Page 1 of 4
HIGH PRESSURE
TECHNICAL DATA SOLENOID VALVE
RATED TO 300 PSI (21 BAR)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@[Link]
1. DESCRIPTION
The high pressure solenoid valve is a two-way type with one inlet and one outlet. It is a packless, inter-
nal pilot operated valve, suitable for use in releasing water pressure from the priming chamber of Viking
Model E Series Deluge Valves and Viking Model H Series Flow Control Valves. The solenoid valve has
floating diaphragm construction, which requires a minimum pressure drop across the valve to operate
properly. The valves are available with a voltage rating of 24V DC in a normally closed or normally open
configuration, or 110/50-120/60 normally closed configuration. These solenoid valves are for use with
system control units that are listed and/or approved for releasing service for water based fire protection
systems.
Features:
1. Normally closed or Normally open
2. 24 VDC or 110/50-120/60 VAC
3. Easy to clean.
4. Body Style: Straight through
5. Required Accessories: A 50 mesh strainer must be installed on the inlet side of the valve at the
priming line connection. This strainer is included as part of the Model E-1 Deluge Valve Trim
and Model H Flow Control Valve Trim.
6. NEMA 1 through 9. (See Table 1)
Table 1 - Part Numbers and Specifications
Maximum Listings & Approvals
Part For Viking DC Cur- Cv
Description 1 Model 2 Orifice Wattage Ambient ATEX
Number System rent Factor UL CE CSA FM 9 LPCB
Temp. 6
Normally Closed
NEMA 2,3,3S,4,4X 24 VDC 11591 9/16" 10.0 DC 416 mA 150°F (65°C) 4.1 Yes 3 Yes No Yes 8 Yes Yes
NEMA 1,2,3,3S,4,4X 110 VAC/50 HZ 11593 9/16" 10.0 AC 416 mA 150°F (65°C) 4.1 Yes 3 Yes No Yes 8 No No
NEMA 1,2,3,3S,4,4X 120 VAC/60 HZ 11593 9/16" 10.0 AC 416 mA 150°F (65°C) 4.1 Yes 3 Yes No Yes 8 No No
Explosion Proof Firecycle III,
TotalPac &
NEMA 3,3S,4,4X,6,6P,7,9 24 VDC 11592 9/16" 10.0 DC 416 mA 150°F (65°C) 4.1 Yes 4 Yes No Yes 7 Yes No
Special Ap-
NEMA 3,3S,4,4X,6,6P,7,9 110 VAC/50 HZ 11594
plication
9/16" 10.0 AC 416 mA 150°F (65°C) 4.1 Yes 4 No No Yes 7 No No
NEMA 3,3S,4,4X,6,6P,7,9 120 VAC/60 HZ 11594 9/16" 10.0 AC 416 mA 150°F (65°C) 4.1 Yes 4 No No Yes 7 No No
ATEX, EEx, mll, T4/T5 110 VAC/50 HZ 12359 9/16" 10.0 AC 416 mA 150°F (65°C) 4.1 No Yes Yes No No Yes
ATEX, EEx, mll, T4/T5 24 VDC 12360 9/16" 10.0 DC 416 mA 150°F (65°C) 4.1 No Yes Yes No No Yes
Normally Open
NEMA 2,3,3S,4,4X 24 VDC 11595 Firecycle III 9/16" 10.0 DC 416 mA 150°F (65°C) 4.1 Yes 5 Yes No Yes 8 Yes Yes
Explosion Proof
Surefire &
NEMA 3,3S,4,4X,6,6P,7,9 24 VDC 11596 9/16" 10.0 DC 416 mA 150°F (65°C) 4.1 Yes 4 No No Yes 7 Yes No
Trimpac
ATEX, EEx, mll, T4/T5 24 VDC 12358 9/16" 10.0 DC 416 mA 150°F (65°C) 4.1 No Yes Yes No No Yes
Footnotes:
1 Enclosure type: 1 (General Purpose) 2 (Drip-Proof), 3 and 3S (Raintight), 4 and 4X (Watertight), 7 (Explosion-Proof, Class I, Groups A, B, C, and D),
9 (Dust Ignition-Proof Class II, Groups E, F, and G)
2 For AC voltages, in rush current (i.e. start plunger moving) = 93 volt amps. Holding current (i.e. to hold plunger open) = 40 volt amps.
3 UL Listed as Fire Protection Special System Water Control Release Service (UL 429A Product Category VLTR).
4 UL Listed as 429 Hazardous Location
5 UL Listed as Safety Shut-off (UL 429)
6 For Atex Certification, coil is an HZ10 and includes internal and external ground, with 1500 mm long molded cable. Certificate of Conformity LCIE
02 ATEX 6020 X.
7 Explosion-proof versions are CSA recognized to CSA Standards C22.2 Nos. 0, 139, 25, and 30. They are certified for Hazardous Locations Class I,
Groups A, B, C and D; Class II, Groups E, F, and G.
8 CSA recognized to CSA Standards C22.2 number 0 and number 129.
9 FM Approved
General Notes:
FM does not allow 110V/50 HZ or 120V/60 Hz solenoid power supplies for fire protection.
Overall take-out (end of inlet nipple to end of outlet nipple) = 2.95” (74,9 mm). All valves have ½” (15 mm) NPT connections.
Form No. F_113001 18.10.18 P65 Replaces Form No. F_113001 June 5, 2013
(Added P65 Warning.)
Page 2 of 4
HIGH PRESSURE
TECHNICAL DATA SOLENOID VALVE
RATED TO 300 PSI (21 BAR)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@[Link]
2. TECHNICAL DATA Viking Technical Data may be found on
Specifications The Viking Corporation’s Web site at
Body: Brass with ½” (15 mm) NPT connections [Link]
Coil: Class F, Continuous Duty The Web site may include a more recent
edition of this Technical Data Page.
Maximum Operating Pressure: 300 psi (20.7 bar)
Minimum Operating Pressure: 5 psi (.34 bar)
See Table 1 for enclosure descriptions and recommended ambient temperatures.
Material Standards
Seals and Discs: Viton
Tube Sleeve: 303 Stainless Steel
Pilot Guide: 303 Stainless Steel
Pilot Orifice: 303 Stainless Steel
Piston: 303 Stainless Steel
Plunger: 430 Stainless Steel
Spring: 18-8 Stainless Steel
Ordering Information
Part Number: See Table 1
Manufacturer: Parker Hannifin Corp. Skinner Valve division
3. LISTINGS AND APPROVALS (See Table 1 for specific model approvals)
UL Listed - VLTR
FM Approved
CE Approved
ATEX Certified - LCIE 02 A
CSA - Standard C22.2
4. INSTALLATION
1. Check nameplate for correct unit, including voltage and mode of operation. Follow all installation and maintenance instructions
enclosed with the valve.
2. Standard solenoids may be mounted in any position. However, for optimum life and performance, solenoids should be mounted
vertically and upright with the coil upright.
3. A 50 mesh strainer is required on the inlet side of the valve at the priming line connection. This strainer is included as part of the
Model E-1 Deluge Valve Trim. Install the strainer as indicated on Viking’s trim drawing. Install the solenoid according to markings
on the valve body. Apply pipe-joint compound sparingly to male pipe threads only. If applied to valve threads, it may enter the
valve and cause operation difficulty or leakage. Avoid putting pipe compound on first two male threads as well.
4. The unit must be wired in accordance with local and national electrical codes. For valves equipped with water tight enclosures,
the electrical fittings must be approved for use in the hazardous location.
5. Upon completing the installation, the entire system must be tested for proper operation. See system description and testing
instructions for additional information.
5. OPERATION
The solenoid valve is an internal pilot operated valve with pilot and bleed orifices utilizing line pressure for operation. Normally closed,
de-energized valves open when energized. Power is applied to the solenoid coil, causing the solenoid core to lift, opening the pilot
orifice to the outlet side of the valve. This relieves pressure on the top side of the diaphragm and allows the line pressure to open the
valve. When de-energized, the solenoid core reseals the pilot orifice, allowing the line pressure to build above the diaphragm, closing
the valve.
Normally closed solenoid valves are commonly used as releases for Viking deluge and flow control valves. Opening the solenoid valve
allows the deluge or flow control valve to open.
Note: When using a normally closed solenoid valve as a release, a system will not operate automatically on total loss of power. For this
reason, it is recommended and normally required that an emergency back-up, supervised power supply be provided to maintain fire
protection during interruptions of the main power system and to meet the requirements of appropriate Authorities Having Jurisdiction.
Form No. F_113001 18.10.18 P65
Page 3 of 4
HIGH PRESSURE
TECHNICAL DATA SOLENOID VALVE
RATED TO 300 PSI (21 BAR)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@[Link]
6. INSPECTIONS, TESTS AND MAINTENANCE
WARNING: THE OWNER IS RESPONSIBLE FOR MAINTAINING THE FIRE PROTECTION SYSTEM IN PROPER OPERATING CONDI-
TION. ANY SYSTEM MAINTENANCE OR TESTING THAT INVOLVES PLACING A CONTROL VALVE OR DETECTION SYSTEM OUT OF
SERVICE MAY ELIMINATE THE FIRE PROTECTION OF THAT SYSTEM. PRIOR TO PROCEEDING, NOTIFY ALL AUTHORITIES HAVING
JURISDICTION. CONSIDERATION SHOULD BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN THE AFFECTED AREA.
WARNING: PRIOR TO OPERATING THE SOLENOID VALVE, BE SURE TO CLOSE THE SYSTEM CONTROL VALVE TO AVOID UNIN-
TENTIONAL OPERATION OF THE DELUGE VALVE.
1. Inspections: It is imperative that the system be inspected and tested in accordance with NFPA 25 on a regular basis. The fre-
quency of the inspections may vary due to contaminated water supplies, corrosive water supplies, or corrosive atmospheres.
In addition, the alarm devices, detection systems, or other connected trim may require a more frequent schedule. Refer to the
system description and applicable codes for minimum requirements.
2. The valve must be operated at least monthly. The valve must open and close freely. When open, the water flow must be clear
and clean at the proper flow rate. When closed, a total water shut-off must be observed. After the test, the strainer must be
cleaned. Prior to cleaning the strainer, the priming line valve must be closed and the priming line depressurized. After the strainer
is cleaned, the priming line valve must be reopened.
3. The valve must be inspected at least monthly for cracks, corrosion, leakage, etc., and cleaned, repaired, or replaced as neces-
sary.
4. At least annually, the valve diaphragms and seats must be inspected and if necessary, repaired or replaced.
WARNING: CLOSE SYSTEM CONTROL VALVE, TURN OFF POWER SUPPLY, AND DEPRESSURIZE VALVE BEFORE DISASSEM-
BLING VALVE. IT IS NOT NECESSARY TO REMOVE THE VALVE FROM THE PIPE LINE TO MAKE INSPECTIONS.
5. When lubricating valve components, use a high grade silicone grease (Dow Corning® 111 Compound Lubricant or equal).
6. When reassembling, tighten parts to torque values indicated in Parker’s maintenance instructions (packed with valve).
7. After maintenance is completed, operate the valve a few times to be sure of proper operation. A metallic “click” signifies the so-
lenoid is operating.
8. It is recommended that the valve be replaced at seven-year intervals. Shorter intervals may be required if the valve is subject to
corrosive water supplies or atmospheres.
9. All service must be performed by qualified personnel. Upon completion of inspections or replacement of the valve, the entire
system must be checked for proper operation. See appropriate system description and testing instructions for additional informa-
tion.
7. AVAILABILITY
The Viking Solenoid Valve is available through a network of domestic and international distributors. See the Viking Corp. Web site for
closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
Form No. F_113001 18.10.18 P65
Page 4 of 4
HIGH PRESSURE
TECHNICAL DATA SOLENOID VALVE
RATED TO 300 PSI (21 BAR)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@[Link]
Figure 1 - Dimensions are the same for all models
Form No. F_113001 18.10.18 P65 Replaces Form No. F_113001 June 5, 2013
(Added P65 Warning.)