12kV Metalclad Switchgear Specifications

This document provides specifications for 12kV metalclad switchgear models 12A20 and 12A25, including rated voltages, currents, insulation levels, dimensions, and protection classes. Key specifications listed are a rated voltage of 12kV, short circuit withstand currents of 20-25kA for 3 seconds, and IP4X/3X enclosure/compartment protection. Dimensions provided are 600-2000mm widths, 2200-2250mm depths, and 2300mm heights.

Uploaded by

haman man
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
285 views1 page

12kV Metalclad Switchgear Specifications

This document provides specifications for 12kV metalclad switchgear models 12A20 and 12A25, including rated voltages, currents, insulation levels, dimensions, and protection classes. Key specifications listed are a rated voltage of 12kV, short circuit withstand currents of 20-25kA for 3 seconds, and IP4X/3X enclosure/compartment protection. Dimensions provided are 600-2000mm widths, 2200-2250mm depths, and 2300mm heights.

Uploaded by

haman man
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

The values below are given for normal operating condition as defined in IEC 60298, IEC

60694, IEC 62271-100 / 200

Switchgear Model 12A20 12A25


Rated voltage kV 12 12
Rated frequency Hz 50 50
Rated insulation level
-Power frequency withstand voltage/min kV 28/32 28/32
-Lightning impulse withstand voltage (peak) kV, 1.2/50 μs 75/85 75/85

Rated normal current of Busbar A 800/1250/2000


Rated short time withstand current kA/3s 20 25
Rated peak withstand current kA 50 63
Standard degree of protection (1)
Enclosure 4X
Compartment 3X

Dimension
Width mm 600, 800, (2000A)
Depth mm 2200,2250 (with PT)
Height mm 2300
Other values are available on request.

12A20 / 25
12kV METALCLAD SWITCHGEAR
Circuit Breaker Model VFT-12
Rated voltage kV 12
Rated current A 630/1250/2000
Rated frequency Hz 50
Rated insulation level
-Power frequency withstand voltage kV/ 1 min 28/32
-Lightning impulse withstand voltage kV, 1.2/50 μs 75/85

Rated short circuit breaking current kA, rms 50/63


Rated short circuit withstand current kA/3s 20/25
Rated short circuit making current (peak) kA 50/63
Mechanical endurance 10,000
Rated operating sequence/duty 0-0.3s-CO-3min-CO

Rated closing time ms <60


Rated opening time ms <50
Rated breaking time ms <60

Standard trip/close supply (1) Vdc 30/110


Other values are available on request.
Standard motor charging supply (2) Vdc (Vac) 30/110(240 Vac)

GENERAL DESCRIPTION
Indoor air insulated metalclad switchgear. Mechanical intelocks are provided to
safeguards against maloperation.
Vacuum circuit breaker is mounted on truck for
horizontal withdrawal and isolation. Design type tested to IEC 62271-100/200,
IEC 60298, IEC 60056, IEC 60694
Integral fault making earthing switch, class A on the
circuit side. Busbar earthing truck is optional.

You might also like