Customer Contract
Location #
Project
Contractor
AREVA T&D Site test record RELAY TEST Doc. Ref.
MFAC34- HIGH IMPEDANCE DIFFERENTIAL RELAY
1. GENERAL DATA AND INFORMATION:
Circuit Ref. Designation
Panel No. Serial No.
Make Model No.
Dwg & Sh No. Frequency:
Flag Type No. of Contacts
Setting Range:
2. MECHANICAL CHECKS AND VISUAL INSPECTION:
ITEM DESCRIPTION CHECKED
1 Inspect for any physical damage or defects.
2 Verify connections as per approved drawings.
3 Check that serial no. of relay matching with serial no. of case.
4 Relay CT shorting function checked.
5 Test switch checked for correct function.
6 Stabilizing resistors final setting value.
3. ELECTRICAL TESTS:
3.1 PICKUP / DORP OFF TEST:
Injection done including METROSIL resistor.
R Y B
Pickup
Voltage
Dropof Dropof Dropof current
setting Pickup Pickup Pickup Pickup Pickup Pickup
f f f limit
(V) current voltage current voltage current voltage
voltage voltage voltage (mA)
(mA) (V) (mA) (V) (mA) (V)
(V) (V) (V)
25 18-20
50 18-20
75 18-23
100 19-28
125 20-39
150 24-60
175 33-95
Plug
33-95
remove
Note: pickup voltage +/- 10% setting ,D/O and P/U ratio >50%.
Test performed by Test witnessed by Date of test
AREVA T&D
Name MUSTAFA HAJI
Signature
Customer Contract
Location #
Project
Contractor
AREVA T&D Site test record RELAY TEST Doc. Ref.
MFAC34- HIGH IMPEDANCE DIFFERENTIAL RELAY
3.2 OPERATING TIME TEST:
Setting voltage Applied voltage Measured operating time in msec
Limits
(V) 2xsetting (V) R Y B
Between 15-30 msec
(Max. to min. setting
respectively)
(Refer graph)
3.3 FINAL SETTING TESTS:
3.3.1 PICKUP / DORP OFF TEST:
R Y B
Opearate
Voltage
Dropof Dropof Dropof current
setting Pickup Pickup Pickup Pickup Pickup Pickup
f f f limits
(V) current voltage current voltage current voltage
voltage voltage voltage (mA)
(mA) (V) (mA) (V) (mA) (V)
(V) (V) (V)
Note: pickup voltage +/- 10% setting ,D/O and P/U ratio >50%.
3.3.2 OPERATING TIME TEST:
Applied voltage Measured operating time in msec
Setting voltage (V) Remarks
2xsetting (V) R Y B
Between 15-30
msec
(Max. to min.
setting respectively)
(Refer graph)
4. FUNCTIONAL TESTS:
Item Description Checked
1 All output contacts resistance measured.
2 Flag operation checked.
3 Check metrosil non-linear resistors connection
Test performed by Test witnessed by Date of test
AREVA T&D
Name MUSTAFA HAJI
Signature