4577 - Carrier 30 XA 352
4577 - Carrier 30 XA 352
50 Hz
1 - INTRODUCTION...................................................................................................................................................................... 4
1.1 - Installation safety considerations........................................................................................................................................... .4
1.2 - Equipment and components under pressure........................................................................................................................ .4
1.3 - Maintenance safety considerations........................................................................................................................................ .5
1.4 - Repair safety considerations................................................................................................................................................... .5
2 - Preliminary checks....................................................................................................................................................... 6
2.1 - Check equipment received...................................................................................................................................................... .6
2.2 - Moving and siting the unit....................................................................................................................................................... .7
3 - dimensions, clearances.............................................................................................................................................. 8
3.1 - 30XA 252-352 (standard) and 252-302 (option 254/255)..................................................................................................... .8
3.2 - 30XA 402-452 (standard) and 352-452 (option 254/255)..................................................................................................... .8
3.3 - 30XA 502 (standard and option 254/255).............................................................................................................................. .9
3.4 - 30XA 602-802 (standard) and 602-702 (option 254/255)..................................................................................................... .9
3.5 - 30XA 852-902 (standard) and 752-852 (option 254/255)................................................................................................... .10
3.6 - 30XA 1002 (standard) and 902-1002 (option 254/255)...................................................................................................... .10
3.7 - 30XA 1102-1352 (standard and option 254/255)................................................................................................................ .11
3.8 - 30XA 1402-1502 module 1 (standard and option 254/255)............................................................................................... .11
3.9 - 30XA 1402-1502 module 2 (standard and option 254/255)............................................................................................... .12
3.10 - 30XA 1702 module 1 (standard and option 254/255)...................................................................................................... .12
3.11 - 30XA 1702 module 2 (standard and option 254/255)...................................................................................................... .13
3.12 - Multiple chiller installation................................................................................................................................................. .13
4 - Physical and electrical data for 30XA units......................................................................................... 14
4.1 - Physical data 30XA - Standard units and option 119***................................................................................................... .14
4.2 - Physical data 30XA - Units with option 254 and 255***................................................................................................... .15
4.3 - Sound levels............................................................................................................................................................................ .15
4.4 - Short-circuit stability current for all units........................................................................................................................... .16
4.5 - Electrical data 30XA - Standard unit (including option 81)............................................................................................. .16
4.6 - Electrical data 30XA - Option 119 (including option 81)................................................................................................. .17
4.7 - Electrical data 30XA - Option 254/255 (including option 81).......................................................................................... .18
4.8 - Electrical data 30XA - Option 254/255 with option 119 (including option 81).............................................................. .19
4.9 - Compressor electrical data.................................................................................................................................................... .20
4.10 - Compressor usage per circuit (A, B, C, D)........................................................................................................................ .20
4.11 - Electrical data, optional hydronic module........................................................................................................................ .20
5 - ELECTRICAL CONNECTION............................................................................................................................................. 21
5.1 - Power supply........................................................................................................................................................................... .21
5.2 - Voltage phase imbalance (%)............................................................................................................................................... .21
5.3 - Power connection/disconnect switch.................................................................................................................................... .21
5.4 - Recommended wire sections................................................................................................................................................ .22
5.5 - Power cable entry................................................................................................................................................................... .22
5.6 - Field control wiring................................................................................................................................................................ .22
6 - Application data............................................................................................................................................................ 23
6.1 - Operating limits...................................................................................................................................................................... .23
6.2 - Minimum chilled water flow (units without hydronic module)........................................................................................ .23
6.3 - Maximum chilled water flow (units without hydronic module)....................................................................................... .23
6.4 - Variable flow evaporator....................................................................................................................................................... .24
6.5 - System minimum water volume........................................................................................................................................... .24
6.6 - Maximum system water volume........................................................................................................................................... .24
6.7 - Evaporator water flow rate................................................................................................................................................... .24
6.8 - Evaporator pressure drop curve........................................................................................................................................... .25
7 - WATER CONNECTIONS....................................................................................................................................................... 26
7.1 - Operating precautions........................................................................................................................................................... .26
7.2 - Victaulic water connections................................................................................................................................................... .27
7.3 - Flow control............................................................................................................................................................................ .28
7.4 - Evaporator water box bolt tightening................................................................................................................................. .28
7.5 - Frost protection...................................................................................................................................................................... .28
7.6 - Operation of two units in master/slave mode..................................................................................................................... .29
7.7 - Pump pressure/flow rate curves............................................................................................................................................ .30
7.8 - Available static system pressure (optional hydronic module).......................................................................................... .30
8 - FREE-COOLING OPTION.................................................................................................................................................... 31
8.1 - Characteristics........................................................................................................................................................................ .31
8.2 - Operating limits...................................................................................................................................................................... .31
8.3 - Operation................................................................................................................................................................................ .31
9 - Heat reclaim condenser option....................................................................................................................... 32
9.1 - Technical data, 30XA units with heat reclaim condenser option...................................................................................... .32
9.2 - Dimensions, clearances.......................................................................................................................................................... .32
9.3 - Condenser location................................................................................................................................................................ .36
9.4 - Condenser water connections............................................................................................................................................... .36
9.5 - Operating limits for stable operation (no mode changeover).......................................................................................... .36
9.6 - Operating limits for changeover between modes . ............................................................................................................ .36
9.7 - Flow control............................................................................................................................................................................ .37
9.8 - Heat reclaim operation.......................................................................................................................................................... .37
9.9 - Condenser pump selection.................................................................................................................................................... .37
9.10 - Frost protection.................................................................................................................................................................... .37
10 - Major system components and operation data.................................................................................. 38
10.1 - Direct-drive twin-screw compressor with variable capacity slide valve........................................................................ .38
10.2 - Pressure vessels.................................................................................................................................................................... .38
10.3 - High-pressure safety switch................................................................................................................................................ .39
10.4 - Condensers............................................................................................................................................................................ .39
10.5 - Fans........................................................................................................................................................................................ .39
10.6 - Electronic expansion valve (EXV).................................................................................................................................... .39
10.7 - Moisture indicator................................................................................................................................................................ .39
10.8 - Filter drier............................................................................................................................................................................. .39
10.9 - Sensors................................................................................................................................................................................... .39
11 - Options and accessories......................................................................................................................................... 41
12 - STANDARD MAINTENANCE........................................................................................................................................... 42
12.1 - Level 1 maintenance (see note).......................................................................................................................................... .42
12.2 - Level 2 maintenance (see note).......................................................................................................................................... .42
12.3 - Level 3 (or higher) maintenance (see note)...................................................................................................................... .42
12.4 - Tightening torques for the main electrical connections................................................................................................... .42
12.5 - Tightening torques for the main bolts and screws............................................................................................................ .43
12.6 - Condenser coil...................................................................................................................................................................... .43
12.7 - Evaporator maintenance..................................................................................................................................................... .43
12.8 - Compressor maintenance.................................................................................................................................................... .44
12.9 - Precaution for compresssor power supply bus bar connection...................................................................................... .44
13 - start-up cHecklist for 30XA Liquid chillers (use for job file)................................................ 45
The cover photograph is for illustrative purposes only and is not part of any offer for sale or contract.
1 - INTRODUCTION Safety is only guaranteed, if these instructions are carefully
followed. If this is not the case, there is a risk of material
The 30XA Aquaforce units are designed to cool water for deterioration and injuries to personnel.
the air conditioning of buildings and industrial procsses.
Never cover any safety devices.
Prior to the initial start-up of the 30XA units, the people
involved in the on-site installation, start-up, operation, and This applies to the relief valve in the water circuit and the
maintenance of this unit should be thoroughly familiar with relief valve(s) in the refrigerant circuit(s).
these instructions and the specific project data for the
installation site. Ensure that the valves are correctly installed, before
operating the unit.
The 30XA liquid chillers are designed to provide a very high
level of safety during installation, start-up, operation and In certain cases the relief valves are installed on isolating
maintenance. They will provide safe and reliable service valves. These valves are factory-supplied lead-sealed in the
when operated within their application range. open position. This system permits isolation and removal
of the relief valves for checking and replacing. The relief
This manual provides the necessary information to fami- valves are designed and installed to ensure protection
liarize yourself with the control system before performing against overpressure caused by fire.
start-up procedures. The procedures in this manual are
arranged in the sequence required for machine installation, The relief valve must only be removed when the fire risk
start-up, operation and maintenance. is fully controlled and this is the responsibility of the
operator.
Always ensure that all required safety measures are followed,
including those in this document, such as: wearing protec- All factory-installed relief valves are lead-sealed to prevent
tive clothing (gloves, shoes) and safety glasses, using appro- any calibration change. If the relief valves are installed
priate tools, employing qualified and skilled technicians on a change-over manifold, this is equipped with a relief
(electricians, refrigeration engineers) and following local valve on each of the two outlets. Only one of the two relief
regulations. These units comply with the requirements of valves is in operation, the other one is isolated. Never
the European machine safety, electromagnetic compatibility, leave the change-over valve in the intermediate position,
pressurised equipment and low voltage directives. i.e. with both ways open (locate the control element in the
stop position). If a relief valve is removed for checking or
1.1 - Installation safety considerations replacement please ensure that there is always an active
relief valve on each of the change-over valves installed in
Access to the unit must be reserved to authorised personnel, the unit.
qualified and trained in monitoring and maintenance. The
access limitation device must be installed by the customer If the unit is installed in a room, the safety valves must be
(e.g. cut-off, enclosure). connected to discharge pipes. These pipes must be installed
in a way that ensures that people and property are not
After the unit has been received, when it is ready to be exposed to refrigerant leaks. These fluids may be diffused
installed or reinstalled, and before it is started up, it must be in the air, but far away from any building air intake, or
inspected for damage. Check that the refrigerant circuit(s) they must be discharged in a quantity that is appropriate
is (are) intact, especially that no components or pipes have for a suitably absorbing environment.
shifted (e.g. follow-ing a shock). If in doubt, carry out a leak
tightness check and verify with the manufacturer that the Periodic check of the relief valves: See paragraph
circuit integrity has not been impaired. If damage is detected “Maintenance safety considerations”.
upon receipt, immediately file a claim with the shipping
company. Provide a drain in the discharge circuit, close to each
relief valve, to avoid an accumulation of condensate or
Carrier strongly recommends employing a specialised rain water.
company to unload the machine.
Ensure good ventilation, as accumulation of refrigerant
Do not remove the skid or the packaging until the unit is in an enclosed space can displace oxygen and cause
in its final position. These units can be moved with a fork asphyxiation or explosions.
lift truck, as long as the forks are positioned in the right
place and direction on the unit. Inhalation of high concentrations of vapour is harmful
and may cause heart irregularities, unconsciousness, or
The units can also be lifted with slings, using only the death. Vapour is heavier than air and reduces the amount
designated lifting points marked on the unit. of oxygen available for breathing. These products cause
eye and skin irritation. Decomposition products are
These units are not designed to be lifted from above. Use hazardous.
slings with the correct capacity, and always follow the
lifting instructions on the certified drawings supplied 1.2 - Equipment and components under pressure
with the unit.
See section “10.2 - Pressure vessels”.
1.3 - Maintenance safety considerations At least once a year thoroughly inspect the protection
devices (valves). If the machine operates in a corrosive
Engineers working on the electric or refrigeration compo- environment, inspect the protection devices more frequently.
nents must be authorized, trained and fully qualified to do so.
Regularly carry out leak tests and immediately repair
All refrigerant circuit repairs must be carried out by a trained any leaks.
person, fully qualified to work on these units. He must have
been trained and be familiar with the equipment and the Ensure regularly that the vibration levels remain accep-
installation. All welding operations must be carried out by table and close to those at the initial unit start-up.
qualified specialists.
Before opening a refrigerant circuit, purge and consult the
Any manipulation (opening or closing) of a shut-off pressure gauges.
valve must be carried out by a qualified and authorised
engineer. These procedures must be carried out with the Change the refrigerant when there are equipment failures,
unit shut-down. following a procedure such as the one described in NFE
29-795 or carry out a refrigerant analysis in a specialist
NOTE: The unit must never be left shut down with the laboratory.
liquid line valve closed, as liquid refrigerant can be trapped
between this valve and the expansion device. (This valve Plug all openings whenever the refrigerant circuit is opened
is situated on the liquid line before the filter drier box.) for up to one day. For longer openings place a nitrogen
charge in the circuit.
During any handling, maintenance and service operations
the engineers working on the unit must be equipped with 1.4 - Repair safety considerations
safety gloves, glasses, shoes and protective clothing.
All installation parts must be maintained by the personnel in
Never work on a unit that is still energized. charge, in order to avoid material deterioration and injuries
to people. Faults and leaks must be repaired immediately.
Never work on any of the electrical components, until the The authorized technician must have the responsibility to
general power supply to the unit has been cut using the repair the fault immediately. Each time repairs have been
disconnect switch(es) in the control box(es). carried out to the unit, the operation of the safety devices
must be re-checked.
If any maintenance operations are carried out on the unit,
lock the power supply circuit in the open position ahead Comply with the regulations and recommendations in unit
of the machine. and HVAC installation safety standards, such as: EN 378,
ISO 5149, etc.
If the work is interrupted, always ensure that all circuits
are still deenergized before resuming the work. If a leak occurs or if the refrigerant becomes contaminated
(e.g. by a short circuit in a motor) remove the complete
ATTENTION: Even if the unit has been switched off, the charge using a recovery unit and store the refrigerant in
power circuit remains energized, unless the unit or circuit mobile containers.
disconnect switch is open. Refer to the wiring diagram for
further details. Attach appropriate safety labels. Repair the leak detected and recharge the circuit with the
total R134a charge, as indicated on the unit name plate.
Operating checks: During the life-time of the system, Certain parts of the circuit can be isolated. Only charge
inspection and tests must be carried out in accordance liquid refrigerant R134a at the liquid line.
with national regulations.
Ensure that you are using the correct refrigerant type
The information on operating inspections given in annex before recharging the unit.
C of standard EN278-2 can be used if no similar criteria
exist in the national regulations. Charging any refrigerant other than the original charge
type (R134a) will impair machine operation and can even
While working in the fan area, especially when grilles or lead to a destruction of the compressors. The compressors
casings are removed, disconnect the fan power supply to operating with this refrigerant type are lubricated with a
prevent their automatic restart. synthetic polyolester oil.
Safety device checks (annex C6 – EN378-2): The safety Do not use oxygen to purge lines or to pressurize a machine
devices must be checked on site once a year for safety for any purpose. Oxygen gas reacts violently with oil,
devices (high-pressure switches), and every five years for grease, and other common substances.
external overpressure devices (pressure relief valves).
Never exceed the specified maximum operating pressures.
Check manual “30XA Pro-Dialog Control” for a detailed Verify the allowable maximum high- and low-side test
explanation of the high-pressure switch test method. pressures by checking the instructions in this manual and
the pressures given on the unit name plate.
Do not use air for leak testing. Use only refrigerant or dry The refrigerant lines can break under the weight and
nitrogen. release refrigerant, causing personal injury.
Do not unweld or flamecut the refrigerant lines or any Do not climb on a machine. Use a platform, or staging to
refrigerant circuit component until all refrigerant (liquid work at higher levels.
and vapour) has been removed from chiller. Traces of
vapour should be displaced with dry air nitrogen. Refrige- Use mechanical lifting equipment (crane, hoist, winch, etc.)
rant in contact with an open flame produces toxic gases. to lift or move heavy components. For lighter components,
use lifting equipment when there is a risk of slipping or
The necessary protection equipment must be available, losing your balance.
and appropriate fire extinguishers for the system and the
Use only original replacement parts for any repair or com-
refrigerant type used must be within easy reach.
ponent replacement. Consult the list of replacement parts
that corresponds to the specification of the original equip-
Do not siphon refrigerant.
ment.
Avoid spilling liquid refrigerant on skin or splashing it Do not drain water circuits containing industrial brines,
into the eyes. Use safety goggles. Wash any spills from the without informing the technical service department at the
skin with soap and water. If liquid refrigerant enters the installation site or a competent body first.
eyes, immediately and abundantly flush the eyes with
water and consult a doctor. Close the entering and leaving water shutoff valves and
purge the unit water circuit, before working on the compo-
Never apply an open flame or live steam to a refrigerant nents installed on the circuit (screen filter, pump, water
container. Dangerous overpressure can result. If it is flow switch, etc.).
necessary to heat refrigerant, use only warm water.
Do not loosen the water box bolts until the water boxes
During refrigerant removal and storage operations follow have been completely drained.
applicable regulations. These regulations, permitting condi-
tioning and recovery of halogenated hydrocarbons under Periodically inspect all valves, fittings and pipes of the
optimum quality conditions for the products and optimum refrigerant and hydronic circuits to ensure that they do
safety conditions for people, property and the environment not show any corrosion or any signs of leaks.
are described in standard NFE 29795.
It is recommended to wear ear defenders, when working
Any refrigerant transfer and recovery operations must be near the unit and the unit is in operation.
carried out using a transfer unit. A 3/8” SAE connector on
the manual liquid line valve is supplied with all units for 2 - Preliminary checks
connection to the transfer station. The units must never be
modified to add refrigerant and oil charging, removal and 2.1 - Check equipment received
purging devices. All these devices are provided with the
units. Please refer to the certified dimensional drawings for • Inspect the unit for damage or missing parts. If damage
the units. is detected, or if shipment is incomplete, immediately
file a claim with the shipping company.
Do not re-use disposable (non-returnable) cylinders or • Confirm that the unit received is the one ordered.
attempt to refill them. It is dangerous and illegal. When Compare the name plate data with the order.
cylinders are empty, evacuate the remaining gas pressure, • The unit name plate must include the following
and move the cylinders to a place designated for their information:
recovery. Do not incinerate. - Version number
- Model number
Do not attempt to remove refrigerant circuit components - CE marking
or fittings, while the machine is under pressure or while it - Serial number
is running. Be sure pressure is at 0 kPa before removing - Year of manufacture and test date
components or opening a circuit. - Refrigerant used and refrigerant class
- Refrigerant charge per circuit
Do not attempt to repair or recondition any safety devices - Containment fluid to be used
when corrosion or build-up of foreign material (rust, dirt, - PS: Min./max. allowable pressure (high and low
scale, etc.) is found within the valve body or mechanism. pressure side)
If necessary, replace the device. Do not install safety valves - TS: Min./max. allowable temperature (high and
in series or backwards. low pressure side)
- Relief valve set pressure
ATTENTION: No part of the unit must use feet, racks or - Pressure switch cut-out pressure
supports during operation. Periodically monitor and - Unit leak test pressure
repair or if necessary replace any component or piping - Voltage, frequency, number of phases
that shows signs of damage. - Maximum current drawn
- Maximum power input
- Unit net weight
• Confirm that all accessories ordered for on-site WARNING: Never push or lever on any of the enclosure
installation have been delivered, and are complete panels of the unit. Only the base of the unit frame is
and undamaged. designed to withstand such stresses.
The unit must be checked periodically during its whole Checks before system start-up
operating life to ensure that no shocks (handling accessories, Before the start-up of the refrigeration system, the complete
tools etc.) have damaged it. If necessary, the damaged parts installation, including the refrigeration system must be veri-
must be repaired or replaced. See also chapter “Mainte- fied against the installation drawings, dimensional drawings,
nance”. system piping and instrumentation diagrams and the wiring
diagrams.
2.2 - Moving and siting the unit
During the installation test national regulations must be
2.2.1 - Moving followed. If no national regulation exists, paragraph 9-5 of
standard EN 378-2 can be used as a guide.
See chapter 1.1 “Installation safety considerations”.
External visual installation checks:
2.2.2 - Siting the unit • Compare the complete installation with the refrigeration
system and power circuit diagrams.
Always refer to the chapter “Dimensions and clearances” • Check that all components comply with the design
to confirm that there is adequate space for all connections specifications.
and service operations. For the centre of gravity coordinates, • Check that all safety documents and equipments that
the position of the unit mounting holes, and the weight are required by current European standards are present.
distribution points, refer to the certified dimensional • Verify that all safety and environmental protection
drawing supplied with the unit. devices and arrangements are in place and comply
with the current European standard.
The support points under the chassis must have at least the • Verify that all relevant documents for pressure vessels
size of the chassis opening at the lifting point (minimum (certificates, name plates, files, instruction manuals etc.)
220 x 180 mm) in order to prevent a deformation of the required by the current European standards are present.
chassis. • Verify the free passage of access and safety routes.
• Check that ventilation in the plant room is adequate.
Typical applications of these units are in refrigeration • Check that refrigerant detectors are present.
systems, and they do not require earthquake resistance. • Verify the instructions and directives to prevent the
Earthquake resistance has not been verified. deliberate removal of refrigerant gases that are harmful
to the environment.
CAUTION: Only use slings at the designated lifting • Verify the installation of connections.
points which are marked on the unit. • Verify the supports and fixing elements (materials,
routing and connection).
Before siting the unit check that: • Verify the quality of welds and other joints.
• the permitted loading at the site is adequate or that • Check the protection against mechanical damage.
appropriate strenghtening measures have been taken. • Check the protection against heat.
• the unit is installed level on an even surface (maximum • Check the protection of moving parts.
tolerance is 5 mm in both axes). • Verify the accessibility for maintenance or repair and
• there is adequate space above the unit for air flow and to check the piping.
to ensure access to the components. • Verify the status of the valves.
• the number of support points is adequate and that they • Verify the quality of the thermal insulation and of the
are in the right places. vapour barriers.
• the location is not subject to flooding.
• for outdoor installations, where heavy snowfall is likely
and long periods of sub-zero temperatures are normal,
provision has to be made to prevent snow accumulating
by raising the unit above the height of drifts normally
experienced. Baffles may be necessary to deflect strong
winds. They must not restrict air flow into the unit.
3 - dimensions, clearances
1 1
1 1
3.3 - 30XA 502 (standard and option 254/255)
2
1 1
1 1
3.5 - 30XA 852-902 (standard) and 752-852 (option 254/255)
2
1 1
1 1
10
3.7 - 30XA 1102-1352 (standard and option 254/255)
1 1
1
Module 2
11
3.9 - 30XA 1402-1502 module 2 (standard and option 254/255)
Module 1
2
Module 2
12
3.11 - 30XA 1702 module 2 (standard and option 254/255)
Module 1
A A
2200
2200
B B B
2200
2200
B B B
2200
1500 1500
B
2200
Legend
B A Wall
B Units
1500
13
4 - Physical and electrical data for 30XA units
Note:
Unit sizes 30XA 1402 to 1702 are supplied in two field-assembled modules.
14
4.2 - Physical data 30XA - Units with option 254 and 255***
30XA 252 302 352 402 452 502 602 702 752 802 852 902 1002 1102 1202 1302 1352 1402 1502 1702
Nominal cooling capacity*
Option 254 kW 271 295 322 387 438 493 600 659 708 766 809 870 967 1119 1218 1299 1399 1433 1484 1619
Option 255 kW 268 293 319 383 434 488 594 652 701 758 801 861 957 1108 1205 1286 1385 1419 1469 1603
Nominal power input*
Option 254‡ kW 88 99 104 124 145 160 198 212 236 258 270 303 327 370 413 453 513 479 497 539
Option 255‡ kW 90 101 106 127 148 163 202 217 241 263 277 310 335 378 422 464 527 489 509 552
Operating weight** kg 4160 4190 4710 5190 5260 5830 6870 7030 7820 8140 8260 9010 9260 11470 11890 12250 12640 9180/ 9340/ 8270/
4650 4650 8270
Refrigerant R-134a
Circuit A kg 60 64 70 85 85 102 102 100 129 112 130 129 140 102 112 112 112 140 140 130
Circuit B kg 64 64 56 56 56 56 88 95 88 95 95 103 129 92 92 92 98 103 129 95
Circuit C kg - - - - - - - - - - - - - 135 135 135 122 135 135 130
Circuit D kg - - - - - - - - - - - - - - - - - - - 95
Compressors 06T semi-hermetic screw compressors, 50 r/s
Circuit A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Circuit B 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Circuit C - - - - - - - - - - - - - 1 1 1 1 1 1 1
Circuit D - - - - - - - - - - - - - - - - - - - 1
Minimum capacity % 15 15 15 15 15 15 15 15 15 15 15 15 15 10 10 10 10 10 10 8
Control PRO-DIALOG, electronic expansion valve (EXV)
Condensers All aluminium micro-channel heat exchanger
Condenser fans Axial Flying Bird 4 fans with rotating shroud
Quantity 6 6 7 8 8 9 11 12 13 13 14 15 16 19 20 20 20 24 24 28
Total air flow l/s 20500 20500 20500 27333 27333 30750 37583 41000 41000 41000 47833 47833 54667 64917 68333 68333 68333 82000 82000 95667
Fan speed r/s 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7
Evaporator Flooded multi-pipe type
Water content l 58 61 61 66 70 77 79 94 98 119 119 130 140 168 182 203 224 230 240 240
Maximum pressure**** kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
* Nominal conditions: evaporator entering/leaving water temperature = 12°C/7°C. Outdoor air temperature = 35°C, evaporator fouling factor = 0.000018 m2 K/W
** Weights are guidelines only. Weight and diameters of connection modules 1 and 2 for sizes 1402 to 1702. The refrigerant charge is also given on the unit nameplate.
*** Option 254 = Units with copper/aluminium coils
Option 255 = Units with copper/aluminium coils without slots
**** Max. water-side operating pressure without hydronic module
‡ Data is not contractually binding and for information only. The values are rounded.
Notes:
Unit sizes 30XA 1402 to 1702 are supplied in two field-assembled modules.
Option 119 (high energy efficiency) can be used together with options 254 and 255. Contact your Carrier representative to obtain the performances.
30XA 252 302 352 402 452 502 602 702 752 802 852 902 1002 1102 1202 1302 1352 1402 1502 1702
Standard unit
Sound power level* dB(A) 89 89 89 92 93 93 94 93 95 95 94 96 95 96 96 96 97 97 97 97
Sound pressure level at 10 m** dB(A) 57 57 57 60 61 61 62 61 63 63 62 63 63 63 63 63 64 64 64 64
Standard unit + option 257
Sound power level* dB(A) 86 86 86 89 90 90 91 90 92 92 91 93 92 93 93 93 94 94 94 94
Sound pressure level at 10 m** dB(A) 54 54 54 57 58 58 59 57 60 59 58 60 59 60 60 60 61 61 61 61
High energy efficiency version (option 119)
Sound power level* dB(A) 94 94 94 95 95 95 96 96 98 98 98 99 98 99 100 99 100 101 100 101
Sound pressure level at 10 m** dB(A) 62 62 62 62 62 62 63 64 65 66 65 66 65 66 67 66 67 68 67 67
Unit with options 119 + 257
Sound power level* dB(A) 92 92 92 94 94 94 95 95 96 96 96 97 97 98 98 98 98 99 99 99
Sound pressure level at 10 m** dB(A) 60 60 60 62 62 62 62 62 63 63 63 64 64 65 65 65 62 66 66 65
* 10-12 W - In accordance with ISO 9614-1 and certified by Eurovent
** Average sound pressure level, unit in a free field on a reflective surface
15
4.4 - Short-circuit stability current for all units
30XA 252 302 352 402 452 502 602 702 752 802 852 902 1002 1102 1202 1302 1352 1402 1502 1702
Short-circuit stability current (TN system)*
Circuits A + B** kA 38 38 38 38 38 38 50 50 50 50 50 50 50 50 50 50 50 50 50 50
Circuits C + D** kA - - - - - - - - - - - - - 50 50 50 50 50 50 50
Units with option 81 A - - - - - - - - - - - - - 50 50 50 50 50 50 -
* Type of system earthing
** rms value
Note:
Motor and fan electrical data if the unit operates at Eurovent conditions (motor ambient temperature 50°C): 1.9 A
Start-up current: 8.4 A
Power input: 760 W
16
4.6 - Electrical data 30XA - Option 119 (including option 81)
30XA - option 119 252 302 352 402 452 502 602 702 752 802 852 902 1002 1102 1202 1302 1352 1402 1502 1702
Power circuit
Nominal power supply V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit 24 V via internal transformer
Maximum start-up current*
Circuit A+B A 274 274 292 407 510 510 583 616 782 812 815 905 954 583 782 812 901 905 954 815
Circuit C+D†† A - - - - - - - - - - - - - 587 587 587 587 587 587 815
Option 81 A - - - - - - - - - - - - - 1010 1099 1175 1265 1275 1321 -
Nominal start-up current**
Circuit A+B A 246 246 261 379 479 479 535 561 734 757 760 845 860 535 734 757 846 845 860 760
Circuit C+D†† A - - - - - - - - - - - - - 587 587 587 587 587 587 760
Option 81 A - - - - - - - - - - - - - 907 991 1026 1124 1122 1133 -
Cosine Phi maximum*** 0.88 0.87 0.87 0.88 0.88 0.88 0.88 0.88 0.86 0.86 0.86 0.85 0.86 0.88 0.86 0.87 0.85 0.85 0.86 0.86
Cosine Phi nominal**** 0.84 0.84 0.83 0.83 0.85 0.85 0.86 0.86 0.84 0.84 0.84 0.82 0.82 0.84 0.83 0.83 0.83 0.82 0.82 0.84
Maximum power input†
Circuit A+B kW 126 136 147 172 192 212 257 278 304 323 356 372 435 257 304 353 400 405 435 356
Circuit C+D†† kW - - - - - - - - - - - - - 217 217 217 216 217 217 356
Option 81 A - - - - - - - - - - - - - 475 522 570 615 622 652 712
Nominal unit current draw****
Circuit A+B A 151 167 182 210 237 264 320 346 404 427 446 516 546 320 404 439 537 535 546 446
Circuit C+D†† A - - - - - - - - - - - - - 273 273 273 275 273 273 446
Option 81 A - - - - - - - - - - - - - 593 678 712 812 808 820 893
Maximum unit current draw (Un)†
Circuit A+B A 208 226 243 284 316 350 423 457 512 542 596 635 734 423 512 588 678 688 734 596
Circuit C+D†† A - - - - - - - - - - - - - 367 367 367 364 367 367 596
Option 81 A - - - - - - - - - - - - - 790 879 956 1041 1056 1102 1191
Maximum unit current draw (Un -10%)***
Circuit A+B A 219 243 262 305 340 376 455 491 551 583 640 683 790 455 551 633 729 740 790 640
Circuit C+D†† A - - - - - - - - - - - - - 395 395 395 391 395 395 640
Option 81 A - - - - - - - - - - - - - 850 946 1028 1120 1135 1185 1281
* Instantaneous start-up current (operating current of the smallest compressor + fan current + locked rotor current in star connection of the largest compressor). Values
obtained at operation with maximum unit power input.
** Instantaneous start-up current (operating current of the smallest compressor + fan current + locked rotor current in star connection of the largest compressor). Values
obtained at standard Eurovent unit operating conditions: air 35°C, water 12/7°C
*** Values obtained at operation with maximum unit power input.
**** Values obtained at standard Eurovent unit operating conditions: air 35°C, water 12/7°C
† Values obtained at operation with maximum unit power input. Values given on the unit name plate
†† Circuit D - only for size 1702
Note:
Motor and fan electrical data if the unit operates at Eurovent conditions (motor ambient temperature 50°C): 3.6 A
Start-up current: 20 A
Power input: 1.65 kW
17
4.7 - Electrical data 30XA - Option 254/255 (including option 81)
Note:
Motor and fan electrical data if the unit operates at Eurovent conditions (motor ambient temperature 50°C): 1.9 A
Start-up current: 8.4 A
Power input: 760 W
18
4.8 - Electrical data 30XA - Option 254/255 with option 119 (including option 81)
Note:
Motor and fan electrical data if the unit operates at Eurovent conditions (motor ambient temperature 50°C): 3.6 A
Start-up current: 20 A
Power input: 1.65 kW
19
4.9 - Compressor electrical data
Legend
MHA - Maximum compressor operating current, limited by the unit (current given for maximum capacity at 360 V)
LRYA - Locked rotor current for star connection (connection during compressor start-up)
LRDA - Locked rotor current for delta connection
30XA
Compressor 252 302 352 402 452 502 602 702 752 802 852 902 1002 1102 1202 1302 1352 1402 1502 1702
06TSA155 AB B - B - - - - - - - - - - - - - - - -
06TSA186 - A AB - B B - - - - - - - - - - - - - -
06TTA266 - - - A - - - - - - - - - - - - - - - -
06TTA301 - - - - A - B - B - - - - B B - - - - -
06TTA356 - - - - - A A AB - B B - - A - B - - - BD
06TUA483 - - - - - - - - A A - AB - - A - B B - -
06TUA554 - - - - - - - - - - A - AB C C AC AC AC ABC AC
20
5 - ELECTRICAL CONNECTION Calculate the maximum deviation from the 400 V average:
(AB) = 406 - 400 = 6
Please refer to the certified dimensional drawings, supplied (BC) = 400 - 399 = 1
with the unit. (CA) = 400 - 394 = 6
Motor
5.1 - Power supply
The maximum deviation from the average is 6 V. The
The power supply must conform to the specification on the greatest percentage deviation is:
chiller nameplate. The supply voltage must be within the
range specified in the electrical data table. For connections 100 x 6/400 = 1.5 %
refer to the wiring diagrams and the certified dimensional
drawings. This is less than the permissible 2% and is therefore
acceptable.
WARNING: Operation of the chiller with an improper
supply voltage or excessive phase imbalance constitutes 5.3 - Power connection/disconnect switch
abuse which will invalidate the Carrier warranty. If the
phase imbalance exceeds 2% for voltage, or 10% for Units Connection points
current, contact your local electricity supply at once and 30XA 0252-1002 1 per unit
ensure that the chiller is not switched on until corrective 30XA 1102-1702 1 for circuits A and B
measures have been taken. 1 for circuit(s) C (and D)
Example:
On a 400 V - 3 ph - 50 Hz supply, the individual phase
voltages were measured to be:
* The required protection level for this class is IP43BW (according to reference
document IEC 60529). All 30XA units are protected to IP44CW and fulfil this
protection condition.
21
5.4 - Recommended wire sections For 30XA unit sizes 602 to 1702 the control box that includes
the power supply cable connection terminal is located in
Wire sizing is the responsibility of the installer, and depends the lower part of the unit. In this case the control box is
on the characteristics and regulations applicable to each raised by 120 mm compared to the lowest point of the chassis.
installation site. The following is only to be used as a guide- The cable entry point depends on the unit configuration:
line, and does not make in any way liable. After wire sizing 1. Unit raised from the ground (e.g. installation on sup-
has been completed, using the certified dimensional drawing, port rails): It is recommended to enter the power cables
the installer must ensure easy connection and define any from below the control box. A removable aluminium
modifications necessary on site. plate below the control box allows introduction of the
cables.
The connections provided as standard for the field-supplied 2. Unit placed on the ground: For power cable entry from
power entry cables to the general disconnect/isolator switch below the control box ensure that the cable bend radius
are designed for the number and type of wires, listed in the is compatible with the connection space available in
table below. the control box. If not, an aluminium plate on the
control box face allows introduction of the cables.
The calculations are based on the maximum machine
current (see electrical data tables). For units with three circuits with option 81 (single power
connection point) the connection must be made from below
For the design the following standardised installation the unit.
methods are used, in accordance with IEC 60364, table 52C:
• For 30XA units installed outside the building: IMPORTANT: Check the cable bend radius for cable entry
No.17: suspended aerial lines into a control box, located in the lower part of the unit.
No. 61: buried conduit with a derating coefficient of 20.
Refer to the certified dimensional drawing for the unit.
The calculation is based on PVC or XLPE insulated cables
with copper core. The maximum temperature is 46°C for 5.6 - Field control wiring
30XA units.
Refer to the 30XA Pro-Dialog Controls IOM and the
The given wire length limits the voltage drop to < 5%. certified wiring diagram supplied with the unit for the field
control wiring of the following features:
IMPORTANT: Before connection of the main power • Evaporator pump interlock (mandatory)
cables (L1 - L2 - L3) on the terminal block, it is imperative • Remote on/off switch
to check the correct order of the 3 phases before proceeding • Demand limit external switch
to the connection on then terminal block or the main • Remote dual set point
disconnect/isolator switch. • Alarm, alert and operation report
• Evaporator pump control
5.5 - Power cable entry • Heat reclaim condenser pump control (option)
• Hot water valve control (option)
The power cables can enter the 30XA control box from • Set point reset via outside air temperature sensor reset
below or from the unit side. • Various interlocks on the Energy Management Module
(EMM) board (accessory or option)
Selection table of minimum and maximum wire sections for connection to 30XA units
Maximum wire Minimum calculated section Maximum calculated section
section
30XA Section (mm2) Section (mm2)* Max. length (m) Wire type Section (mm2)* Max. length (m) Wire type
252 2 x 240 1 x 95 190 XLPE Cu 2 x 95 410 PVC Cu
302 2 x 240 1 x 95 190 XLPE Cu 2 x 120 435 PVC Cu
352 2 x 240 1 x 120 197 XLPE Cu 2 x 150 455 PVC Cu
402 2 x 240 1 x 150 200 XLPE Cu 2 x 185 470 PVC Cu
452 2 x 240 1 x 185 205 XLPE Cu 2 x 120 435 XLPE Cu
502 2 x 240 1 x 240 205 XLPE Cu 2 x 150 455 XLPE Cu
602 4 x 240 2 x 95 190 XLPE Cu 2 x 240 480 XLPE Cu
702 4 x 240 2 x 120 198 XLPE Cu 2 x 240 480 XLPE Cu
752 4 x 240 2 x 120 198 XLPE Cu 3 x 240 600 XLPE Cu
802 4 x 240 2 x 150 200 XLPE Cu 3 x 240 600 XLPE Cu
852 4 x 240 2 x 150 200 XLPE Cu 4 x 240 685 XLPE Cu
902 6 x 240 2 x 185 205 XLPE Cu 4 x 240 685 XLPE Cu
1002 6 x 240 2 x 240 205 XLPE Cu 5 x 240 750 XLPE Cu
Circuits A and B/C
1102 4 x 240/2 x 240 2 x 95/1 x 240 190/280 XLPE Cu 4 x 240/2 x 240 685/480 PVC Cu/XLPE Cu
1202 4 x 240/2 x 240 2 x 150/1 x 240 280/280 XLPE Cu 4 x 240/2 x 240 685/480 XLPE Cu/XLPE Cu
1302 4 x 240/2 x 240 2 x 150/1 x 240 280/280 XLPE Cu 4 x 240/2 x 240 685/480 XLPE Cu/XLPE Cu
1352 6 x 240/2 x 240 2 x 185/1 x 240 280/280 XLPE Cu 5 x 240/2 x 240 750/480 XLPE Cu/XLPE Cu
1402 6 x 240/2 x 240 3 x 150/1 x 240 280/280 XLPE Cu 5 x 240/2 x 240 750/480 XLPE Cu/XLPE Cu
1502 6 x 240/2 x 240 3 x 150/1 x 240 280/280 XLPE Cu 6 x 240/2 x 240 750/480 XLPE Cu/XLPE Cu
1702 4 x 240/4 x 240 2 x 150/2 x 150 200/200 XLPE Cu 4 x 240/4 x 240 685/685 XLPE Cu
Option 81
1102-1502 8 x 240
* Power supply wire section (see diagram in chapter 5 ‘Electrical connection’).
Note: The current values used are given for a unit equipped with a hydronic kit operating at maximum current.
22
6 - Application data 6.2 - Minimum chilled water flow (units without
hydronic module)
6.1 - Operating limits
The minimum chilled water flow is shown in the table on
Evaporator fluid temperature the next page. If the system flow is less than this, the evapo-
°C Minimum Maximum
Water entering temperature at start-up - 45 rator flow can be recirculated, as shown in the diagram.
Water entering temperature during operation 6.8 21
Water leaving temperature during operation 3.3 15
For minimum chilled water flow rate
Note: If the leaving water temperature is below 4°C, a glycol/water solution or the
frost protection option must be used.
1
Condenser air temperature
°C Minimum Maximum
Storage -20 68
Operation, standard unit -10 55*
With winter operation option (option 28) -20 55*
With high energy efficiency option (option 119) -10 55*
Note: If the air temperature is below 0°C, a glycol/water solution or the frost 2
protection option must be used.
Legend
1 Evaporator
2 Recirculation
3.3
Evaporator leaving water temperature, °C
Legend:
Part load average: from 46°C for standard unit
from 50°C with option 119.
Legend
Operating range, standard unit. 1 Evaporator
2 Bypass
Below 0°C air temperature the unit must either be equipped with the
evaporator frost protection option (41A or 41B), or the water loop must be
protected against frost by using a frost protection solution (by the installer).
23
6.4 - Variable flow evaporator 6.6 - Maximum system water volume
Variable evaporator flow can be used in standard 30XA Units with hydronic module incorporate an expansion
chillers. The chillers maintain a constant leaving water tem- tank that limits the water volume. The table below gives
perature under all flow conditions. For this to happen, the the maximum loop volume for pure water or ethylene
minimum flow rate must be higher than the minimum flow glycol with various system concentrations, as well as the
given in the table of permissible flow rates and must not static pressures. If the maximum volume is insufficient,
vary by more than 10% per minute. compared to the minimum system water loop volume, an
additional expansion tank must be added to the system.
If the flow rate changes more rapidly, the system should
contain a minimum of 6.5 litres of water per kW instead of 30XA 252-452 502
3.25 l/kW. Static pressure bar 1 2 2.5 1 2 2.5
Maximum water loop volume l
Pure water 2400 1600 1200 3960 2640 1980
6.5 - System minimum water volume Ethylene glycol 10% 1800 1200 900 2940 1960 1470
Ethylene glycol 20% 1320 880 660 2100 1400 1050
Ethylene glycol 30% 1080 720 540 1740 1160 870
Whichever the system, the water loop minimum capacity is Ethylene glycol 40% 900 600 450 1500 1000 750
given by the formula:
* The maximum water flow rate corresponds to a pressure drop of 100 kPa.
Bad Good
Bad Good
24
6.8 - Evaporator pressure drop curve
100
252
302-352
3 402
5 6
452
3
5 502
Pressure drop, kPa
6 602
10
10 Water flow rate, l/s 50
100
702
752
3 802 - 852
4 902
5 1002
6 1102
7 1202
8 1302
2 3 4 5 6 7 8 9 10
9 1352 - 1402
10 1502 11
Pressure drop, kPa
11 1702
10
10 Water flow rate, l/s 100
25
7 - WATER CONNECTIONS Carrier recommendations on heat exchange fluids:
1. No NH4+ ammonium ions in the water, they are very
ATTENTION: Before carrying out any water connections detrimental for copper. This is one of the most impor-
install the water box purge plugs (one plug per water box tant factors for the operating life of copper piping. A
in the lower section - supplied in the control box). content of several tenths of mg/l will badly corrode the
copper over time.
For size and position of the heat exchanger water inlet and 2. Cl- Chloride ions are detrimental for copper with a risk
outlet connections refer to the certified dimensional drawings of perforations by corrosion by puncture. If possible
supplied with the unit. keep below 10 mg/l.
3. SO42- sulphate ions can cause perforating corrosion, if
The water pipes must not transmit any radial or axial force their content is above 30 mg/l.
to the heat exchangers nor any vibration. 4. No fluoride ions (<0.1 mg/l).
5. No Fe2+ and Fe3+ ions with non negligible levels of dis-
The water supply must be analysed and appropriate filtering, solved oxygen must be present. Dissolved iron < 5 mg/l
treatment, control devices, isolation and bleed valves and with dissolved oxygen < 5 mg/l.
circuits built in, to prevent corrosion, fouling and deteriora- 6. Dissolved silicon: silicon is an acid element of water
tion of the pump fittings. Consult either a water treatment and can also lead to corrosion risks. Content < 1 mg/l.
specialist or appropriate literature on the subject. 7. Water hardness: TH >5°F. Values between 10 and 25
can be recommended. This will facilitate scale deposit
7.1 - Operating precautions that can limit corrosion of copper. TH values that are
too high can cause piping blockage over time. A total
The water circuit should be designed to have the least num- alkalimetric titre (TAC) below 100 is desirable.
ber of elbows and horizontal pipe runs at different levels. 8. Dissolved oxygen: Any sudden change in water oxy-
Below the main points to be checked for the connection: genation conditions must be avoided. It is as detrimen-
• Comply with the water inlet and outlet connections tal to deoxygenate the water by mixing it with inert
shown on the unit. gas as it is to over-oxygenate it by mixing it with pure
• Install manual or automatic air purge valves at all oxygen. The disturbance of the oxygenation conditions
high points in the circuit(s). encourages destabilisation of copper hydroxides and
• Use an expansion device to maintain pressure in the enlargement of particles.
circuit(s) and install a safety valve as well as an expan- 9. Specific resistance – electric conductivity: the higher the
sion tank. specific resistance, the slower the corrosion tendency.
• Install thermometers in both the entering and leaving Values above 3000 Ohm/cm are desirable. A neutral
water connections. environment favours maximum specific resistance
• Install drain connections at all low points to allow the values. For electric conductivity values in the order of
whole circuit to be drained. 200-6000 S/cm can be recommended.
• Install stop valves, close to the entering and leaving 10. pH: Ideal case pH neutral at 20-25°C
water connections. 7 < pH < 8
• Use flexible connections to reduce the transmission of
vibrations. If the water circuit must be emptied for longer than one
• Insulate all pipework, after testing for leaks, both to month, the complete circuit must be placed under nitrogen
reduce heat gains and to prevent condensation. charge to avoid any risk of corrosion by differential aeration.
• Cover the insulation with a vapour barrier.
• Where there are particles in the fluid that could foul Charging and removing heat exchange fluids should be done
the heat exchanger, a screen filter should be installed with devices that must be included on the water circuit by
ahead of the pump. The mesh size of the filter must be the installer. Never use the unit heat exchangers to add
1.2 mm (see ‘Typical water circuit’ diagram on the right). heat exchange fluid.
• Before the system start-up verify that the water circuits
are connected to the appropriate heat exchangers (e.g.
no reversal between evaporator and condenser).
• Do not introduce any significant static or dynamic pres-
sure into the heat exchange circuit (with regard to the
design operating pressures).
• Before any start-up verify that the heat exchange fluid
is compatible with the materials and the water circuit
coating.
26
7.2 - Victaulic water connections
9
C D A 13
15
16 9 9
12 17 1
4 7
12 10
3
11
B
16 17 6
9
14
18
Legend
27
7.3 - Flow control 7.5 - Frost protection
Evaporator flow switch and chilled water pump interlock 7.5.1 - Standard machine
If the chiller or the water piping is in an area where the
IMPORTANT: On 30XA units, the unit water flow switch ambient temperature can fall below 0°C it is recommended
must be energised, and the chilled water pump interlock to add an antifreeze solution to protect the unit and the
must be connected. Failure to follow this instruction will water piping to a temperature of 10 K below the lowest
void the Carrier guarantee. temperature likely to be reached at the installation site.
Use only antifreeze solutions, approved for heat exchanger
The water flow switch is installed on the evaporator water duty. If the system is not protected by an antifreeze solution
inlet and adjusted by the control, based on unit size and and will not be used during the freezing weather conditions,
application. If adjustment is necessary, it must be carried draining of the cooler and outdoor piping is mandatory.
out by qualified personnel trained by Carrier Service. Damage due to freezing is not covered by the warranty.
Terminals 34 and 35 are provided for field installation of IMPORTANT: Depending on the climatic conditions in
the chilled water pump interlock (auxiliary contact for pump your area you must:
operation to be wired on site). • Add ethylene glycol with an adequate concentration
to protect the installation up to a temperature of 10 K
7.4 - Evaporator water box bolt tightening below the lowest temperature likely to occur at the
installation site.
The evaporator (and condenser) are of the shell and tube • If the unit is not used for an extended period, it is
type with removable water boxes to facilitate cleaning. Re- recommended to drain it, and as a safety precaution
tightening or tightening must be done in accordance with add ethylene glycol to the heat exchanger, using the
the illustration below. water entering purge valve connection (a purge connec-
tion is available somewhere on the heat exchanger
Water box tightening sequence water box in case the machine is not perfectly level).
• At the start of the next season, refill the unit with water
and add an inhibitor.
• For the installation of auxiliary equipment, the instal-
ler must comply with basic regulations, especially for
minimum and maximum flow rates, which must be
between the values listed in the operating limit table
(application data).
Legend
1 Sequence 1: 1 2 3 4
Sequence 2: 5 6 7 8
Sequence 3: 9 10 11 12
2 Tightening torque
Bolt size M16 - 171 - 210 Nm
28
7.6 - Operation of two units in master/slave mode 30XA with configuration: leaving water control
Each unit controls its own water pump. If there is only one
common pump, in cases with variable flow, isolation valves
Legend
must be installed on each unit. They will be activated at the
opening and closing by the control of each heat pump (in 1 Master unit
this case the valves are controlled using the dedicated water 2 Slave unit
pump outputs). See the 30XA Pro-Dialog Control IOM Control boxes of the master and slave units
for a more detailed explanation. Water inlet
Water outlet
Water pumps for each unit (included as standard for units with hydronic
module)
Additional sensors for leaving water control, to be connected to channel 1 of
the slave boards of each master and slave unit
CCN communication bus
Connection of two additional sensors
29
7.7 - Pump pressure/flow rate curves
200 400
375
175 350
325
150 300
275
125
250
100 225
75
1 2 3 4 200
1 2 3 4
175
150
50
125
25 100
75
0 50
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
Legend Legend
1 30XA 252-302 1 30XA 252
2 30XA 352 2 30XA 302-352
3 30XA 402 3 30XA 402-452
4 30XA 452-502 4 30XA 502
200 400
375
175
350
150 325
Available static pressure, kPa
Available static pressure, kPa
300
125 275
250
100 225
200
75 175
50 1 2 34 5 6 150
25
125
100 1 2 3 4 5 6
75
0 50
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33
Water flow rate, l/s Water flow rate, l/s
Legend Legend
1 30XA 252 1 30XA 252
2 30XA 302 2 30XA 352
3 30XA 352 3 30XA 302
4 30XA 402 4 30XA 402
5 30XA 452 5 30XA 452
6 30XA 502 6 30XA 502
30
8 - FREE-COOLING OPTION
8.1 - Characteristics
30XA with Option 118A 252 302 352 402 452 502 602 702 752 802 852 902 1002
Operating weight* kg 3840 3880 3920 4780 4850 5330 6260 6410 6710 7010 7560 7860 8440
Refrigerant charge kg
Circuit A 36 37 37 54 56 64 64 64 72 76 79 76 83
Circuit B 38 38 39 37 39 39 64 68 64 67 70 79 87
Refrigerant charge, option 254 kg
Circuit A 60 64 ** 87 87 104 104 102 ** ** 133 ** 143
Circuit B 64 64 ** 56 56 56 90 97 ** ** 97 ** 132
* Standard unit and option 119
** Option 118A (free cooling) is not compatible with these units.
8.2 - Operating limits The change-over between the cooling and free-cooling
modes is automatically controlled (it is possible to block the
Cooling mode
change-over to free-cooling by reconfiguring the machine -
Evaporator Minimum Maximum
see Controls IOM). The configurable parameters permitting
Entering water temperature at start-up °C - 45
Entering water temperature during operation °C 6.8 21 change-over are the outside air temperature and the leaving
Leaving water temperature during operation °C 3.3 26 water temperature set-point. As soon as the temperature
Condenser (air) Minimum Maximum
difference LWTstp - OAT is above 8 K the current capacity
Outdoor ambient operating temperature °C -10 55*
With winter operation option (option 28) °C -20 55* in cooling mode is calculated and compared with the theo-
Free-cooling mode retical free-cooling capacity. This comparison authorizes/
Evaporator Minimum Maximum stops the change-over to free-cooling.
Entering water temperature at start-up °C - 45
Leaving water temperature during operation °C 3,3 26*
After change-over to free-cooling all compressors are
Condenser (air) Minimum Maximum
Outdoor ambient operating temperature °C -10 20
stopped, the two (or four) two-way valves change to the free-
With winter operation option (option 28) °C -20 20 cooling position (the compressor functions are bypassed).
* Maximum configurable set-point As soon as the valves open, the free-cooling pump is started.
This change-over logic takes around 4 minutes. Taking this
8.3 - Operation
timing into consideration two cooling - free-cooling change-
1
overs are authorized per hour.
4 4
9 9
6 6
3 3
2 2
Legend
1 Evaporator
2 Air condenser (coils)
3 Motorised two-way valve, discharge side
4 Compressor and oil separator
5 Principal electronic expansion valve (EXV)
6 Pressure and temperature measurement to calculate the sub-cooling upstream
of the pump
7 Motorised two-way bypass valve
8 Free-cooling expansion device (EXV)
9 Refrigerant pump
31
9 - Heat reclaim condenser option
9.1 - Technical data, 30XA units with heat reclaim condenser option
30XA heat reclaim mode 252 302 352 402 452 502 602 702 752 802 852 902 1002
Cooling capacity* kW 261 291 311 379 438 493 603 665 707 775 814 875 971
Heating capacity in heat reclaim mode* kW 336 373 401 481 554 620 760 832 894 974 1027 1105 1229
Total power input (unit)* kW 82 90 99 113 128 140 172 183 206 219 234 253 283
Total energy efficiency ratio (EER/COP) kW/kW 3.16/ 3.22/ 3.15/ 3.36/ 3.40/ 3.53/ 3.52/ 3.63/ 3.43/ 3.53/ 3.48/ 3.45/ 3.42/
4.07 4.13 4.06 4.27 4.31 4.46 4.44 4.55 4.35 4.45 4.40 4.38 4.35
Operating weight** kg 4230 4270 4280 5260 5380 5880 7000 7100 7470 7680 8320 8670 9280
Refrigerant charge
Circuit A kg 36 37 37 53 54,5 62 62 62 70 74 77 74 96
Circuit B kg 38 38 39 37 39 39 62 66 62 69 68 77 94
Heat reclaim condenser Flooded multi-pipe condenser
Water volume l 38 38 38 55 68 68 55 + 55 55 + 55 55 + 68 55 + 68 55 + 68 68 + 68 68 + 68
Water connections Victaulic
Diameter in 3-1/2 3-1/2 3-1/2 4 4 4 4 4 4 4 4 4 4
Outside diameter mm 93 93 93 106 106 106 106 106 106 106 106 106 106
* Entering and leaving water temperature: evaporator 12°C/7°C; heat reclaim condenser: 40°C/45°C
** Weights are for guidance only
A A
C
2297
Ø141.30
560
1500
1500
2238 470
500
A
2231
2200
1500 3582
32
9.2.2 - 30XA 402-452 - heat reclaim option
A A
2297
C C
964
Ø141.30
4798 2253
1500
500
2067
2231
2200
1500 4776
A A
2297
C C
141.3
5992 2253
1500
1500
2873
2231
A
2200
1500 5970
33
9.2.4 - 30XA 602-802 - heat reclaim option
A A A
2297
C
141.3 168.3
7186 2253
1500
1500
2231
A
2200
1500 7164
A A A
2297
Ø 168.3
8380 2253
1500
1500
2836
2231
A A
2200
1500 8358
34
9.2.6 - 30XA 1002 - heat reclaim option
A A A
2297
C 219.1
9574 2253
1500
1500
2832
A
A
2231
9552
2200
1500
35
9.3 - Condenser location 9.5 - Operating limits for stable operation (no mode
changeover)
All heat reclaim condensers are located between the air-
cooled condensers on the upper part of the chassis, suppor- 9.5.1 - Cooling only mode
ted by two cross rails. The water inlet and outlet are on the Please refer to the earlier chapters in this manual:
same side. 6.1 - Unit operating range
6.7 - Evaporator water flow rate
9.4 - Condenser water connections
9.5.2 - Heat reclaim mode
9.4.1 - Unit with one heat reclaim condenser (30XA 252-502)
Condenser water temperature
The water flow switch must be installed at the water inlet of °C Minimum Maximum
the installation that arrives at the heat reclaim condenser. Water entering temperature at start-up 12.5* 55
Water entering temperature during operation 20 55
Water leaving temperature during operation 25 60
2 Evaporator water temperature
4 °C Minimum Maximum
Water entering temperature at start-up - 45
Water entering temperature during operation 6.8 21
1 Water leaving temperature during operation 3.3 15
* The water entering temperature at start-up must not be lower than 12.5°C. For
installations with a lower temperature a three-way valve must be used.
5 3
NOTE: If the temperature at the evaporator is below 4°C, a glycol/water solution or
the frost protection option must be used.
Legend
1 Heat reclaim condenser 9.6 - Operating limits for changeover between modes
2 Entering water temperature sensor (supplied)
3 Leaving water temperature sensor (supplied)
4 Condenser water flow switch (supplied) From cooling only to heat reclaim and vice versa.
5 Three-way valve (not supplied)
Heat reclaim condenser water temperature
9.4.2 - Unit with two heat reclaim condensers (30XA 602-1002) °C Minimum Maximum
The two condensers must be installed in parallel in the water Water entering temperature 12.5 57.5
Ambient operating temperature -10* 45
system of the installation. The water flow switch and the * -20°C with winter operation option (option 28)
entering/leaving water temperature sensors must be instal-
led in the line that is common to both heat reclaim circuits
and as close as possible to the condensers. A T-piece must
be provided by the installer at the water inlet and outlet of
the condensers.
2
4 1
5 3
6
Legend
Please refer to the legend in chapter 9.4.1 opposite, noting that items 2, 3 and 4 -
flow switch and sensors - are placed on the common sections.
36
9.7 - Flow control
Deadband
Setpoint, K
output activates the system pump. Once the pump is started, C
flow detection takes place for one minute. If no flow is -1.25 K
-1,25°C
detected by the end of this time: B
-2.5 K
-2,5°C
1. changeover to the heat reclaim mode is not permitted
2. mode is changed to cooling only mode when the water A
Changeover from one mode to the other (changeover from Condenser 10" (water volume = 38 litres)
Condenser 12" (water volume = 55 litres)
heat exchange at the air condenser to heat exchange at the Condenser 14" (water volume = 68 litres)
water condenser and vice versa) is ensured by motorised
For units with a water condenser please refer to chapter 9.1.
two-way valves located upstream of the air and water con-
densers.
9.10 - Frost protection
Depending on the mode selected (heat reclaim or cooling),
the logic compares the water entering temperature required
The heat reclaim condenser is equippped with electric
with the setpoint of the condenser entering water tempera-
heaters to protect the condenser against frost. These are
ture, chosen by the user. Depending on this difference the
activated if the condenser entering and leaving water tem-
unit circuits are either activated or deactivated in heat
peratures are below 3°C and deactivated, if they are higher
reclaim mode (one or two together), as shown in the follo-
than 4.4°C.
wing diagram and table.
37
10 - Major system components and • Regularly check for possible presence of impurities
operation data (e.g. silicon grains) in the heat exchange fluids. These
impurities maybe the cause of the wear or corrosion
10.1 - Direct-drive twin-screw compressor with by puncture.
variable capacity slide valve • Filter the heat exchange fluid check and carry out
internal inspections as described in EN 378-2, annex C.
• 30XA units use 06T geared twin-screw compressors • In case of re-testing please refer to the maximum
equipped with a variable capacity slide valve for operating pressure given on the unit nameplate.
continuous control between 30% and 100% of full • The reports of periodical checks by the user or operator
load. must be included in the supervision and maintenance
• Nominal capacities range from 120 to 530 kW. The file.
seven models used in the 30XA range are economised.
Repair
10.1.1 - Oil filter Any repair or modification, including the replacement of
The 06T screw compressor has an independent oil filter moving parts:
attached to the oil separator. This filter is field replaceable. • must follow local regulations and be made by qualified
operators and in accordance with qualified procedures,
10.1.2 - Refrigerant including changing the heat exchanger tubes.
The 30XA a water chiller operating only with refrigerant • must be made in accordance with the instructions of the
R134a. original manufacturer. Repair and modification that
necessitate permanent assembly (soldering, welding,
10.1.3 - Lubricant expanding etc.) must be made using the correct proce-
The 06T screw compressor is approved for use with the fol- dures and by qualified operators.
lowing lubricant: CARRIER MATERIAL SPEC PP 47-32. • An indication of any modification or repair must be
shown in the monitoring and maintenance file.
10.1.4 - Oil supply solenoid valve
An oil supply solenoid valve is installed on the oil return Recycling
line as standard to isolate the compressor from oil flow The unit is wholly or partly recyclable. After use it contains
when the compressor is not operating. The oil solenoid refrigerant vapours and oil residue. It is coated by paint.
valve is field replaceable.
Operating life
10.1.5 - Suction and economizer screens This unit is designed for:
To increase the reliability of the compressor, a screen has • prolonged storage of 15 years under nitrogen charge
been incorporated as a standard feature into suction and with a temperature difference of 20 K per day.
economizer inlets of the compressor. • 452000 cycles (start-ups) with a maximum difference
of 6 K between two neighbouring points in the vessel,
10.1.6 - Capacity control system based on 6 start-ups per hour over 15 years at a usage
The 06T screw compressor has an unloading system that is rate of 57%.
standard on all compressors. This unloading system consists
of slide valve that permits changing the length of the screw Corrosion allowances:
used for the refrigerant compression. This valve is control- Gas side: 0 mm
led by the action of a piston controlled by two solenoid Heat exchange fluid side: 1 mm for tubular plates in lightly
valves on the oil return line. alloyed steels, 0 mm for stainless steel plates or plates with
copper-nickel or stainless steel protection.
10.2 - Pressure vessels
10.2.1 - Evaporator
General 30XA chillers use a flooded multi-tube evaporator. The water
Monitoring during operation, re-qualification, re-testing circulates in the tubes and the refrigerant is on the outside
and re-testing dispensation: in the shell. One vessel is used to serve both refrigerant
• Follow the regulations on monitoring pressurised circuits. There is a centre tube sheet which separates the two
equipment. refrigerant circuits. The tubes are 3/4” diameter copper with
• It is normally required that the user or operator sets an enhanced surface inside and out. There is just one water
up and maintains a monitoring and maintenance file. circuit, and depending on the size of the chiller, there may
• Follow the control programmes of EN 378-2, annexes be one, two or three water passes.
A, B, C and D.
• If they exist follow local professional recommendations. The units have three refrigerant circuits with two evaporators
• Regularly inspect the condition of the coating (paint) connected in series on the heat transfer fluid.
to detect blistering resulting from corrosion. To do this,
check a non-insulated section of the container or the The evaporator shell has a thermal insulation of 19 mm
rust formation at the insulation joints. thick polyurethane foam, an aluminium sheet and a water
drain and purge.
38
It has been tested and stamped in accordance with applicable 10.4 - Condensers
pressure codes for a maximum operating pressure of 2100
kPa refrigerant-side and 1000 kPa water-side. The 30XA coils are micro-channel condensers made entirely
of aluminium. Optional coils with internally groved copper
The water connection of the heat exchanger is a Victaulic tubes with aluminium fins are also available (options 254
connection. As an option the evaporator is available with and 255).
frost protection (evaporator frost protection option).
10.5 - Fans
The products that may be added for thermal insulation of
the containers during the water piping connection procedure The fans are axial Flying Bird fans equipped with rotating
must be chemically neutral in relation to the materials and shroud and made of composite recyclable material. Each
coatings to which they are applied. This is also the case for motor is fixed with transverse supports. The motors are
the products originally supplied by Carrier. three-phase, with permanently lubricated bearings and
insulation class F.
10.2.2 - Oil separator
In these units, the oil separator is a pressure vessel that is 10.6 - Electronic expansion valve (EXV)
mounted under the outside vertical condenser coils. Dis-
charge gas at the compressor outlet is directed towards the The EXV is equipped with a stepper motor (2785 to 3690
bottom of the oil separator ring and most of the oil separates steps, depending on the model) that is controlled via the
from the gas by strong deceleration and by gravity. The gas EXV board.
then flows through a wire mesh screen where the remaining
oil is separated by coalescence and flows to the bottom of The EXV is also equipped with a sightglass that permits
the ring. The gas is now free from oil and leaves the ring at verification of the mechanism movement and the presence
the top towards the condenser. of the liquid gasket.
The oil separator is equipped with a trace heater regulated 10.7 - Moisture indicator
by the control. This heater is equipped with an internal
thermostat that disconnects the power supply when the Located on the EXV, permits control of the unit charge and
temperature reaches 85°C and automatically resets when indicates moisture in the circuit. The presence of bubbles in
the temperature again falls to a normal value. the sight-glass indicates an insufficient charge or non-con-
densables in the system. The presence of moisture changes
The products that may be added for thermal insulation of the colour of the indicator paper in the sight-glass.
the vessels during the water piping connection procedure
must be chemically neutral in relation to the materials and 10.8 - Filter drier
coatings to which they are applied. This is also the case for
the products originally supplied by Carrier. The role of the filter drier is to keep the circuit clean and
moisture-free. The moisture indicator shows, when it is
10.2.3 - Economiser function necessary to change the element. A difference in tempera-
The economiser function includes a liquid line valve, a filter ture between the filter inlet and outlet shows that the
drier, two EXVs, a plate heat exchanger as well as protection element is dirty.
devices (fuse or valve).
10.9 - Sensors
At the condenser outlet a part of the liquid is expanded
via the secondary EXV in one of the heat exchanger The units use thermistors to measure the temperature, and
circuits and then returns as gas at the compressor pressure transducers to control and regulate system opera-
economiser. This expansion permits increase of the liquid tion (see 30XA - Pro-Dialog Control IOM for a more
sub-cooling of the rest of the flow that penetrates the detailed explanation).
evaporator via the principal EXV. This permits increasing
the cooling capacity of the system as well as its efficiency.
39
30XA fan arrangement
1.1 2.3 2.1 1.1 1.2 1.3 2.7 2.3 2.2 2.1
1.2 1.3 2.2 1.4 1.5 1.6 1.7 2.6 2.5 2.4
1.1 1.2 2.2 2.1 1.1 1.2 1.3 1.4 2.3 2.2 2.1
2.4
1.3 1.4 2.3 1.5 1.6 1.7 1.8 2.7 2.6 2.5
1.1 1.2 2.3 2.1 1.1 1.2 1.3 1.4 2.4 2.3 2.2 2.1
1.3 1.4 1.5 2.2 1.6 1.7 1.8 1.8 2.8 2.7 2.6 2.5
1.1 1.2 1.3 2.2 2.1 3.1 3.2 3.3 3.4 1.1 1.2 1.3 2.3 2.2 2.1
1.4 1.5 1.6 2.3 3.5 3.6 3.7 3.8 1.4 1.5 1.6 2.5 2.4
1.1 1.2 1.3 2.3 2.2 2.1 3.1 3.2 3.3 3.4 1.1 1.2 1.3 2.5 2.2 2.1
1.4 1.5 1.6 2.5 2.4 3.5 3.6 3.7 3.8 1.4 1.5 1.6 1.7 2.4 2.5
1.1 1.2 1.3 2.3 2.2 2.1 3.1 3.2 3.3 3.7 1.1 1.2 1.3 2.3 2.2 2.1
1.4 1.5 1.6 2.6 2.5 2.4 3.4 3.5 3.6 1.7 1.4 1.5 1.6 2.6 2.5 2.4
1.1 1.2 1.3 2.5 2.2 2.1 3.1 3.2 3.3 3.4 1.1 1.2 1.3 1.4 2.3 2.2 2.1
2.7
1.4 1.5 1.6 1.7 2.4 2.3 3.5 3.6 3.7 3.8 1.5 1.6 1.7 1.8 1.9 2.6 2.5 2.4
1.1 1.2 1.3 1.4 2.3 2.2 2.1 3.1 3.2 3.3 3.4 1.1 1.2 1.3 1.4 2.4 2.3 2.2 2.1
1.5 1.6 1.7 1.8 2.6 2.5 2.4 3.5 3.6 3.7 3.8 1.5 1.6 1.7 1.8 2.8 2.7 2.6 2.5
30XA 1702
1.1 1.2 1.3 1.4 2.3 2.2 2.1 3.1 3.2 3.3 3.4 4.3 4.2 4.1
x.y x.y x = Circuit number 1.5 1.6 1.7 1.8 2.6 2.5 2.4 3.5 3.6 3.7 3.8 4.6 4.5 4.4
y = Start-up order
NOTE: The values above do not correspond to the fan designation. The fan
designation and position are given on the unit drawings and wiring diagrams
supplied with the unit.
40
11 - Options and accessories
41
12 - STANDARD MAINTENANCE • Check the water connections
• Purge the water circuit (see chapter “Water flow control
Air conditioning equipment must be maintained by profes- procedure”)
sional technicians, whilst routine checks can be carried out • Clean the water filter (see chapter “Water flow control
locally by specialised technicians. procedure”)
• Fully clean the condensers with a low-pressure jet and
Simple preventive maintenance will allow you to get the a bio-degradable cleaner (counter-current cleaning -
best performance from your HVAC unit: see chapter “Condenser coil - level 2)
• improved cooling performance • Replace the stuffing box packing of the pump after
• reduced power consumption 10000 hours of operation
• prevention of accidental component failure • Check the unit operating parameters and compare
• prevention of major time-consuming and costly inter- them with previous values
ventions • Keep and maintain a maintenance sheet, attached to
• protection of the environment each HVAC unit
There are five maintenance levels for HVAC units, as All these operations require strict observation of adequate
defined by the AFNOR X60-010 standard. safety measures: individual protection garments, compliance
with all industry regulations, compliance with applicable
12.1 - Level 1 maintenance (see note) local regulations and using common sense.
Simple procedure can be carried out by the user: 12.3 - Level 3 (or higher) maintenance (see note)
• Visual inspection for oil traces (sign of a refrigerant
leak) The maintenance at this level requires specific skills/
• Air heat exchanger (condenser) cleaning - see chapter approval/tools and know-how and only the manufacturer,
“Condenser coil - level 1” his representative or authorised agent are permitted to
• Check for removed protection devices, and badly carry out these operations. These maintenance operations
closed doors/covers concern for example:
• Check the unit alarm report when the unit does not • A major component replacement (compressor, evapo-
work (see report in the 30XA Pro-Dialog Plus control rator)
manual). • Any intervention on the refrigerant circuit (handling
refrigerant)
General visual inspection for any signs of deterioration. • Changing of parameters set at the factory (application
change)
12.2 - Level 2 maintenance (see note) • Removal or dismantling of the HVAC unit
• Any intervention due to a missed established mainte-
This level requires specific know-how in the electrical, nance operation
hydronic and mechanical fields. It is possible that these • Any intervention covered by the warranty
skills are avail-able locally: existence of a maintenance
service, industrial site, specialised subcontractor. NOTE: Any deviation or non-observation of these mainte-
nance criteria will render the guarantee conditions for the
In these cases, the following maintenance operations are HVAC unit nul and void, and the manufacturer, France,
recommended. will no longer be held responsible.
Carry out all level 1 operations, then: 12.4 - Tightening torques for the main electrical
• At least once a year tighten the power circuit electrical connections
connections (see tightening torques table).
Component Designation Value
• Check and re-tighten all control/command connections, in the unit (Nm)
if required (see tightening torques table). Screw on bus bar, customer connection
• Check the differential switches for correct operation M8 18
every 6 months (free-cooling option 118A). M10 L1/L2/L3 30
Soldered screw PE, customer connection (M12) PE 70
• Remove the dust and clean the interior of the control Tunnel terminal screw, compressor contactor
boxes, if required. Contactor 3RT103*
Contactor 3RT104* 5
• Check the presence and the condition of the electrical Contactor 3RT105* 11
protection devices. Contactor 3RT106* KM* 21
Tunnel terminal screw, current transformer
• Check the correct operation of all heaters. Size 2 (3RB2956*) 11
• Replace the fuses every 3 years or every 15000 hours Size 3 (3RB2966*) TI* 21
(age-hardening). Compressor earth terminal in the power wiring
control box, terminal M8 Gnd 30
• Replace the control box cooling fans used with option Compresor phase connection terminals M12 1/2/3/4/5/6 on EC 25
22 (with designation EF22_) every five years. Compressor earth connection Gnd on EC* 25
Tunnel terminal screw, disconnects 3RV1011* QF*/QM* 1
• Check the height of the anti-vibration mountings Tunnel terminal screw, hydronic pump contactor
(located between the compressor rails and the unit Contactor 3RT101* KM90* 1
Contactor 3RT102* 2.2
chassis) after 5 years of operation, and then each year. Screw on bus bar for power connection between
When the total minimum height of the mountings is the control boxes for option 81 L1/L2/L3 30
less than 28 mm replace the mountings.
42
12.5 - Tightening torques for the main bolts and For normal maintenance routines we recommend using 1 kg
screws of the concentrated product, diluted to 10%, to treat a coil
surface of 2 m2. This process can either be carried out using
Screw type Used for Value
(Nm)
a high-pressure spray gun in the low-pressure position. With
Metal screw D=4.8 Condensing module, housing supports 4.2
pressurised cleaning methods care should be taken not to
Screw H M8 Condensing module, compressor fixing 18 damage the coil fins. The spraying of the coil must be done:
Taptite screw M10 Condensing module, chassis - structure fixing, 30
control box fixings, compressor fixings,
• in the direction of the fins
oil separator fixing • in the opposite direction of the air flow direction
Taptite screw M6 Piping support, cowling 7 • with a large diffuser (25-30°)
Screw H M8 Piping clip 12
Screw H M6 Piping clip 10 • at a minimum distance of 300 mm from the coil.
Nut H M10 Compressor chassis 30
Nut H M10 Hydronic pump chassis 30
Screw H M8 Filter drier cover 40
It is not necessary to rinse the coil, as the products used
Screw H M12 Economiser port flange 40 are pH neutral. To ensure that the coil is perfectly clean, we
Screw H M16 Oil separator flanges, suction flanges 110
Screw H M16 Heat exchanger water boxes 190
recommend rinsing with a low water flow rate. The pH
Screw H M20 Suction flanges 190 value of the water used should be between 7 and 8.
Nut 5/8 ORFS Oil line 65
Nut 3/8 ORFS Oil line 26
WARNING: Never use pressurised water without a large
diffuser. Do not use high-pressure cleaners for Cu/Cu and
12.6 - Condenser coil
Cu/Al coils! High pressure cleaners are only permitted
for MCHX coils (maximum permitted pressure 68 bar)
We recommend, that finned coils are inspected regularly to
check the degree of fouling. This depends on the environ-
Concentrated and/or rotating water jets are strictly for-
ment where the unit is installed, and will be worse in urban
bidden.
and industrial installations and near trees that shed their
leaves.
Never use a fluid with a temperature above 45°C to clean
the air heat exchangers.
For coil cleaning, two maintenance levels are used, based
on the AFNOR X60-010 standard:
Correct and frequent cleaning (approximately every three
months) will prevent 2/3 of the corrosion problems.
Level 1
Protect the control box during cleaning operations.
• If the condensers are fouled, clean them gently in a
vertical direction, using a brush.
12.7 - Evaporator maintenance
• Only work on condensers with the fans switched off.
• For this type of operation switch off the HVAC unit if
Check that:
service considerations allow this.
• the insulating foam is intact and securely in place.
• Clean condensers guarantee optimal operation of
• the cooler heaters are operating, secure and correctly
your HVAC unit. This cleaning is necessary when the
positioned.
condensers begin to become fouled. The frequency of
• the water-side connections are clean and show no sign
cleaning depends on the season and location of the
of leakage.
HVAC unit (ventilated, wooded, dusty area, etc.).
• With MCHX condensers it is preferable to clean them
with a vacuum cleaner or a high-pressure cleaner
(maximum 68 bar and with 300 mm distance between
the diffuser and the coil).
Level 2
The two cleaning products can be used for any of the follow-
ing coil finishes: Cu/Cu, Cu/Al, Cu/Al with Polual, Blygold
and/or Heresite protection.
43
12.8 - Compressor maintenance 12.9 - Precaution for compresssor power supply bus
bar connection
12.8.1 - Oil separator
Check the correct operation of the heaters and check that This note applies to units using power supply bus bars with
they are well attached to the oil separator ring. riveted contact block at the level of the connection cages in
the control box. During re-connection it is imperative to:
12.8.2 - Integral oil filter change • engage each bus bar in the cage up to the stop
As system cleanliness is critical to reliable system operation, • ensure visually that the bus bars have good contact at
there is a filter in the oil line at the oil separator outlet. The the connection areas: there must not be any free move-
oil filter is specified to provide a high level of filtration (5 µm) ment between the bus bar and the connection area
required for long bearing life. created by the fixing rivet of the contact block.
The filter should be checked after the first 500 hours of Connection of the contactor or current transformer
operation, and every subsequent 2000 hours. The filter should
be replaced at any time when the pressure differential 1
across the filter exceeds 2 bar.
44
13 - start-up cHecklist for 30XA Liquid chillers (use for job file)
Preliminary information
Job name:................................................................................................................................................................................................
Location:.................................................................................................................................................................................................
Installing contractor:.............................................................................................................................................................................
Distributor:.............................................................................................................................................................................................
Unit
Model:.............................................................................................
Compresseurs
Circuit A Circuit B
Model number................................................................................ Model number............................................................................
Serial number................................................................................. Serial number.............................................................................
Motor number................................................................................ Motor number............................................................................
Circuit C Circuit D
Model number................................................................................ Model number............................................................................
Serial number................................................................................. Serial number.............................................................................
Motor number................................................................................ Motor number............................................................................
Evaporator
Model number................................................................................
Serial number.................................................................................
Condenser
Model number................................................................................
45
Unit start-up
WARNING: Operation of the chiller with an improper supply voltage or excessive phase imbalance constitutes abuse
which will invalidate the Carrier warranty. If the phase imbalance exceeds 2% for voltage, or 10% for current, contact
your local electricity supply at once and ensure that the chiller is not switched on until corrective measures have been
taken.
warning: Plot cooler pressure drop on performance data chart (in product data literature) to determine total litres
per second (l/s) and find unit’s minimum flow rate.
warning: Once power is supplied to the unit, check for any alarms (refer to the 30XA controls IOM for the alarm
menu).
46
Order No: 13452-76, 03.2008 - Supersedes order No: 13452-76, 07.2007 Manufacturer: Carrier SCS, Montluel, France.
Manufacturer reserves the right to change any product specifications without notice. Printed in the Netherlands.