 110.85mm say 110mm

Actual d:

d = 110 – 40 – 5
d = 65 mm

Check if reinforcement steel will yield:

ρmin = 1.4 = 1.4 = 0.00333


fy 420

ρ = As
bd
= [ ¶ (10)²] [5]
____4____
(1000) (65)
ρ = 0.00604

ρmax = 0.75[ 0.85f’cβ1(600) ]


fy (fy + 600)
= 0.75 [0.85(28)(0.85)(600)]
420(420 + 600)
ρmax = 0.02125

THEREFORE: ρmin < ρ < ρmax = 0.00333 < 0.00604 < 0.02125 (SAFE!)
2. ISOLATED FOOTING

Allowable Soil Pressure = 200kPa


Allowable Punching Shear = 1.50891MPa
Allowable Beam Shear = 0.7638 MPa
F’c = 21 MPa
Fy = 275 Mpa
Column Loads:

PDL = 133 kN
PLL = 36 kN
Moments:

MDL = 5 kN-m
MLL = 2 kN-m

Assume wt. of footing = 7% of column load


Wt. of footing = 0.07 (133+36)
Total Load = 11.83 + 133 + 36 = 180.83 kN

Depth = 300 mm

Net Ultimate Pressure:

qult = Pu ( 1 + 6e )
B² B

Factored Load:

Pu = 1.4 PDL + 1.7 PLL


= 1.4 (133) + 1.7 (36)
Pu = 247.40 kN

Factored Moment:

Mu = 1.4 MDL + 1.7 MLL


= 1.4 (5) + 1.7 (2)
Mu = 10.4 kN-m

e = 10.4 kN-m = 0.04204


247.40

qult = Pu ( 1 + 6e )
B² B
= 247.40 [ 1 + 6(0.04204)]
0.9m² 0.9
Max. qult = 391.03 kPa
Min. qult = 219.83 kPa

Check for beam shear:

D = 300 mm

Vc = 1/6 √f’c
= 1/6 √21
Vc = 0.7638 MPa (ALLOWABLE)
y = 172
0.09 0.9

y = 17.20 kPa

Vu = 391(0.09)(0.9) – ½ (17.20)(0.09)(0.9)
Vu = 30.97 kPa

Vn = Vu = 30.97(1000)
Øbd 0.85(900)(300)

Vn = 0.135 MPa < 0.7638 MPa (SAFE!)

For Bending:

y = 172
0.39 0.9

y = 74.53 kPa

Mu = 391(0.09)(0.39/2) – ½ (74.53)(0.09)(0.39/2)
Mu = 25.062 kN-m

Mu = ØRub d²
25,062,000 = 0.90 Ru (900) (300)²
Ru = 0.3438

ρ = 0.85f’c [ 1 - 1 – 2Ru ]
fy √ 0.85 f’c
ρ = 0.85(21) [ 1 - 1 – 2(0.3438) ]
275 √ 0.85(21)
ρ = 0.00126

ρmin = 1.4 = 1.4 = 0.00509


fy 275

Use ρ = ρmin = 0.00509

Compute steel area requirements:

As = ρbd
= 0.00509(900)(300)
As = 1,374.54 mm²

Actual No. of bars (7- 12mmØ RSB)

As = = ¶d²(n) = ¶(12)² (7)= 791.68 mm²


4 4

ρ = As = 791.68 mm² = 0.00293 < 0.00509


bd 900(300)
s
Therefore: Steel reinforcement does not yield.

Use 7 - 16 mm Ø RSB

As = = ¶d²(n) = ¶(16)² (7)= 1,407.43 mm²


4 4

ρ = As = 1,1407.43 mm² = 0.00521 > 0.00509 (OK!)


bd 900(300)

ρmax = 0.75[ 0.85f’cβ1(600) ]


fy (fy + 600)
= 0.75 [0.85(21)(0.85)(600)]
275(275 + 600)
ρmax = 0.02837

THEREFORE: ρmin < ρ < ρmax = 0.00509 < 0.00521 < 0.02837 (SAFE!)
3. REINFORCED CONCRETE BEAM

Design Criteria

F’c = 21 MPa
Fy = 275 MPa

Loads:

Wslab = 2.40kPa
Wwall = 3.60kPa
Wceiling = 0.24kPa
Wbeam = 2.88kPa
Roof = 4.646kPa

TOTAL DEADLOAD = 13.796kPa


TOTAL LIVELOAD = 0.38kPa

END REACTIONS/END SHEAR

R1 = R2 = V = (13.796 + 0.38) = 7.088kPa


2

MINIMUM BENDING MOMENT

At support:
MDL = 13.976 (0.3) = 4.14 kN-m
MLL = 0.38 (0.3) = 0.114 kN-m
MU = 1.4 (1.14) = 5.796 kN-m

At mid-span, M = wL/24 or ½ moment at support


MDL = 13.976 (0.3) (1/2) = 2.07kN-m
MLL = 0.38 (0.3) (1/2) = 0.057 kN-m
MU = 1.4 (1.14) (1/2) = 2.898 kN-m

REQUIRED THEORETICAL MOMENT

Capacity reduction factor, Ø = 0.90

a. At support = ML = 5.796/0.90 = 6.44 kN-m


b. At midspan = ML = 2.898/0.90 = 3.22 kN-m
FACTORED VALUE OF END SHEAR

Vu = 1.4 (13.796) + 1.7 (0.38)


2 2
Vu = 9.9802kPa

FACTORED LOAD

Wu = 1.4 (13.796) + 1.7 (0.38)


Wu = 19.96 kPa or 19.96/6 = 3.33 kPa/m

Shear force at distance “d” from support


Vud = 9.98 – 3.33 (1.5) = 4.985kPa
AREA OF TENSION REINFORCEMENT

ρmax = 0.75[ 0.85f’cβ1(600) ]


fy (fy + 600)
= 0.75 [0.85(21)(0.85)(600)]
275(275 + 600)
ρmax = 0.02837

Use ρ = 0.50 ρmax

ρ = 0.50 ρmax
= 0.50 (0.02837)
ρ = 0.01418

ρ = As
bd
0.01418 = As
120(300)
As = 510.66mm²

AØ = ¶d² = ¶(12)² = 113.10 mm²


4 4

N = As = 510.66 = 4.52 say 5 pcs.


A Ø 113.10

Check if steel reinforcement will yield:

As = = ¶d²(n) = ¶(12)² 5)= 565.49 mm²


4 4

ρ = As = 565.59 mm² = 0.0157


bd 120(300)

ρmin = 1.4 = 1.4 = 0.00509


fy 275

THEREFORE: ρmin < ρ < ρmax = 0.00509 < 0.0157 < 0.02837 (SAFE!)
4. COLUMN

Trial Design:

B = 120 mm
D = 300 mm
F’c = 21 MPa
Fy = 275 MPa
PD = 200 kN
PL = 45 kN

Working Stress Design:

P = 0.85 Ag ( 0.25 f’c + fy ρg) ……………....SAFE LOAD FOR SHORT COLUMN


P’ = P ( 1.07 – 0.008 h/r ) ……………………SAFE LOAD FOR LONG COLUMN

Substituting the values:

ρ = As
bd
= [ ¶ (12)²] [6]
____4____
(120) (300)
ρ = 0.01885

Ag = Area of column = (0.12) (0.30) = 0.036 m²

DL + LL = 200 kN + 45 kN = 245 kN

P = 0.85 (0.30) (0.12)[ 0.25(21,000 kN/m²) + 275,000 kN/m²(0.01885)


P = 319.27 kN

P = 319.27 [ 1.07 – 0.008 (3.30/2.96) ]


P = 338.77 kN > 245kN (SAFE!)

5. ROOF

From the roof plan, tributary width

Width = 6.20 m
Weight of wood = 2.30 kPa
Allowable Bending = 16.26 MPa
Allowable Shear = 1.10 Mpa

Load Analysis

a. DEADLOAD

Roofing sheets = 0.24 kPa


Rafter Wt. = 0.096 kPa
Purlins = 1.20 kPa
Suspending ceiling = 0.24 kPa

TOTAL DEADLOAD = 1.776 kPa


b. LIVELOAD = 0.96 kPa
c. WINDLOAD

Pn = 2Psinθ
1 + sin²θ

Where:

Pn = wind pressure on vertical surface = 0.003V³

Basic wind speed (Zone 1) = V = 200 kph = 125mph

P = 0.003 (125)²
= 46.9 psf
P = 2.24 kPa

Pn = 2 (2.24) sin 34º


1 + (sin 34º)²
Pn = 1.91 kPa

Combination of Loads:

DL + LL = 15.93 kN

Tangent Load = 3.71 kN

Bending Moment of Normal Load = wL = 15.93 (6.20) = 12.34 kN-m


8 8

Check for flexure:

F = 6M = 6 ( 12.34) = 1.26 kPa < 1.10 kPa ( ADEQUATE! )


bd² (2.4)(3.5)(7)