The document provides design parameters and calculations for a pipe rack structure. It outlines materials used, soil properties, and allowable bearing capacities. It describes modeling the pipe rack in STAAD as a 3D frame with standard sections. Load cases and combinations are defined per design standards. Unity stress ratio diagrams show the pipe rack is within acceptable limits under all load combinations analyzed.

Uploaded by

Omkar Kulkarni
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views11 pages

Pipe Rack Design Presentation

The document provides design parameters and calculations for a pipe rack structure. It outlines materials used, soil properties, and allowable bearing capacities. It describes modeling the pipe rack in STAAD as a 3D frame with standard sections. Load cases and combinations are defined per design standards. Unity stress ratio diagrams show the pipe rack is within acceptable limits under all load combinations analyzed.

Uploaded by

Omkar Kulkarni
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • Design Parameters: Details the materials used in structural design, including specific parameters like strength and density.
  • Idealization of Structure: Describes the modeling of the structure in STAAD PRO and associated design assumptions.
  • Pipe Rack 3D Models: Presents the 3D models created in STAAD, with visual diagrams illustrating the structure.
  • Result Summary: Summarizes key results like deflection check ratios, explaining the permissible limits for structure stability.
  • Conclusion: Concludes the report with observations and confirms the safety of the structural design based on analysis results.
  • Footing Summary: Provides a summary of footing base pressures and evaluations for structure support.

PIPERACK DESIGN CALCULATIONS

2.0 DESIGN PARAMETERS


For the structural design following materials are used
Characteristic Strength of concrete =25MPa …. (28-day cube strength)
Yield strength of Reinforcement = 500 MPa
Grade of Structural Steel = 250 MPa
For the design of foundation following limits are considered:
Foundation Depth =2m
Net Allowable Bearing Pressure = 400 kN/m2*
Density of soil = 18 kN/m³
Bore hole No. = BH-08
Note: * Reference soil bearing capacity
The Allowable Net Bearing Capacity of soil (Ref. BH No-08) is mentioned 40 t/m2 at 2 m depth below
ground level as per latest geotechnical investigation report document No. XXXX-03-000-XXXXX-
001, for design Allowable Net Bearing Capacity considered is 25 t/m2.
For the design of Steel structure following limits are considered:
PIPERACK DESIGN CALCULATIONS

3.0 IDEALIZATION OF STRUCTURE


The PR steel structure is modelled in STAAD PRO as a 3D Model. The following Modelling, Analysis
and Design assumptions are adopted
 Modelling is done as a wire frame with frame element command to the scale matching with
Architectural GA drawings at center line.
 Standard Sections are used for the beams, columns, tie members and bracing where adequate.
 Loading for the seismic are generated in STAAD (refer the Appendix B) by providing the specified
seismic parameters.
 Other primary loads are applied in the model using the load commands. Load combinations are
defined as per the design basis XXXX-03-000-XXXXX-001
 Design parameters are defined in STAAD Pro with IS 800 LSD code as mentioned in design basis.
After the super structure design, the reactions from the STAAD model are used for the design of
footings. The design of foundations is done by using STAAD Foundation Advance.

4.0 LOAD CALCULATION


Refer Appendix-B for load calculations. Basic load cases and load combinations are provided as per
Structural Design Basis & Std. Engineering Practice.

5.0 STAAD MODEL


5.1 PIPE RACK 3D MODEL IN STAAD:

45

44

43
P27
42

P26 41
40
PIPERACK DESIGN CALCULATIONS

5.2 PIPE RACK 3D MODEL IN STAAD:

5.3 PIPE RACK MEMBER & NODES NOS IN STAAD :-

P27 P26
5.3
Grid no. 40
PIPERACK DESIGN CALCULATIONS

P27 P26

Grid no. 41

P27 P26

Grid no. 42
PIPERACK DESIGN CALCULATIONS

P27 P26

Grid no. 43

P27 P26

Grid no. 44
PIPERACK DESIGN CALCULATIONS

P27 P26

Grid no. 45
PIPERACK DESIGN CALCULATIONS

5.4 PIPE RACK UNITY STRESS RATIO DIAGRAM IN STAAD:-

45

44
43
P27 42

P26 41
40 Column

0.0166 0.202 0.202 0.544 0.544 0.299 0.19 0.169 0.561 0.561 0.563 0.563 0.0166

0.293 0.175 0.431 0.159 0.113 0.392 0.175 0.374

0.527 0.47 0.533 0.753 0.61 0.61 0.585 0.61 0.522

0.293 0.142 0.422 0.163 0.123 0.403 0.142 0.374

0.0166 0.2 0.2 0.672 0.672 0.546 0.387 0.191 0.187 0.559 0.559 0.561 0.561 0.0173

0.0108 0.0566
0.0121 0.0117

0.27 0.125

EL: 105.700
Load 401
PIPERACK DESIGN CALCULATIONS

0.0168 0.168 0.168 0.259 0.544 0.552 0.103 0.0937 0.527 0.519 0.498 0.493 0.0234

0.317 0.175 0.334 0.183 0.137 0.288 0.175 0.443

0.355 0.645 0.458 0.875 0.876 0.875 0.465 0.875 0.412

0.317 0.142 0.375 0.154 0.123 0.302 0.142 0.443

0.0166 0.144 0.144 0.441 0.449 0.117 0.101 0.426 0.419 0.397 0.396 0.0189

EL: 107.700
0.0186 0.184 0.184 0.27 0.31 0.4 0.373 0.402 0.402 0.373 0.441 0.457 0.441 0.442 0.457 0.44 0.0186

0.105 0.244 0.167 0.261 0.159 0.118 0.713 0.172 0.17 0.289 0.168 0.167 0.284 0.167 0.168
Load 4010.0852
0.265

0.0709
0.419 0.0709 0.0709 0.109 0.0939 0.115 0.114 0.125 0.103 0.0999 0.115 0.0955 0.0939 0.11 0.092 0.337
0.0912

0.124 0.116 0.229 0.153 0.24 0.165 0.225 0.233 0.231 0.152 0.231 0.231 0.135 0.229 0.229 0.123 0.125

0.0992 0.0948 0.14 0.086 0.131 0.0821 0.0709 0.12 0.0709 0.071 0.128 0.0851 0.0922 0.16 0.106 0.113

0.168 0.102 0.23 0.117 0.24 0.165 0.192 0.23 0.23 0.121 0.231 0.231 0.117 0.23 0.23 0.113 0.149

0.101 0.0957 0.14 0.0858 0.131 0.0826 0.0741 0.14 0.11 0.11 0.143 0.111 0.111 0.154 0.112 0.117

0.13 0.126 0.23 0.15 0.239 0.128 0.293 0.229 0.231 0.15 0.233 0.233 0.139 0.234 0.235 0.119 0.125

0.37
0.0709 0.0709 0.0709 0.0709 0.0709 0.0709 0.14 0.117 0.129 0.125 0.11 0.119 0.116 0.0965 0.112 0.11
0.286

0.11 0.241 0.181 0.332 0.183 0.0893 0.377 0.18 0.176 0.306 0.169 0.166 0.29 0.162 0.161 0.284 0.0878

0.0166 0.178 0.177 0.291 0.442 0.46 0.437 0.367 0.398 0.398 0.374 0.405 0.421 0.405 0.405 0.422 0.405 0.0166

0.0136 0.0112
0.059 0.0112

0.2 0.303

EL: 109.700

0.0165 0.153 0.153 0.483 0.483 0.434 0.311 0.346 0.347 0.312 0.413 0.431 0.417 0.403 0.449 0.406 0.0166
Load 401
0.32 0.304

0.137 0.138
0.248 0.269

0.234 0.255
0.133 0.132
0.0747 0.0335

0.24 0.124 0.0915


0.335
0.244 0.247
0.0165 0.149 0.149 0.488 0.502 0.394 0.233 0.263 0.279 0.279 0.265 0.39 0.405 0.389 0.39 0.406 0.39 0.0166

0.275 0.1010.0115 0.0142

0.275 0.219

Load 401
EL: 112.200
PIPERACK DESIGN CALCULATIONS

Grid ‘P27’

Grid ‘P26’
PIPERACK DESIGN CALCULATIONS

6.0 RESULT SUMMARY


Maximum deflection check ratio is given below in the tables:

The limiting permissible horizontal deflection for multi-storeyed steel structure Maximum member is
Height / 300
Height of PR = 10.4m.
Allowable horizontal deflection = (10.4 x 1000)/300 = 34.67 mm.
Maximum Actual Deflection = 12.66 mm.
Unity Check ratio is given below in the tables

Member type Member size Stress ratio


Column UB610X229X101 0.627
UB610X229X101 0.585
Main beam
UB356X171X45 0.713
Secondary beam UB356X171X45 0.876
UB406X178X54 0.671
Long. Beam UB406X178X54 0.607
UB406X178X54 0.468
Cantilever CH100X50X10 0.291
Walkway beam CH150X75X18 0.140
Stub column CH150X75X18 0.230
Plan Bracing UA90X90X8 LD 0.183
Bracing UA90X90X8 SA 0.635
Knee brace UA90X90X8 0.170
Plan Bracing UA75X75X6 LD 0.419
Bracing UA120X120X12 SA 0.618
PIPERACK DESIGN CALCULATIONS

7.0 FOOTING SUMMARY

Base Pressure (kN/m2) Overturning


Node No. Sliding
Max. Min. X Z
856 857 64.20 -11.41 5.81 27.54 5.30
858 859 68.50 -12.89 5.20 66.10 4.55
860 862 88.57 -36.00 2.87 4.43 2.70
861 863 101.28 -36.00 2.78 4.40 2.37
864 865 67.68 -10.09 5.23 67.85 4.59
866 867 72.78 -16.85 5.21 24.35 4.49
8.0 CONCLUSION
The design of the structural foundation and steel structures are performed as per standards and
specifications using STAAD.PRO & STAAD Foundation Advance & found safe. For detailed reports
refer subsequent Appendixes. Based on this report the following drawings are generated.

• XXXX-03-000-XXXXX-001- PR Base Plate Layout & Details


• XXXX-03-000-XXXXX-002- PR Structural framing plans and elevation details
• XXXX-03-000-XXXXX-003- PR Foundation layout and RC details