General Signal Conditioner Cards


Specifications
GS 33K50H80-50E

[Release 5]

n OUTLINE
Signal Conditioner Cards, which interface to the process, are installed in Signal Conditioner Nests.
The signal conditioner cards can convert the I/O signals, isolate the I/O signals, and provide an isolated power
supply from a built-in distributor.
For example, the measuring ranges of temperature and mV input signal conditioner cards can be changed
by a portable BRAIN terminal. Some cards have communication functions and supply power to BRAIN Series
transmitters (BRAIN UNI∆, BRAIN ADMAG and BRAIN YEWFLO).
You can select from 16 types of cards according to the kind of field signal.

Yokogawa Electric Corporation GS 33K50H80-50E


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright Aug. 2011 (YK)
Tel.: 81-422-52-5634 Fax.: 81-422-52-9802 3rd Edition Aug. 31, 2015 (YK)
<<Contents>> <<Index>> 2
n SPECIFICATIONS
Standards Specifications (1)

Thermocouple input Resistance thermometer Potentiometer


Name mV input card
card sensor input card Input card
Model EM1 ET5 ER5 ES1
RTD (3-wire, Measuring
current: 1mA)
TC JIS C1602, • JIS C1604: 2013,
DC voltage IEC 60584-1 (ITS-90) IEC 60751 (ITS-90) Pt100 Potentiometer,
Input signal
-50 to +150 mV Type • JIS C1604: 1989, 3-wire
K, T, J, E, B, R, S, N DIN (IPTS-68) Pt100
• JIS C1604: 1989 JPt100
• JIS C1604: 1981 Pt50
10 to 63 mV Total resistance:
Span 10 to100 mV DC (Thermoelectric 10 to 650 °C (*5) 100 to 2000 Ω
Measuring range conversion) Span: 80 to 2000 Ω
Smaller of 3 times Smaller of 3 times Within 50 % of total
Zero elevation Max. 5 times span
span and ±50 mV span and ±25 mV resistance
Measuring range change Can be changed by BRAIN terminal
1 MΩ (10 kΩ 1 MΩ (10 kΩ
Input resistance –
when power off) when power off)
External input resistance 500 Ω max. Max. 150 Ω/wire (*1) Max. 10 Ω/wire
Allowable input voltage -0.5 to 4 V DC – –
Input linearization None Provided Provided None
Output signal 1 to 5 V DC, 2 outputs (output resistance: 1 Ω max., load resistance: 2 kΩ min.)
Selectable (upscale, downscale) or off (can be changed by BRAIN), scaleout time less than
Burnout
60 sec.
Between input and output signals, input signal and power input Between output signal and
Signal isolation
power input
Mounting method Mounted in special nest (signals and power supply are connected via backboard and connector)
External wiring: M4 screw terminals for I/O in special nest Wiring to I/O cards: By special cable
Wiring
using connector
External dimensions 73 (Width)x24 (Height)x115 (Depth) mm (including knob)
Weight 70 g
Within larger of ±0.1 %
Within ±0.1 % Within larger of ±0.1 % of Within ±0.1 %
Accuracy rating (*4) of span and ±20 µV of
of span span and 0.2 °C of span
input conversion
Reference junction Type R, S: ±2 °C
– – –
compensation error Other types: ±1 °C (*3)
Between input and output signals, input signal and power input: at 500 V DC,100 MΩ Between
Isolation resistance
output signal and power input: at 500 V DC,100 MΩ
Between input and output signals, input signal and power input: 1500 V AC for 1 minute
Withstanding voltage
Between output signal and power input: 500 V AC for 1 minute
Power supply voltage 24 V DC ±10 %
Max. current consumption (24 V DC) 60 mA 60 mA 60 mA 60 mA
Ambient conditions 0 to 50 °C /5 to 90 % RH (non-condensing)
Effect of ambient temperature change Max. ±0.2 % of span for 10 °C change
Effect of power supply voltage change Max. ±0.1 % of span for change of 24 V DC ±10 %
Reference Junction
Accessory – Compensation Sensor – –
(*6)

*1: Influence of external input resistance: ±0.1 °C/10 Ω (3 lines should be in balance)
*2: Span must be at least 50 % of total resistance.
*3: For Type B, there is no reference junction compensation.
*4: Accuracy rating of #2 output: ±0.2 % (deviation from #1 output).
*5: For JIS C 1604: 1989 JPt100, Span is 10 to 500 °C.
*6: Connected it to B and C terminals of signal conditioner.

All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K50H80-50E Aug. 31, 2015-00
<<Contents>> <<Index>> 3
Standards Specifications (2)

Input isolator 2-wire transmitter


Input isolator
card (with 2-wire transmitter input card input card (with HART
Name card (1 to 5 V
square root (*2) communication function)
input)
extraction) (*4) (*5) (*6) (*7)
Model EH1 EH5 EA1 EA2 EA5 EA7
4 to 20 mA DC signal from 2-wire transmitter
Input signal 1 to 5 V DC 1 to 5 V DC
(Power can be fed transmitter)
250 Ω or its equivalent
1 MΩ
Input resistance 250 Ω (voltage drop is 5 V or less,
(100 kΩ when power off)
at 20 mA input)
External input resistance – RL= (20 – minimum transmitter operating voltage) /0.02 Ω
Allowable input voltage ±30 V DC ±9 V DC Allowable input current: 40 mA DC
Square
Square root root
Input linearization – – –
extraction (*1) extraction
(*1)
25 to 28 V DC
25.0 to 25.5 V DC
Transmitter power supply – (current limit: 25 to
(current limit: 25 to 35 mA)
35 mA)
4 to 20 mA, 1 output
1 to 5 V DC, 2 outputs (output resistance: 1 Ω max. load resistance: (output resistance: 500 kΩ
Output signal
2 kΩ min.) min. load resistance: 0 to
350 Ω)
Signal isolation Between input and output signals, input signal and power supply input
Mounting method Mounted in special nests (connected via backboard and connector)
External wiring: Connect M4 screw terminals for I/O in the special nest
Wiring
Connected I/O card: Special cable
External dimensions 73 (Width)x24 (Height)x115 (Depth) mm
Weight 70 g
Within ±0.1 % of the span.
Accuracy rating (*3)
However, accuracy under 2 % of EH5 and EA5 input must be in ±1 % of the span.
Between input and output signals, input signal and power input: at 500 V DC,100 MΩ
Isolation resistance
Between output signal and power input: at 500 V DC, 100 MΩ
Between input and output signals, input signal and power input: 1500 V AC for 1 minute
Withstanding voltage
Between output signal and power input: 500 V AC for 1 minute
Power supply 24 V DC ±10 %
Maximum current consumption 55 mA 50 mA 80 mA 100 mA 80 mA 100 mA
Ambient conditions 0 to 50 °C /5 to 90 % RH (non-condensing)
Effect of ambient temperature change Max. ±0.2 % of span for 10 °C change
Effect of power supply voltage change Max. ±0.1 % of span for change of 24 V DC ±10 %

*1: Relationship between input and output is as follows:


Y = 2 X – 1 + 1 (V), where X is input and Y is output.
*2: EA2 can be combined with intelligent transmitter BRAIN SERIES.
*3: Accuracy rating of #2 output: ±0.2 % (deviation from #1 output).
*4: EA7 cannot be used with SPBD standby manual station.
*5: EA7 can only be connected to HART communication devices such as up to 5 units of devices (e.g. transmitter) and a
secondary device (e.g. hand held terminal).
*6: When EA7 is used with following Yokogawa products, change the setting of EA7 for HART communication is required.
- Model YTA (Stype 1 and 2) temperature transmitters shipped befor 2003
- Models DY and DYA vortex flowmeters shipped before 2003
- Models AM11, AE, AE14, SE, and SE14 magnetic flowmeters
*7: HART communication does not work properly when EA7 is used in combination with Yokogawa EXA202 series analytical
products (models PH202G, PH202S, SC202G, SC202S, ISC202G, ISC202S, D0202G, and D0202S). Model FLXA21
works appropriately.

All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K50H80-50E Aug. 19, 2011-00
<<Contents>> <<Index>> 4
Standards Specifications (3)

Control output
Control output isolator isolator card (with
Name Output isolator card Output isolator card
card (*3) HART communication
function) (*2) (*3)
Model EH0 EA0 EC0 EC7
Input signal 1 to 5 V DC 1 to 5 V DC 4 to 20 mA DC
250 Ω or equivalent at 20
Input resistance 1 MΩ (100 kΩ when power off) 250 Ω or its reguivalent
mA input
External resistance of
–- –- Reference (*1)
input
Allowable input voltage ±30 V DC Allowable input current: 40 mA DC
Output signal 1 to 5 V DC, 1 point 4 to 20 mA DC, 1 point
Output resistance Up to 1 Ω 500 kΩ or more
Output load resistance 2 kΩ or more Up to 750 Ω
Signal isolation Isolated between output and input signals, and output signal and power input
Mounting method Mounted in special nests (connected via backboard and connector)
External wiring: Connected to M4 screw terminals for input/output of special nests I/O cards: Special cable
Wiring
(connector cable)
External dimensions 73 (Width)x24 (Height)x115 (Depth) mm (including knob)
Weight 70 g
Accuracy rating Within ±0.1 % of span Within ±0.1 % of span Within ±0.2 % of span
Between output and input signals, output signal and power input: at 500 V DC, 100 MΩ
Isolation resistance
Between input signal and power input: at 500 V DC, 100 MΩ
Between output and input signals, output signal and power input: 1500 V AC for 1 minute
Withstanding voltage
Between input signal and power input: 500 V AC for 1 minute
Power supply 24 V DC ±10 %
Maximum current
consumption (24 V 50 mA 85 mA 60 mA
DC)
Ambient conditions 0 to 50 °C /5 to 90 % RH (non-condensing)
Effect of ambient
Max. ±0.2 % of span for 10 °C change
temperature change
Effect of power supply
Max. ±0.1 % of span for change of 24 V DC ±10 %
voltage change

*1: Allowable external input residence ≤ Allowable load resistance of current signal –250 (Ω).
*2: EC7 can only be connected to HART communication devices such as a device (e.g. positioner) and a secondary device
(e.g. hand held terminal).
*3: EC0 has load-open detection function. So suitable arrester for EC0 is AR-HA (not AR-SA.)
EC7 also has load-open detection function. However, suitable arrester for EC7 is AR-SA.

All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K50H80-50E Aug. 19, 2011-00
<<Contents>> <<Index>> 5
Standards Specifications (4)

Name Pulse train input card


Model EP1
2-wire type: On/Off contact, voltage pulse, current pulse (Power fed to transmitter is available)
Input signal
3-wire type: power feeding type voltage pulse
Input frequency 0 to FR (kHz). However, 0 FR ≤ 6 (kHz) (*1)
Min. Input pulse width On and Off time: 60 µs each
Contact input: Relay contact, transistor contact
Detecting level Open: 100 kΩ or more
Closed: 200 Ω or less
Contact capacity 15 V DC, 15 mA or more
Input signal level Voltage/current Pulse input:
EL (low level) -1 to +8 V DC
Eh (High level) +3 to +24 V DC
Voltage swing Eh-EL ≥ 3 V (5 V or more for 6 kHz or more)
Signal source resistance: 1 kΩ or less
Input filter 10 ms, ON/OFF for setting Jumper pin
Internal load resistance
Selected from 200 Ω, 510 Ω or 1 kΩ (by jumper pin inside card)
(for current pulse)
power supply for transmitter 12 V DC ±10 %, 30 mA or less
Output signal Transistor contact (open collector), 2 outputs
Output frequency Same as input frequency
Output contact capacity 30 V DC, 30 mA (Max.)
Signal isolation Isolated between input and output signals, and input signal and power supply input
Mounting method Mounted in special nests (signal and power supply are connected via backboard and connector)
External wiring: Connected to M4 screw terminals for input/output of special nest, I/O card:
Wiring
Special cable (connector connection)
External dimensions 73 (Width)x24 (Height)x115 (Depth) mm (including knob)
Weight 70 g
Between input and output signals, input signal and power input: at 500 V DC,100 MΩ
Isolation resistance
Between output signal and power input: at 500 V DC, 100 MΩ
Between input and output signals, input signal and power input: 1500 V AC for 1 minute
Withstanding voltage
Between output signal and power input: 500 V AC for 1 minute
Power voltage 24 V DC ±10 %
Maximum current consumption
60 mA
(24 VDC)
Ambient conditions 0 to 50 °C /5 to 90 % RH (non-condensing)

*1: For voltage or current pulse, if swing amplitude is 5 V or more, 0< FR ≤ 12 (kHz) is available.

All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K50H80-50E Aug. 19, 2011-00
<<Contents>> <<Index>> 6
Standards Specifications (5)

Name Frequency input


Model EP3
2-wire type: On/Off contact, voltage pulse, current pulse
Input signal (Internal distributor may be used to supply power to transmitter)
3-wire type: Voltage pulse, internal distributor may be used to supply power to transmitter
Input frequency 0 to 10 kHz (Low level input cut off point 0.01 Hz)
100% frequency 0.1 Hz to 10 kHz
Zero elevation Between 0 to 50 % of input frequency
Measuring range and low
Can be changed by BRAIN terminal (*1)
level input cut off point
On time: 60 µs Off time : 60 µs (for input frequency 0 to 6 kHz)
Main. Input pulse width
On time: 30 µs Off time : 30 µs (for input frequency 6 to 10 kHz)
Contact input: Relay contact, transistor contact
Detection level Open: more than100 kΩ
Closed: less than 200 Ω
Contact capacity: at least 15 V DC, 15 mA or more
Voltage/current Pulse input:
Input signal level
EL (low level): -1 to +8 V DC
Eh (high level): +3 to +24 V DC
Voltage swing: (Eh-El): ≥ 3 Vpp (for input frequency 0 to 6 kHz )
≥ 5 Vpp (for input frequency 6 to 10 kHz )
Signal source resistance: 1 kΩ or less
Internal load resistance Selected for 200 Ω, 500 Ω or 1 kΩ, Jumper pin on the card (for current pulse input)
Input filter 10 ms, ON/OFF for setting Jumper pin
Internal distributor 12 V DC 30 mA or 24 V DC 30 mA. Set for Jumper pin
Output signal 1 to 5 V DC, 2 outputs (output resistance: 1 Ω max., load resistance: 2 kΩ min.)
Accuracy rating (*2) Within ±0.1 % of span
Signal isolation Isolated between input and output signals, and input signal and power supply input
Mounting method Mounted in special nests (signal and power supply are connected via backboard and connector)
External wiring: Connected to M4 screw terminals for input/output inspecial nest, I/O card:
Wiring
Special cable (connector connection)
External dimensions 73 (Width)x24 (Height)x115 (Depth) mm (including knob)
Weight 75 g
Between input and output signals, input signal and power input: at 500 V DC,100 MΩ
Isolation resistance
Between output signal and power input: at 500 V DC, 100 MΩ
Between input and output signals, input signal and power input: 1500 V AC for 1 minute
Withstanding voltage
Between output signal and power input: 500 V AC for 1 minute
Power voltage 24 V DC ±10 %
Maximum current
110 mA
consumption (24 VDC)
Ambient conditions 0 to 50 °C /5 to 90 % RH (non-condensing)
Effect of ambient
Max. ±0.2 % of span for 10 °C change
temperature change
Effect of power supply
Max. ±0.1 % of span for change of 24 V DC ±10 %
voltage change

*1: Valid number of digit is 4 for the range and low cut off point.
*2: Accuracy rating for the second output is ±0.2 %.

All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K50H80-50E Aug. 19, 2011-00
<<Contents>> <<Index>> 7
Name Input/Output through-card Extension card Communication card
Model EX1 EXT ESC
Input signals are output as they are.
Input/Output signal –- –-
(This card has no second output.)
External wiring: Connected to M4
screw terminals for input/Output in
Wiring –-
special nest, I/O card: Special cable
(connector connection)
73 (Width) x 24 (Height) x 115 (Depth) 72 (Width) x 23 (Height) x 243 95 (Width) x 24 (Height) x 113
External dimensions
mm (including knob) (Depth) mm (including knob) (Depth) mm
Weight 30 g 200 g 200 g
Between input signal and power input:
Between communication signal line
at 500 V DC, 100 MΩ
Isolation resistance –- and power input: at 500 V DC,
Between output signal and power
100 MΩ
input: at 500 V DC, 100 MΩ
Between input signal and power input:
Between communication
1500 V AC for 1 minute
Withstanding voltage –- signal line and power input:
Between output signal and power
500 V AC for 1 minute
input: 500 V AC for 1 minute
Power voltage No power supply required No power supply required 24 V DC ±10 %
Maximum current
–- –- 100 mA
consumption (24 V DC)
Ambient conditions 0 to 50 °C/5 to 90 % RH (non-condensing)

n RECOMMENDED RANGE LIST


Recommended Ranges for Thermocouple Recommended Ranges for resistance
Thermometer Sensor
Sensor Recommended range (°C)
0 to 1000 0 to 1600 600 to 1600 Sensor Recommended range (°C)
Type R
0 to 1200 400 to 1400 800 to 1600 –20 to 50 0 to 70 20 to 50
Type S
0 to 1400 500 to 1500 –40 to 60 0 to 100 50 to 100
Pt100 (JIS:2013/
Type B 600 to 1500 600 to 1700 ** –50 to50 0 to 120 50 to 150
IEC/ITS-90),
0 to 300 200 to 500 500 to 1000 –50 to 100 0 to 150 50 to 200
Pt100 (JIS:1989/
0 to 400 200 to 700 500 to 1200 –50 to 150 0 to 200 100 to 200
DIN/IPTS-68),
0 to 500 200 to 1000 600 to 1000 –100 to 50 0 to 250 100 to 250
JPt100(JIS:1989),
0 to 600 300 to 600 600 to 1200 –200 to 50 0 to 300 100 to 300
Type K Pt50(JIS:1981)
0 to 800 300 to 800 700 to 1000* 0 to 20 0 to 400 200 to 400
0 to 1000 400 to 800 700 to 1200* 0 to 50 0 to 500 300 to 500
0 to 1200 400 to 1000
Note: Bold letters show Japan Electric Measuring
100 to 500 500 to 800
Instruments Manufacturer’s Association Standard.
0 to 200 0 to 500 200 to 500
0 to 250 0 to 600 300 to 500
Type J 0 to 300 100 to 300 300 to 600
0 to 350 100 to 500
0 to 400 200 to 400
0 to 200 0 to 600 200 to 500
0 to 250 0 to 700 300 to 500
0 to 300 0 to 800 300 to 600
Type E
0 to 350 100 to 300 300 to 700
0 to 400 100 to 500
0 to 500 200 to 400
–100 to 200 0 to 250 100 to 300
Type T
–150 to 150 0 to 300

Note: Bold letters show Japan Electric Measuring


Instruments Manufacturer’s Association Standard.
Note: Zero elevation exceeds specified specifications.
Note: Measuring range of Type B is 600 to 1700 °C.
0% value must be above 200 °C

All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K50H80-50E Aug. 31, 2015-00
<<Contents>> <<Index>> 8
n MODELS AND SUFFIX CODES
l Signal Conditioner Cards

Style Code
Description
(*1)
ET5 *C Thermocouple input card
ER5 *C Resistance thermometer sensor input card
ES1 *C Potentiometer input card
EM1 *C mV input card
EH1 *B Input isolator card (1 to 5V)
EH5 *C Input isolator card (1 to 5V with square root)
EA1 *B 2-wire transmitter input card
Model EA2 *B 2-wire transmitter input card (used with BRAIN series)
EA5 *C 2-wire transmitter input card (with square root)
EP1 *A Pulse train input card
EP3 *A Frequency input card
EC0 *A Control output isolator card
EA0 *B Output isolator card (4 to 20 mA)
EH0 *B Output isolator card (1 to 5V)
EX1 *A I/O through card
/BU Upscale burnout (*2)
Suffix
/BD Downscale burnout (*2)
Codes
/DF Fahrenheit display function (*3)

*1: Style Code is described as SUFFIX on the actual products.


*2: Applied to ET5, ER5, ES1, and EM1. Can be changed using BRAIN terminals.
*3: Applied to ET5 and ER5. If “/DF” is not specified, temperature in Fahrenheit can not be indicated.

Description
EA7 2-Wire transmitter input card (with HART communication function)
Model
EC7 Control output isolator card (with HART communication function)

l Extension Card

Description
Model EXT Extension card (for BRAIN terminal)
Style Code
*A Style A
(*1)

*1: Style Code is described as SUFFIX on the actual products.

l Communication Cards for BRAIN terminal

Description
Model ESC Communication card for BRAIN terminal (installed in SC nest)
Style Code
*B Style B
(*1)

*1: Style Code is described as SUFFIX on the actual products.

All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K50H80-50E Aug. 1, 2014-00
<<Contents>> <<Index>> 9
Field Side Terminal
Terminal Code
Signal Conditioner Card
A B C
EM1 + -
+ -

RJC Sensor

Thermocouple
ET5 (*1) RJC Sensor
connected to connected to
B terminal C terminal

ER5 (*2)

ES1 (*3)
100 % 0%
2-wire + -
(voltage, connect)
EP1
2-wire power supply Signal Power supply
EP3
3-wire power supply + Power supply -
EH1, EH5 + -

+ -
EA1, EA2, EA5, EA7 (*4) (*5)
- +

EH0, EA0, EC0, EC7 + -


EX1 + -
[Link]

*1: The Reference Junction Compensation Sensor (RJC Sensor) is attached to ET5. Connected it to B and C terminals of
signal conditioner.
*2: Must be wiring resistance of A as same as B.
*3: Must be wiring resistance of A as same as C.
*4: B terminal is used when combined with BARD safety barrier.
*5: In the case of 4-to-20 mA input that requires no transmitter power supply, connect to C-terminal (+) and B-terminal (–) .
Input resistance of EA1, EA2 and EA5 is 250 Ω
For EA7, input resistance is equivalent to 250 Ω (voltage drop is 5 V or less, at 20 mA input).

All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K50H80-50E Aug. 19, 2011-00
<<Contents>> <<Index>> 10
n EXTERNAL DIMENSIONS (*1)
Unit: mm

SPAN

67.5

96.5
ZERO

23.6 114.5
[Link]

*1: Not include EXT, ESC.

n ACCESSORIES AND SPARE PARTS


The spare parts listed below are provided with the ET5.

Name Part No. Description Quantity Remarks


Connected it to B and C terminals of signal
RJC Sensor L3501RA Reference Junction Compensation Sensor 1
conditioner.

n ORDERING INFORMATION
• Specify model and option code if required.
• Input specifications (for ET5, ER5, ES1, EM1, and EP3)
ET5: The standards that thermocouple should comply with, type and measuring range
(ex: IEC, Type K, 0 to 800 °C)
ER5: The standards that RTD should comply with, type, resistance at 0 °C, and measuring range
(ex: JIS: 2013, Pt100, 0 to 300 °C)
ES1: Whole resistance, resistance at 0 % point, resistance at 100 % point.
EM1: Measuring range.
EP3: Measuring range (Unit: Hz). Valid number is 4 digits. But can be applied 10000.
If burnout function is required, specify /BU or /BD.

n TRADEMARKS
CENTUM is a registered trademark of Yokogawa Electric Corporation.

All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K50H80-50E Aug. 31, 2015-00