INSEPCTION & TEST CHART FOR SCR ROOM
HIGH PRESSURE CO2 SYSTEM NEW INSTALLATION
RIG : ODIN STAR CLASS : A.B.S.
OWNER : NABORS DRILLING FLAG :
PANAMA
PROTECTED AREA: SCR ROOM HULL : B-178
PERFORMANCE
CHECK POINT CARRIED NOT
OUT APPLICABLE
01) Complete installation as per the
approved drawing
02) Manifold leak test, at 7 Bar with
main valve closed for 02 minutes
03) Down stream pipe leak test at 7 Bar
with nozzle ends blanked (for 02
Minutes)
04) Time delay and cylinder actuator
operation test (operating 04 Nos.
actuators after 30 seconds) from
Control Station I
05) Pilot discharge line leak test at 7 bar
for 2 minutes from Control Station I
06) Distribution Main Valve function test
(Main Valve for SCR Room) from
Control Station I
07) Function test for audible & visual
alarms, ventilation shutdown test from
Control Station I
08) Time delay and cylinder actuator
operation test (operating 04 Nos.
actuators after 30 seconds) from
Control Station II
09) Pilot discharge line leak test at 7 bar
for 2 minutes from Control Station II
10) Distribution Main Valve function test
(Main Valve for SCR Room) from
Control Station II
PERFORMANCE
CHECK POINT CARRIED NOT
OUT APPLICABLE
11) Function test for audible & visual
alarms, ventilation shutdown test from
Control Station II
12) CO2 Operating Instructions &
evacuation sign board checked
13) Reset the system
NOTE: The system is now in operative condition.
REMARKS: …………………………………………………………………………………….
……………………………………………………………………………………
WITNESS: OWNER’S REPRESENTATIVE:
CLASS: __________________ SIGN & STAMP :
SIGN & STAMP NAME :
NAME : TITLE :
DATE : DATE :
SOLAS REPRESENTATIVE : LAMPRELL
REPRESENTATIVE :
SIGN & STAMP : SIGN & STAMP :
NAME : _________________ NAME : __________________
TITLE : __________________ TITLE : __________________
DATE : __________________ DATE : __________________
RIG REPRESENTATIVE
SIGN & STAMP :
NAME : _________________
TITLE : __________________
DATE : __________________