GUARANTEED TECHNICAL PARTICULARS
Sl Particulars Details
1 Type of Design as per ISS 12V 42Ah
2 Manufacturers Type Design EXIDE / Type EP (Exide Power Safe) EP42-12
3 Ah Capacity 20 Hrs rate of Discharge at 1.75ECV 42Ah @ 20 Hrs @ 1.75 ECV (C20 Rating)
7 Plates per Cell (3 Positive and 4 Negative): For total 12V Monoblock battery: 42 Plates (18
4 Total no of Plates Per Cell
Positive & 24 Negative)
5 Nominal Cell Voltage (Volts) 12V
6 No of Cells in Each Bank 6 Cells each of 2V in a Battery x n Batteries in a Bank = 6 x n Nos of 2V cells in a Bank
7 No of Spare Cells if any in each Bank --
8 Internal Resistance for each cell (Micto Ohms)
Resistance of the Battery including inter connection between 8 milli Ohms at fully charged Condition @ 25 Deg C for each Battery consisting of 6 nos of 2V
9
cells (Ohms) cells
Cell discharge rate in Ampere (From rated Voltage to final
10
discharge rate in amp)
5 Hour Discharge rate in Amps 7.56A up to 1.75 VPC
2 Hours Discharge rate in amps 15.96A up to 1.75 VPC
1 Hour Discharge rate in amps 27.3A up to 1.75 VPC
30 Minutes discharge rate in amps 47.04A up to 1.75 VPC
10 minutes’ discharge rate in amps 90.3A up to 1.5 VPC
1 minute discharge rate in amps Not Applicable
11 Short Circuit Current in Amps 992 Amps
12 Material of Cell containers Poly Propylene Co Polymer (PPCP)
Material used for battery box Not Applicable
13 Thickness, type and material of separators 1.1 mm Absorbent glass matrix (AGM) separators
S Construction Details
Positive Plate Flat Pasted
Negative Plate Flat Pasted
Surface area of plates in [Link] 16888.80 [Link]
15 Ampere hour efficiency 90%
watt Hour Efficiency 80%
Recommended Float Charging Voltage /Battery: 13.7± 0.1V/ Charging Current Maximum 12.6
16 Recommended Float Charge current and Voltage
Amps (i.e 0.3 CA) and Minimum 4.2 Amps (i.e 01. CA)
Recommended Boost Charging Voltage per 12V Monoblock Battery: 14.7± 0.1V / Charging
Recommended Boost Charge current and Voltage
Current Maximum 12.6 Amps (i.e 0.3 CA) and Minimum 4.2 Amps (i.e 01. CA)
Time required for Boost Charging from Discharged condition 8 to 10 Hours (Approx) with the recommended Boost current and Voltage setting.
18 (i) Max Charging Current per cell upto 12.6 Amps
(ii) Nominal Charging rate Minimum 4.2 Amps and maximum 12.6 amps
Explosion Proof Vent Plugs functioning as One-way pressure relief valves to release the
19 (i) Whether explosion proof vent plugs provided
internal gases.
(ii) Whether vent is spill proof Spill Proof vent provided
Type of inter cell connection and whether they are covered
20 Internal Welded Type. Plastic sleeves not applicable for internal welded type
with plastic sleeves
21 Dimension of each 12V Block. Cell
Length 199±5mm
Width 165±5mm
Height 181±5mm
Bottom Thickness in mm: 2.7mm without footrest & 3mm with footrest.
Thickness of Container in mm Side wall Thickness in mm: 2.8mm
Lid thickness in mm: 2.4mm
Net weight of the cell complete with acid 12V block (kg) 13.9 Kgs (± 5%)
22 Expected life span of battery 5 Years @ 27 Deg C in Standby Mode (i.e Designed Flaot Life)
23 Accessories Provided Yes
24 Special conditions if any Nill
Yours faithfully,
For EXIDE INDUSTRIES LIMITED
Venkata Narayana M
Area Manager-Industrial, Bangalore
venkatanm@[Link] /9900571054