REB-16 Relays Installation Guide

The document provides installation instructions for the REB-16 relays extension box. It should be installed by an electrician with power disconnected. It recommends installing in a service room away from gases or humidity. The installation involves connecting wires according to diagrams and sealing cable holders after mounting. The unit has 5A relay outputs and operates from 110/240VAC power with overvoltage protection.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
143 views4 pages

REB-16 Relays Installation Guide

The document provides installation instructions for the REB-16 relays extension box. It should be installed by an electrician with power disconnected. It recommends installing in a service room away from gases or humidity. The installation involves connecting wires according to diagrams and sealing cable holders after mounting. The unit has 5A relay outputs and operates from 110/240VAC power with overvoltage protection.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Relays Extension Box REB-16

Installation Guide

~ N GND
CL D COM

COM D

R
E
L
ROTEM A
CONTROLLER Y
S

O
U
T

[Link] 19/06/2001 Rev:1.0 1


Relays Extension Box REB-16
Installation Guide

~ N GND
CL D COM

COM D

R
E
L
ROTEM A
CONTROLLER Y
S

O
U
T

[Link] 19/06/2001 Rev:1.0 2


Installation
The REB-16 must be installed by an authorized [Link]
must be disconnected to avoid electrical shock and damage.

To avoid exposing the REB-16 to harmful gases or high humidity,


it is recommended to install it in the service room.

Insttallation Categoty (Overvoltage Category) III

The power supply to the REB-16 should be protected by 5Amps circuit breaker.

1. Open the enclosure lid by unfastening the two screws to the left-hand side
in the front.
2. Place the required cables through the cable holders at the bottom of the
unit. Connect the wires according to the wiring diagrams:
3. Close the REB-16 enclosure lid carefully and tightly. Use RTV silicon or
equivalent sealant to seal the cable holders.
4. After installation is completed, operate the REB-16 for a few hours and re-
check for proper operation.

Specifications
Input Voltage Supply:
Single phase 110 VAC (USA & CANADA).
Single phase 240 VAC (Outside the US & CANADA).
0.315 Amp, 50 - 60 Hz.
Relays Outputs:
5 Amp. Normally Open Relays .
Alarm Output:
NO and NC Pilot Duty.
Operating Temperature Range:
-10°C to 50 °C ( 14 to 122 F° )
Enclosure :
Water and dust tight. (IP55)
Fuses:
Main Fuse: 0.315 Amp Slow.
Relays Fuse: 5 Amp. Slow.

ROTEM Computerized Controllers Ltd. 972-3-9206200 FAX: 972-3-9249834 ISRAEL


Web site [Link] Email- rotem@[Link]

[Link] 19/06/2001 Rev:1.0 3


Installation
The REB-16 must be installed by an authorized [Link]
must be disconnected to avoid electrical shock and damage.

To avoid exposing the REB-16 to harmful gases or high humidity,


it is recommended to install it in the service room.

Insttallation Categoty (Overvoltage Category) III

The power supply to the REB-16 should be protected by 5Amps circuit breaker.

5. Open the enclosure lid by unfastening the two screws to the left-hand side
in the front.
6. Place the required cables through the cable holders at the bottom of the
unit. Connect the wires according to the wiring diagrams:
7. Close the REB-16 enclosure lid carefully and tightly. Use RTV silicon or
equivalent sealant to seal the cable holders.
8. After installation is completed, operate the REB-16 for a few hours and re-
check for proper operation.

Specifications
Input Voltage Supply:
Single phase 110 VAC (USA & CANADA).
Single phase 240 VAC (Outside the US & CANADA).
0.315 Amp, 50 - 60 Hz.
Relays Outputs:
5 Amp. Normally Open Relays .
Alarm Output:
NO and NC Pilot Duty.
Operating Temperature Range:
-10°C to 50 °C ( 14 to 122 F° )
Enclosure :
Water and dust tight. (IP55)
Fuses:
Main Fuse: 0.315 Amp Slow.
Relays Fuse: 5 Amp. Slow.

ROTEM Computerized Controllers Ltd. 972-3-9206200 FAX: 972-3-9249834 ISRAEL


Web site [Link] Email- rotem@[Link]

[Link] 19/06/2001 Rev:1.0 4