Top secret

Secret
Internal use only
Public

Daikin Mobile Monitoring Tool


Table of content

Specifications
Functionality
Compatibility
Additional info
Preparation
Installation
Connection hardware – software
Data possibilities
Record data
Option button in record mode
Playback data
Send data
Delete data
Analyse data via D-checker on PC or Laptop
Functionallity
Function D-checker Monitoring tool
Real time data Yes Yes

Record data Yes Yes

Playback data Yes Yes (own data only)

Export data Yes Yes (by email only)

CSV export Yes No*

Import data Yes No

Graph chart Yes No*

Edit data label Yes No

Customer detail info Yes No

Multi-language switch Yes No

* Possible when openend with D-checker (NEW Version 3.204) software on PC or laptop

3 Title - Internal use only


Compatibility

Supported Daikin Monitoring Remarks Connection plug


products tool
SkyAir OK 2003 models & later 7 pins

RA OK 2002 models & later 5 pins

Chiller Not OK /

VRV OK Max 59 indoor units 7 pins


2003 models & later*
Altherma LT OK 2010 models & later 7 pins

Altherma HT Not OK /

Altherma Flex Not OK /

Refrigeration Not OK

4 Title - Internal use only


Additional information

Bluetooth
- Communication range = 5-7 m
- Class 2 Bluetooth device, supporting Bluetooth 2.0

Combinations
OK/NOK App Tablet Wireless PC PC PC
Smart adapter Software Cable
phone 3.XXX (Normal way)
OK X X X
OK X X X
NOK X X X
OK X X X

5 Title - Internal use only


Preparation

Hardware :
1. BTSC/i2S = Wireless adapter + 2 types of wire harnesses
5 pins

7 pins

6 Title - Internal use only


Preparation

Hardware:
2. S-ISO = Isolator + Wire connection for BTSC/i2S
! Field supplied connection to 5 VCD power supply required

Required for all split units

7 Title - Internal use only


Installation – Software

1. Download and install the Daikin Monitoring app on your


mobile device.
Search for: Daikin Air Conditioning Monitoring Tool

8 Title - Internal use only


Installation – Hardware

1. Only wireless adapter BTSC/i2S


1. Shut off your unit via user interface and circuit breaker.
2. Connect the BTSC/i2S with your units monitoring connection.
(= D-checker connection; Possible with 5 or 7 pins connection)
3. Put the power back on to the unit
4. Check if the LED on the BTSC/i2S is blinking red (2 timer/sec)

9 Title - Internal use only


Installation – Hardware

1. Only wireless adapter BTSC/i2S

Connection harness
(5 pin or 7 pin)

BTSC/i2S

Android™ or Itunes App


BTSC/i2S on mobile device
(Wireless adapter)

10 Title - Internal use only


Installation – Hardware

11 Title - Internal use only


Installation – Hardware

2. Wireless adapter BTSC/i2S + Isolator S-ISO


1. Shut off your unit via user interface and circuit breaker.
2. Connect the S-ISO isolator and BTSC/i2S with your units
monitoring connection.
(= D-checker connection; Possible with 5 or 7 pins connection)
1. Put the power back on for the unit
2. Check if the LED on the BTSC/i2S is blinking red (2 timer/sec)

12 Title - Internal use only


Installation – Hardware

2. Wireless adapter BTSC/i2S + Isolator S-ISO

Connection harness Wire connection between S-ISO and BTSC/i2S


(5 pin or 7 pin)

BTSC/i2S

BTSC/i2S Android™ App


(Wireless adapter)
S-ISO (Electric isolator)

Field supplied 5VDC connection required ! Via Mini-USB connection

13 Title - Internal use only


Installation – Hardware

14 Title - Internal use only


Connection hardware and software for Android

1. Start up the Daikin Mobile Monitoring Tool App

15 Title - Internal use only


Connection hardware and software for Android

2. Select option

16 Title - Internal use only


Connection hardware and software for Android

3. Enter your Service office and the Responsible person

+ Select OK (1)
(2)

17 Title - Internal use only


Connection hardware and software for Android

Now all ‘buttons’ are released

18 Title - Internal use only


Connection hardware and software for Android

4. Select Recording

19 Title - Internal use only


Connection hardware and software for Android

5. Make sure you have Bluetooth connection

20 Title - Internal use only


Connection hardware and software for Android

6. Select scan

21 Title - Internal use only


Connection hardware and software for Android

7. Connect your mobile device


to your Mobile Monitoring tool

Remarks
During first connection it is possible the name
of your device is not correct.

Unpaird = No connection
Paired = Connection

22 Title - Internal use only


Connection hardware and software for Android

8. Enter password 3131

23 Title - Internal use only


Connection hardware and software for Android

Do not pair with multiple


Mobile Monitoring tools!

9. Select OK

24 Title - Internal use only


Connection hardware and software for Ios (Apple)

1. Start up the Daikin Mobile Monitoring Tool App

25 Title - Internal use only


Connection hardware and software for Ios (Apple)

2. Select options

26 Title - Internal use only


Connection hardware and software for Iso (Apple)

3. Enter your Service office and the Responsible person

+ Select OK (1)
(2)

27 Title - Internal use only


Connection hardware and software for Ios (Apple)

Now all ‘buttons’ are free

28 Title - Internal use only


Connection hardware and software for Ios (Apple)

4. Go to Settings on your mobile device

29 Title - Internal use only


Connection hardware and software for Ios (Apple)

5. Select Bluetooth

30 Title - Internal use only


Connection hardware and software for Ios (Apple)

6. Make sure bluetooth is ON

7. Select your wireless adapter

Remark
When your first connect with your
wireless adapter is is possible the name
is not correct

31 Title - Internal use only


Connection hardware and software for Ios (Apple)

8. Enter the PIN code 3131

32 Title - Internal use only


Connection hardware and software for Ios (Apple)

If connected is indicated, go back to the


Daikin Mobile Monitorin tool App

33 Title - Internal use only


Connection hardware and software for Ios (Apple)

9. Select Recording

34 Title - Internal use only


Connection hardware and software for Ios (Apple)

Do not pair with multiple


Daikin Monitoring tools!

10. Select OK

35 Title - Internal use only


Record data – Enter Options

Before selecting Record, you can


go to Options for:
- Display mode
- Sampling rate
- Period
- Duration
- Manual stop
- Unit of measurement

+ Select OK

36 Title - Internal use only


Record data

1. Connect software and hardware


(See chapter “Connect software and hardware”)

37 Title - Internal use only


Record data

2. Enter :
- Customer ID
- Mape name (Auto generates date + time)
- System name (Auto generates date + time)
- Model

Only necessary for personal reference,


has no influence on recording.

38 Title - Internal use only


Record data

3. Select protocol
- SkyAir
- Altherma
- VRV
- …

39 Title - Internal use only


Record data

2. Select Connect

Altherma

40 Title - Internal use only


Record data

Protocol check succeeded


= Mobile device can connect to your unit

3. Select correct data label file

! The device can not automatically select


the correct data label file because the unit
does not send out this information !

4. Select OK

41 Title - Internal use only


Record data

5. Start the recording

Sampling rate is selected


in the beginning of the
procedure.

It can take up to 20 sec before


you see data

42 Title - Internal use only


Record data

6. Double check if the timer is running

43 Title - Internal use only


Record data

Data is divided in sub-sections!

Select the correct sub-section to see


the data.

All data that is shown in D-checker for your


PC or Laptop is also visible with the Mobile
Monitoring tool.
No additional pasword is required, immediatly
all data is available!

44 Title - Internal use only


Record data

7. Stop your recording

45 Title - Internal use only


Option button in record mode (while not recording)

1. Select options

46 Title - Internal use only


Option button in record mode (while not recording)

2. Select
- Display mode
- Select indoor unit
- Record setting

47 Title - Internal use only


Option button in record mode (while not recording)

Display mode Select indoor unit Record settings

1 column display

2 column display

48 Title - Internal use only


Playback recorded data on mobile device

1. Select play

49 Title - Internal use only


Playback recorded data on mobile device

2. Select recording

50 Title - Internal use only


Playback recorded data on mobile device

3. Tap anywhere to show


‘time scroll’ options

> 5 seconds further


< 5 seconds back
>> end of recording
<< beginning of recording

51 Title - Internal use only


Send recorded data

1. Select play

52 Title - Internal use only


Send recorded data

2. Select edit

53 Title - Internal use only


Send recorded data

3. Select the recording(s)

4. Select send

54 Title - Internal use only


Send recorded data

5. Confirm sending

6. Mark as ‘send’ when required

55 Title - Internal use only


Send recorded data

7. Select software for sending data

8. Finish sending data via selected software

56 Title - Internal use only


Analyse data via D-checker software on PC or Laptop

1. Send recorded data via Mobile device to your PC or Laptop


See chapter ‘Send recorded data’.

2. Save file ‘recorded data’ on your PC or Laptop

3. Start up D-checker version 3.XXX on your PC or Laptop


New version of D-checker will be launched together with
Daikin Mobile Monitoring tool.

57 Title - Internal use only


Analyse data via D-checker on PC or Laptop

4. Before continuing, check:


- (Options: COM PORT)
- Options: Service office
- Options: Responsible person

+ Select OK

58 Title - Internal use only


Analyse data via D-checker on PC or Laptop

5. Select Mobile App Data Import

59 Title - Internal use only


Analyse data via D-checker on PC or Laptop

6. Select the file that was saved

! Do not change the name


before importing
! Do not unzip before
importing

60 Title - Internal use only


Analyse data via D-checker on PC or Laptop

7. If this screen pops-up, select OK

61 Title - Internal use only


Analyse data via D-checker on PC or Laptop

8. Select play

62 Title - Internal use only


Analyse data via D-checker on PC or Laptop

9. Select your recording


10. Select Op. Data displ (F1)

63 Title - Internal use only


Analyse data via D-checker on PC or Laptop

‘Standard’ D-checker screen is available now.


For additional information about D-checker V3.XXX,
please go to the user manual of this tool

64 Title - Internal use only