0% found this document useful (0 votes)
104 views1 page

Circuit Breaker and Busbar Compatibility

This document provides a coordination table showing compatible circuit breakers and busbar trunking systems from Merlin Gerin and Telemecanique. It lists various busbar trunking systems along with their ratings in amps at 35°C and the type of Merlin Gerin circuit breakers that are compatible with maximum short-circuit currents. Circuit breakers include models from the Compact, NS, C801, C1001, and Masterpact series for use with trunking systems ranging from 200A to 4000A.

Uploaded by

Hany Shaltoot
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
104 views1 page

Circuit Breaker and Busbar Compatibility

This document provides a coordination table showing compatible circuit breakers and busbar trunking systems from Merlin Gerin and Telemecanique. It lists various busbar trunking systems along with their ratings in amps at 35°C and the type of Merlin Gerin circuit breakers that are compatible with maximum short-circuit currents. Circuit breakers include models from the Compact, NS, C801, C1001, and Masterpact series for use with trunking systems ranging from 200A to 4000A.

Uploaded by

Hany Shaltoot
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Coordination tables between Merlin Gerin circuit breakers

and Telemecanique Canalis busbar trunking systems (cont.)

voltage : 380/415 V
type of Canalis busbar trunking KVA-20 KVA-31 KVA-40 KVA-50 KVA-63 KVA-80
trunking rating (in A at 35°C) 200 315 400 500 630 800
type of circuit breaker Compact NS250N 35
Isc max. in kA ms. NS250H 70
NS250L 100
NS400N 35 45 45 45 45
NS400H 35 70 70 70 70
NS400L 35 150 150 150 150
NS630N 45 45 45 45
NS630H 70 70 70 70
NS630L 150 150 150 150
C801N 40 50
C801H 40 60
C801L 70 110
C1001N 40 50
C1001H 40 60
C1001L 70 110
Masterpact M08N1 33 40
M10N1 33 40
M08H1 33 40
M10H1 33 40
M08H2 33 40
M10H2 33 40
M08L1 40 55
M10L1 40 55

type of Canalis busbar trunking KVC-20 KVC-31 KVC-40 KVC-63 KVC-80


trunking rating (in A at 35°C) 200 315 400 630 800
type of circuit breaker Compact NS250N 35
Isc max. in kA ms. NS250H 70
NS250L 100
NS400N 35 45 45 45
NS400H 35 70 70 70
NS400L 35 150 150 150
NS630N 45 45 45
NS630H 70 70 70
NS630L 150 150 150
C801N 40 50
C801H 40 60
C801L 70 110
C1001N 40 50
C1001H 40 60
C1001L 70 110
Masterpact M08N1 36 40
M10N1 36 40
M08H1 36 40
M10H1 36 40
M08H2 36 40
M10H2 36 40
M08L1 40 55
M10L1 40 55

type of Canalis busbar trunking KTA-10 KTA-12 KTA-16 KTA-20 KTA-25 KTA-30 KTA-40
trunking rating (in A at 35°C) 1000 1200 1600 2000 2500 3000 4000
type of circuit breaker Compact C1001N 50 50
Isc max. in kA ms. C1001H 55 70
C1001L 100 150
C1251N 50 50
C1251H 55 70
Masterpact M10N1 40 40 40 40
M12N1 40 40 40 40
M16N1 40 40 40 40
M20N1 55 55 55 55
M25N1 55 55 55 55
M10H1 40 50 60 65
M12H1 40 50 60 65
M16H1 40 50 60 65
M20H1 60 73 75 75
M25H1 60 73 75 75
M32H1 75 75 75
M40H1 75 75 75
M50H1 90
M10H2 40 50 60 73
M12H2 40 50 60 73
M16H2 40 50 60 73
M20H2 60 73 80 86
M25H2 60 73 80 86
M32H2 80 86 90
M40H2 80 86 90
M50H2 90
M10L1 55 85 130
M12L1 55 85 130
M16L1 65 105 130 130
M20L1 65 105 130 130
M25L1 65 105 130 130

32