0% found this document useful (0 votes)
583 views4 pages

6114D/6124D Motor Specifications

This document provides specifications for an electric generator including: - Key electrical details such as a 3-phase, 4-pole design with 12 leads and a shunt excitation system. - Performance ratings at different power factors, temperatures, voltages and speeds. Maximum kVA ratings range from 414 to 570. - Efficiency ratings from 91.5% to 94.5% depending on loading levels. - Reactance values and time constants that characterize the generator's performance under different operating conditions.

Uploaded by

mahmoud khta
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
583 views4 pages

6114D/6124D Motor Specifications

This document provides specifications for an electric generator including: - Key electrical details such as a 3-phase, 4-pole design with 12 leads and a shunt excitation system. - Performance ratings at different power factors, temperatures, voltages and speeds. Maximum kVA ratings range from 414 to 570. - Efficiency ratings from 91.5% to 94.5% depending on loading levels. - Reactance values and time constants that characterize the generator's performance under different operating conditions.

Uploaded by

mahmoud khta
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

FRAME 6114D / 6124D WINDING 6

MODELS LL6114D / LL6124D / LL6134D REF: F6104DW6-3 JULY 2010

WINDING DETAILS MECHANICAL DETAILS


Code 6 Insulation class H Standard protection IP23
Phase 3 Leads 12 Overspeed rpm 2250
Pole number 4 Pitch 2/3 Air flow 50Hz/60Hz m3/s 0.9 / 1.1

EXCITATION DETAILS WAVEFORM


Excitation system SHUNT AREP/PMG Line voltage on no load or balanced linear rated load
AVR model R450M R450M Total harmonic content THC <4%
Sustained short-circuit current - 300%:10s Telephone influence factor TIF (NEMA) <50
Steady state voltage regulation ±0.5% ±0.5% Telephone harmonic factor THF (IEC) <2%

LINE VOLTAGE No overvoltage tolerance for 440V 50Hz excitation level


Frequency / speed 50Hz / 1500rpm 60Hz / 1800rpm
Series star V 380 400 415 440 380 400 416 440 460 480
Series delta V 220 230 240 220 230 240
Parallel star V 200 208 220 200 208 220 230 240
1 2 3 4 6 7 8 9 10 11
RATING Power factor 0.8, Altitude <=1000m
Class H rise BR 125/40 kVA 455 455 455 430 490 510 545 550 570 570
kW 364 364 364 344 392 408 436 440 456 456
Class H rise PR 150/40 kVA 482 482 482 456 519 541 578 583 604 604
kW 386 386 386 365 416 432 462 466 483 483
Class H rise PR 163/27 kVA 501 501 501 473 539 561 600 605 627 627
kW 400 400 400 378 431 449 480 484 502 502
Class F rise BR 105/40 kVA 414 414 414 391 446 464 496 501 519 519
kW 331 331 331 313 357 371 397 400 415 415

EFFICIENCIES Power factor 0.8


110% Class H BR % 93.2 93.5 93.7 93.9 92.4 92.8 92.8 93.3 93.4 93.7
100% Class H BR % 93.5 93.8 93.9 94.1 92.8 93.1 93.2 93.5 93.7 93.9
75% Class H BR % 94.2 94.4 94.4 94.4 93.5 93.7 93.8 94.1 94.2 94.3
50% Class H BR % 94.5 94.5 94.4 94.1 93.6 93.8 93.9 94.0 94.1 94.1
25% Class H BR % 93.1 92.8 92.6 91.5 91.7 91.8 92.1 92.0 92.0 91.7

CHARACTERISTIC PARAMETERS Reactance base class H BR rating


Kc Short-circuit ratio 0.29 0.33 0.38 0.51 0.20 0.22 0.22 0.26 0.28 0.32
Xd D-Axis synchronous reactance (unsaturated) pu 3.95 3.57 3.32 2.79 5.11 4.80 4.74 4.28 4.06 3.73
X'd D-Axis transient reactance (saturated) pu 0.21 0.19 0.18 0.15 0.27 0.26 0.26 0.23 0.22 0.20
X''d D-Axis sub-transient reactance (saturated) pu 0.149 0.135 0.125 0.105 0.193 0.181 0.179 0.161 0.153 0.140
Xq Q-Axis synchronous reactance (unsaturated) pu 2.37 2.14 1.99 1.67 3.07 2.88 2.85 2.57 2.43 2.24
X''q Q-Axis sub-transient reactance (saturated) pu 0.200 0.180 0.167 0.141 0.258 0.242 0.239 0.216 0.205 0.188
X2 Negative-sequence reactance (saturated) pu 0.175 0.157 0.146 0.123 0.226 0.212 0.209 0.189 0.179 0.164
X0 Zero-sequence reactance (independent) pu 0.011 0.010 0.009 0.008 0.014 0.013 0.013 0.012 0.011 0.010
T'd D-Axis transient time constant ms 100 100
T''d D-Axis sub-transient time constant ms 10 10
T'do D-Axis open-circuit time constant ms 1855 1855
Ta Armature time constant ms 15 15
Tr Voltage recovery time ms < 500 < 500

EXCITATION VOLTAGE AND CURRENT

No load excitation voltage V 8.3 9.2 10.0 12.0 6.2 6.7 7.0 7.8 8.4 9.2
No load excitation current A 0.81 0.90 0.98 1.18 0.61 0.66 0.69 0.76 0.82 0.90
Class H BR excitation voltage V 38.9 38.7 38.9 38.7 38.4 38.5 40.0 39.1 39.8 39.6
Class H BR excitation current A 3.81 3.79 3.81 3.79 3.76 3.77 3.92 3.83 3.90 3.88

WINDING RESISTANCE At 20 o C
Stator line-to-line (series star) Ω 0.0127 Exciter field Ω 10.20
Main field Ω 0.88

According to: IEC 60034, UTE NFC51.111, VDE 0530, BS 4999/5000, NEMA MG 1-33
Values quoted are typical. In line with our policy of continuous improvement, we reserve the right to change specification without notice.
FRAME 6114D / 6124D WINDING 6

MODELS LL6114D / LL6124D / LL6134D REF: F6104DW6-3 JULY 2010

LOCKED ROTOR MOTOR STARTING CURVES Power factor 0.6

50 Hz SHUNT

380V

400V
415V

440V
35

30

25
voltage dip %

20

15

10

0
0 200 400 600 800 1000 1200 1400 1600 1800
kVA

50 Hz AREP / PMG
380V

400V

415V

440V

35

30

25
voltage dip %

20

15

10

0
0 200 400 600 800 1000 1200 1400 1600 1800
kVA

According to: IEC 60034, UTE NFC51.111, VDE 0530, BS 4999/5000, NEMA MG 1-33
Values quoted are typical. In line with our policy of continuous improvement, we reserve the right to change specification without notice.
FRAME 6114D / 6124D WINDING 6

MODELS LL6114D / LL6124D / LL6134D REF: F6104DW6-3 JULY 2010

LOCKED ROTOR MOTOR STARTING CURVES Power factor 0.6

60 Hz SHUNT

380V

400V
416V

440V

460V

480V
35

30

25
voltage dip %

20

15

10

0
0 200 400 600 800 1000 1200 1400 1600 1800
kVA

60 Hz AREP / PMG
380V

400V

416V

440V

460V

480V

35

30

25
voltage dip %

20

15

10

0
0 200 400 600 800 1000 1200 1400 1600 1800
kVA

According to: IEC 60034, UTE NFC51.111, VDE 0530, BS 4999/5000, NEMA MG 1-33
Values quoted are typical. In line with our policy of continuous improvement, we reserve the right to change specification without notice.
FRAME 6114D / 6124D WINDING 6

MODELS LL6114D / LL6124D / LL6134D REF: F6104DW6-3 JULY 2010

THREE-PHASE SHORT-CIRCUIT DECREMENT CURVES No-load excitation at rated speed

400V 50Hz, 480V 60Hz Series Star

10000 asymmetrical

symmetrical AREP/PMG
RMS current (A)

1000

SHUNT

100
1 10 100 1000 10000
time (ms)

Multiplication Factors

50Hz Voltages 380 400 415 440

Multiplication Factor 0.95 1.00 1.04 1.10

Apply factor up to 2xT'd, remainder of curve unchanged

60Hz Voltages 380 400 416 440 460 480

Multiplication Factor 0.79 0.83 0.87 0.92 0.96 1.00

Apply factor up to 2xT'd, remainder of curve unchanged

Winding Connection Series Star Parallel Star Series Delta

Multiplication Factor 1.00 2.00 1.73

Apply factor to the complete curve

According to: IEC 60034, UTE NFC51.111, VDE 0530, BS 4999/5000, NEMA MG 1-33
Values quoted are typical. In line with our policy of continuous improvement, we reserve the right to change specification without notice.

You might also like