Everyday Details
Everyday Details
Cecli C Handisyde
Everyday Details
EVERYDAY DETAILS
Cecil C Handisyde
AREA, MDp
In 1923: The Architectural Press published a delightful aiid the comments. Despite extensive discussion ofdrafts by the
useful littlebook,written byanarchitect namedEdwin Gunn, original team, followedbysubmission oftheir work toat least
called Little ThingsTIvu MatterFor Those Who Build.'It did twoother experts for further checking and comm4t prior to.
not claim, in its 82 pages, to do more than give a practical a
priblication, readers were able to pointout few errorsaswell
man'sview ontherealproblemsofputtingasimple, traditional as adding usefulsuggestions for alternative details. This em-
It
building together. was neverintended to be—and this was phasises how essential itis forworking details to becirefully
itsgreatstrength—an exhaustivetreatiseonbuilding construc- prepared andchecked. Every part ofajob must beconsidered
tion. Its stylewas informal andchattyandTheauthorwas never toensure that,as far as possible, all necessarysite information
one to shrink from giving a 'fra±ik opinion—'that execrable is included, that details arepracticable for the operatives,that
material, black mortar. . .'—oi from beingwhimsical,1. But they are suitable for their particular circumstances, andthat
his intentions were serious and his advice sound, 2 the'will betechnicallyandvisually satisfactoryinperformance.
The preface to the first edition of Gunn's book is equally
applicable to this: 'The authormakes no claimto anything
sensational inthematterof.these notes. Some oftheexpedients
are veryold ones,someare-posibly. new, and these latter are
notall ofhis ownorigination Hebelievesthat everyarchitect
a
*ho strikes or avoids "snag"ought to openthemattertohis
fellows. Quacks secret; scientists pithlish.'
-I
In suspended ground floor construction, 2, 3, the floor level
in elation tofoundations and site concrete affects ovrall
job cost throughits effect on wall height. The costs
l°'
excavation and hardcore arenot directly influeticedby floor
level,but decisions on the level ofoversite concrete will x&5s OpaoE oaoS44
affect hardcore cost. heh of
Vast'Wol pw €xio-ôia4 va,Uo
a)
b)).4Oroo ioJA
c) &eepGY I&J.
\7\/
2
/\
\/\
•.*.••.
/ htrdo1tiokoo'os
ciepeio o,,:
Ivd of o-c4
f
nf: oQe'o oocre4 MO bo oA w4
RL4 .-t of opi
41o sotd
ocooJ,oo
oo3'A1oo)
fR,o-o
jocJ aJ4o.js Th coc.e
Solidfloors
Withsolidgroundfloors, dedsions aboutfloor level not only
•
gI
affect wall heights but also directly influence thickness,and
therefore cost, ofhardcore (see 1).
Oversite excavation
The depth ofoversite excavationaffects hardcore cost and
excavation cost but theimplications ofhastyoffice
decisionsto 'remove topsoil to a depth ofx inns' are not
alwaysappreciated. Opinions about what constitutes
'fopsoil' vary and neither textbooks nor the Building
Regulations are veryhelpful. The Regulations require the
site to be 'effectively cleared ofturfand othervegetable
matter'. Topsoil may vary from almost nil toa metre or
more and itmay have been cultivated to a considerable
depth and contain deep rooted vegetation or have been
undisturbed for centuries and have only turf growing on its
top layer.
The architect may reconsider his decision after seeing the
ground duringexcavation. This may mean an unwelcome
increase in cost bothin more excavation and in the resulting
extrahardcore—one ofthe hard facts oflife is that an over
estimate ofexcavation seldom seems to occur! Sitesurvey or
trial hole information should therefore be sufficient for
correct decisionstobe made before completing design stage.
Hardcore has traditionally been specifiedas 'good clean Isp of liostinto iso rouli Is recscse c000an'e cvdpm
brick brokento pass a 4in ring, or other approved
material'. Nowadaysthis often produces a load ofmixed
rubbish containing anything from old plaster-and bits of
timber to largelumpsofbrick walling.This gets tipped into
position whenthe architect is not on siteand it becomes
difficultto enforce a satisfactoryresult. The thicker the
hardcore the more difficult itis to avOid cavities into which
upper layer material may later subside, 9.
A moderate thickness, 100 to 150mm after consolidation,of
well graded stones, or the use ofhoggin° as a fill material, is-
preferable to a thickpoorfill. Hoggin is usually S
considerably dearer than hardcore. In Scotland, an
alternative material is blaes (oilshale), but this mustbe well
burnt, and should have less than 02 per cent concentration
ofsuiphates. -
Oversite dampproof
-
membranes
On almost all buildings with solid ground floors the
Building Regulations 'deemed to satisfy' clauses require a
continuous dpm. This issometimes placed beneath the
oversite concrete,somelimes as a sandwich between slab and
screed and sometimes on top ofthe concrete when it is used
as a combined dpmand floor finish adhesive, eg with timber
finish on asphalt or pitchmastic or hot bitumçn.
On p.vf. 65w
.::..•'o floorft4hasidicreet
I5 fth
\AAAA
cayc,als
11
Designed reinforcement needs careful positioning. A single ground ' soil, softclay, peat)
Fill ormade-up Compacted sandor Not needed Unsuitable
gravel
Oltactedaverage 0-100 Unsuitable
125/22'
150/55'
layerneeds blocking upandwhen two layers are usedthe soils
top one should be supported onreinforcement chairs. Watertable Stable 150 125 100/22
within 600mm Normal 150 150 125/22
ofsurface Unstable 150 125/55
Ingeneralit is probably better tohave a poor slab on a
150
NB: Withsoftunderlyingstrata andinmining subsidence area,areinforced raft
good baseratherthan a goodslab on a poorbase. For this
reason attentionshouldbe givenespeciallyto quality and c
andstructural separation willbe necessary
these cases itmay be necessaryto treatthe slab as .uopcnded, withbearings
onwalls; hardcore thicknessmay be reduced or, ifconvenient,hardcore maybe
compaction ofhardcore(see 'Hardcore', page 4). omitted andthe soil covered withblinding concrete priortolaying the alab
2
I
2
Strip foundations to external walls
General
For small,single-storeybuildingswith spansup to about
10 m or buildings with domestictype spansandheights up
to threestoreys, the choiceofstriptype'footings is less
obvious than it used to be. Onclay soils, shortboredpiles
may be preferable, while for,light loading on bad ground,
raft foundations are becoming more frequent(see detail 3,
page 11). In spite ofthis, strip footings remain themostusual.
Old text books putgreatemphasis uponfoundationwidth
but said little aboutdepthbelow ground. The 1972Building
Regulations allow quitenarrow foundations for small
building loads on moderate ground such as sandyclay
(Class IV, table'to Regulation D7), while recognition'ofthe
dangers ofclay soil shrinkagehas resultedin more emphasis
on the needfor depth. Simultaneouslythere has been the
change from hand to machine excavation, withits speed,
ease ofdigging deep and narrow trenches andpreference for
digging in uninterrupted straight lines. At the same time
the balance ofcosts has changed to make economy in labour
relatively moreattractive than economy insomematerials.
In spite ofthese changes, designs for strip fqundations and
walls up to ground level, even ifmodified to some extent,
still seem to clingtothe traditional form. Inthe following
examples theimplications uponcostandother aspects are
examined for two designs ofstrip foundation.
Examples
A small building is assumed to have external wall loiding of
approximately 33 kN/mrun ofwall.
1 2
I
10
Table I, presented as indexranges, shows probable cost dpm is correctly joined to the wall dpc.
relationships for cases 1 and 2. These are based upon 4 It is doubtful whether cavity grouting is necessary for the
prices ofitems wit/tourmaking allowancesfor small depthifhardcore consolidationisdone carefully to
non-measurable production savingsonsite. Even on this avoiddamage to the walling. The position ofthe dpm is
basis, although the cost ranges offoundations 1 and 2 debatable: ifplace4 beneath the concrete it is moreliableto
overlap, foundation 2 should be generally cheaper. flamageduring construction, and a muchlonger time must
be allowed forthe drying out ofthickconcrete beforelaying
The GLC made these points: most types offloor finish.'
'1 Figures indicate about80mm backfill externally. This is
a difficultwidthto backfill. Tabie I Costrelationship.forfound.tlzn types A and B'
2 The trench excavation wdul&need to be widerto build Foundationtype Concretemix
i-3-6
Concretemix
i-2—4
brickwork below ground level. 100-122 101-124
3 The cavity grouting drainage fillet should preferably be 90-110 93-li4
above the ground line todrain the cavity. Figures give index
designs Aand B.
ran calculated onprices at tint quarter1971 based on
4 Process 2 is preferred to process 1 andis cheaper. The * Co,taas at October 1973
cavity groutingand drainage fillet have been omitted. There
are advantages inhaving the dpm below the concrete. With
Materials
dpmbeneath the screed, cracking Qfthe screed atits Brickworkhas been taken as local common bricks in
junction with the wall is known to occur.' 1:3 cement/sand mortar.
Cecil Randisyde replied:
'1 Agreed this would be significantfor the depth in 1 but not Table I shows values for twO concrete mixes. Strength of
in 2. concrete may vary very considerably.depending uponwater
2 1 indicates the probable need to widen the trench (shown content and grading ofaggregate.In tnanycases a 1:3:6 mix
on the inside). Ifmore width is considered necessary the should be adequate.
costwill increase, and this should be considered in
comparison with process 2. Wallingmight, in some cases, be ofsuitable quality
3 Agreed this is desirable. The question mightthen arise as concrete blocks ratherthan brick.
to whether the floor structure must beraised in orderto
maintain the floor dpm 150 mm above the bottom ofthe In clay soils, sulphates may bepresentin sufficient
quantity to require higher quality concrete and brickwork.
cavity. This is not statedas a requirement under Building
Regulation C5(c) and shouldnot be necessary ifthe floor
Check list
Design Supervision
Assumingit has been decided to use strip footings: Check settingout. Check excavation dimensions.
From loading calculations and site survey information on Check suil is all as expected, or when necessary agree
soil, determine minimum overall depthand width of action for weak spots etc.
foundation (Building Regulations, Regulation D7).
Immediately before concreting, check trench soil conditions.
Consider cost and otherfactors and decide between concrete Also confirm service entry provisions.
footing with masonry walling and deep concrete trench.
Check qualityofmaterials, and for thin concrete footings,
Check service entry requirements compatible with check thicknàs as laid.
foundation.
Check overlaps at changesin levels (Regulation D7 (e)).
Decide positions for any erfical stepping offoundationson
sloping sites. Check materials and adequacy ofcompaction ofbackfill.
Specification
Describe materials. Consider need to specify special
precautions in high sulphate soils. Describe disposal of
surplus excavation.
3
Raft foundations fOr small buildings
Advantagesand disadvantages
These,consideredat earlydesign stage, should help to
decidewhether detailed investigation is worthwhile. Cost
comparisons between raft andother typesoffoundation are
only feasible when related to specificcasesbut some
influencing factors are mentioned. The edge treatment ofa
raft provides the mainproblems ofstructuraldesign,
building details andvisual effect, 1 to 4.
Advantages
1 Simple machine excavationwithouttrenching.
2Absence offoundation trenches facilitates movement of
men and materials.
3 Excavationlessliablethan trenches to become
waterloggedordamaged in badweather.
4 Less intefference with sub-soil watermovements.
5 May eliminate need for awkward below-groundwalling by
bricklayers.
6 Probably quicker than alternativesofstrip or shortpile
foundations.
7 In poor sites, they avoid penetrating poor bearing
materials jusi below the surface.
Disadvantages
1 May not be adequate for someloading and soil
conditions.
2 Ductsor pipe chases inthe floor present problems.
3 Precautions usually need to be takenagainst drying
shrinkage or frost heaving ofground beneath the raft
perimeter.
4 Unequalloaddistribution,egpiers,may cause problems.
5 Raftsareseldom worthconsidering unless thesite is
substantially level.
12
Edgeof raftdetail
In determining the typeofedge treatment forrafts the
following pointsshould be considered:
1 Provision ofreasonable support for perimeter wall loads.
2 Prevention ofweather effect causing either frostheave or
drying shrinkage ofground beneath the edge oftheraft.
3 Simple and efficient damp-proofing.
4 Accommodationofminor variations in ground levels.
5 Appearance.
6 Permanence ofsatisfactory support conditions.
7 Protection ofsteel and durability ofreinforced concrete.
9IL .
depthunder the wall, 5b.
In6, protection, asin 5, Is required. Withoutthe paved area,
the projecting raft slab could be damaged by lifting under
frost action,orits toe maylose support by drying shrinkage.
Paving shouldbe minimum 600mm wide slabs.
6a
6b
L
7 is satisfactory for weathering ifdepthoftoe is 500 mmin
well draiied cohesionlesssoil, or 1000mm inother soils.
This method loses some ofthe advantages ofaraft and
almost becomes astrip footing. Is unsatisfactoryin mining
areas.
dx Yeqtuv&4
'
fpofrafrs —
aboy rai level
dpw 5&Lhd
dpc
Q1j
a
Sc
14
Sb
Accommodationof variations in
-
groundlevels
Raft constructionofthe type being considered here is
normally considered only for 'level' sites. Minor variations hqi grw oci.skz cwn
inground level are probably best dealt withbylocal
adjustment ofground atthe edge ofthe projecting
paving, 11 (dpm to floor in 11, 12, 13, 14 as 9).
-
iot grau1 adL6ttd u.p
11
12
Appearance
.4[ t—---
Edgeprotectionand the projection ofthe raft itselfprevent prtsctwc.M
normal cultivation immediately adjacertto a building, ac€ aoh4,St
a4%1p
thoughsomeformofraised growing trough can be provided dpc
ifcareis taken topreventdamp penetration above the main
wall dpc, 13.
15
Maintenance
Protection against the effect ofweather uponsoil beneath Protectionofsteel and durabilityofconcrete
the edge ofthe concrete raft must be preserved. Where Where exposed aroundthe perimeter, the concrete must be
paving forms a useful path system, the risk ofalteration is ofgoodquality and provide top pr side cover to steelofat
probably small. Where the paving is not serving auseful least50 mm. Bottom cover tosteel should not be lss than
purpose, its permanence is less certain. Ardent gardening 40 mm.
house-owners probably provide the greatest risk. To ensure
against removal, consider using in situ concrete paving.
l
Cost aspects of rafts
Although detailed costcomparisons can be made only in
1 As an alternative to deep footings.
2 When high water table would complicate trench
excavations.
specificcases, raft foundations may provide economical 3 Where perimeter wall loads are very light, eg timber
solutions, especially when moderately deepsubstructures
would otherwise berequired. An economiccase can be made,
particularly for designs which do not use a projecting slab,
r
framewalls, a simple raft maycost less.
5 Unlikely to be satisfactory economic on sloping sites.
6 Unlikely to be satisfactoty or economic when loading is
and, where structurally acceptable,it is likely to be more veryuneven, egheavy pier loads.
economic to thicken the slab than to projectit beyoid the 7 Unlikely to be economic when ground conditions and
external faceofthe walling. The followingnotesgive some wall loads permit shallowstrip footings.
indication ofwhen rafts may be used .
2
Availabletrot,,BritishStandard, Institution, ParkStreet,London W,1
16
Types of foundation
Wall directon unreinforced oversite concreteon
hardcore
2 eliminatescoat offoundation and site nuisance of
excavatedtrenches.
Wall on unreiiforced
- concrete, thickened to depth -
ofhardcore
3ab is similar to 2 but prevents settlement due to poor
hardcore. Where thickened base isin excavated soil, the
extrathickness ofconcrete givesadditional strength and
allows more spreading ofthe load.
Opc
3b
4b 4c
Concretestripfooting foundation
5abc is similar to 4 but hasnarrow concrete-filled trench
• instead ofwalling do*nto concrete base. Trench can be
elcavated by machIne, avoiding awkward low-levelbrick or
block laying. (See also detail2, page 8, 'Strip foundations to
external walls'.)
•
In 5, unlike4 it is essential toprovideinadvance forany
below-groundservices. -
5a Sc
19
6a 6b
loadings.
'COst comparisons
. aWIndesooundasioncoscs
carried down togood bearing 100-120
Stripfoundations
Table III, expressed as anindex, compares the costranges soil withadditional concrete at abutments with
for strip and concrete-filled narrow trench foundations to of wall 190-230
inteinajwalls. foundations carried 85-195 -
down togoodbearing soil withadditional concrete
The cost comatison is basedupon an8m run ofone Concrete-fillednarrow trenchfoundationat the 120-110
brick thickinternalwalling measured tip to dpc level where level ofexternal wall,foundations forfull length
the bottom ofthe external wall fbundation is 1000mm 'Costsan at January 1974
below gràuid level. Table IV Costrelationshipbetweenstripandraftfoundationa
Description Indexrange.
Table IVindicates cost relationshipsbetween strip or raft
foundations forinternalwalls,
fjnItIOnOcrIed
with
abutments external wall foundations
down 100-120
- ..
Concrete Iloor andconcrete-fillednarrow trcnch 95—120
Inundations carried downtogoodbearing soilwith -
The cost comparison is based upon an8m run- ofone additional concrete atabutments with externalwall -
brick thickinternalwalling withsolid concrete floor 6 m p,aft 125 thickover full floor area, forwall 110-160
either side (but ignoring external walls). -
t
?0
reinforcement below internalwalls, loadingas above
125-150
5 4
,
'
Masonry walls: dpc at base of external walls
A
/
Even the thinnestdpc material, ifproperly laid with mortar
below andabove,,results in.a thicker than normal joint. This
cannot be avoided but,where theeffect is considered
important, theuse of athin damp-proofing material helps.
On sloping sites, the dpc is usually steppedat intervals with
avertical link. This thickvertical joint can bevery
_
V/
unsightly. Travelling horizontally, thethickened dpc joint
will change to a normal thinjoint at the point where the
OLthidk
dpcbendsveitically down. So normal course lines are
intemIpted. Big vertical stepsbecome particularly obtrusive.
it
Subject tosite level requirements, is worthtryingto
position the vertical steps wherethey will be least
noticeable, eg behind planting or at internalcorners, 1,
behind rainwaterpipes(ifthepositions ofthese can be
accurately located in time and ifpipeftxings will not be
driven into thedpc) 2.
// 7/ lii 7/ // /7 /7 -
—
3
Rendqjshouldstop
a
above the dpc level. Some published
4. Theturn down
details4W&nrend projectixg dpc,
optiniistkally assumed on drawings is unlikely to be
achieved wth mostmaterials. Ifit projects flat, 5, it forms a
ledgeforwaterjust where that is most harmful.
The dpc shouldalwayscome totheedge ofarenderedwall,
but npt 'beyond.
ii:
22
it
Where cavitygroutingisrequired, shouldfinish at least
150 mmbelow both dpcs. Ifthereis any doubt about
properclearance ofmortardroppings from the bottom of
the cavity, the 150 mm may not be sufficient, 10.
10
Highlevel groundoutside
Where a site slopes but ground floor level is constant, itis
very easy tofail tonoticethat theinner wall dpc, although dpc
above thebouonofthe cavity, is not above a level to
which the cavity mayfill with water, 11.
Jo
grevaA 9!
8o
do
/
12
/;
23
////-
I
floor membranecan be turnedupand into the wall, lapping — r rer
withthewalldpc, 14. Care is needed topreventdamage II cto
while concretingaid during subsequent site works. Damage OAYt
may not be visible once floor concrete is placed. . 14
ifeaent
site concrete is not laid at walldpc stage, a similar budk-Ac
CLM
/
with the floor membrane tucked into an open
joint is possible butless easy to achieve satisfactorily. /1 S
An alternative, 15, is to stopihe turnedup dpm at top of
site concrete andform the vertical linkas a separate - . CP.U
pass above the wall dpc level and return on to thetop ofthe
oversite concrete with a generous application ofmaterial at
the wall/floorjoint.
// dpM
Floor level above wall dpc
In all the above examples,ithas been assumed that the 77- —
inner wall dpc is above or at floor dpm level. Withcavity 7/
wall construction this is normally so but with sloping sites 7' c
/
l
andsolidwalls there may be situations where the wall dpc
is below the floor dpm level. Ifthis doesoccur,it is dpr 71vi-ieoj •
important to note that the vertical link must be formed 7' J
before the oversite concretciis laid,20. /7] corr ioi
20
T.bleI Coatcompanion of
Cost considerations
The need for full protection against penetration ofdampness
is overriding. Consequentialdamage and repairs caused by
dpc failure aremanytimes more costly than ifdetailing and
construction supervision had been correct iiithefirst place.
n:
tnen:hezoanbur
heuianbase + lead
Twocourses slates
ecot5egineeruig brici
100
204
615
forbrtckworkrr1laced)
(ailowsna,sction
Cost is not usually a determining fatorin the choice ofdpc Leadas no5 1400
levels.and details. Itis only considered wherethefunctional 515
requirements can bemet by a variety ofmaterials, whose Ahisninium20 awg 585
Check list •
Specification
Type and quality ofmaterial. (Note that Building
••
Design
Dpc levels related to aLlground andpaving levels
••
Regulations allow liquid dpms ofeither 3 mm hot
bitumenorcoal tar pitch, or three coat solutions)
•Fix any change inlevel ofdpc, considering appearance
Internaldpc levels related to floor dpm and how Bedding, laps, forming steps, etc
Method ofjoint to vertical or floor membrane
••
•• continuity will be obtained
Check all dpc'-ievelswithbottom ofcavity level
Check top ofwall dpc joint tosuit couresin wall for
Width related to wall width
Draw, or cover by descriptions, all levels and details.
6
Timber framed walls: dpc at ground level
Generalconsiderations 3 Illustrations 1 to 7 do nor show wall structure,thermal
insulation or vapour barriers.* Some form ofinsulation is
Dpá design at the base oftimber-framed walls must be
carefully considered for the particular type ofstructure, almost alwaysrequired. Internalvapour barriersareoften
Detailing will vary according totype ofexternal cladding necessaryespecially ifthe external wall covering is ofatype
and type offloor construction, solid or suspended. Some through whichwatervapour cannot readily escape.
constructions resultin ground floors having to be raised 4 All vulnerable timbers suchas wall plates, sill plates and
considerably above ground level, soleplates should bepressure treated with a preservative
1 On tlopmg sites, positions where the dpc maybe stepped even though they are partlyprotected by a dpc. Treatment
are likelyto be more restrictive than-with masonry wall ofother timberssuch asfloor joists or wailframingmay be
construction. worthwhile, depending on particular circumstances.
2 Thesequence ofbuilding operations has important ,
It may be difficultto place tile fixing bolt near the edge of e4p404t —
.-
Ronald'ssolutions.
I
sketches for alightweight timber-frame structure withhigh
insulation. There ii a continuous dprn between blinding and
floor slab. The slab is stepped back from the edge ofthe
foundation: this allows the door threshold to be flush with
the flooring,and continuous insulation between wallcavity
to the exactlevel would need very goodsupervision, unless and battened floor.
the material were thin enough to be bent to shape easily on Cecil Handisyde commented: 'Thepublished details did
site'. not include an example showing a timber floor on battens.
R. E. Owen, senior lecturerin construction at Oxford The suggested detail exposes the full thicknessofoversite
Polytechnic,pointedout that theproblem is dealt with on concrete above the dpm. Unless the concrete is very well
pages 18 and 19 of Timber stud walls ofSwedishredwood and dried out before the flooring is laid moisture would be
whitewood issued free by The SwedishTimber Council, trappedin a stagnant air space.The Outer cladding is
Sweden House, 14 TrinitySquare, LondonEC3N 4BN. broughtto 150 mm above ground level. Withvulnerable
He continued: 'In every case shown except one the fixing cladding the 200 mm dimension is preferable, but it was
penetrates the horizontal dpc. Inthis exception a fiat notedthat one resultofthat dimension was to raise the level
vertical strap isfixed, one assumes with a heavy screw or ofthe oversite concrçte and therefore toincrease the
coach screw, tothe back ofthe sole plate,whereitwould thickness and cost ofhardcore. The detailproposed by Mr
appear to interfere with the fixing ofthe inner wall lining. Ronald has a similar effect. As drawn the step detail could
Moreover the strap is shown cast into the concrete slab, allowwaterpenetration; a vertical dpc infront ofthe timber
posing problems ofvertical alignment, accuracy and location. plates could usefully beincluded.'
My preferred solution would be a flat galvanised steel strap, The GLCcommented: 'The details are sound. Bolting
about250 x 30 x 3 mm twice screwed to the underside of would be better than cranking for fixing plates to timber. Do
theplate and twice screwed to waterproof plugs in the not like the detail where thedrainage fillet runs along the
concrete (or bythe use ofa pair ofexpanding bolfs of firstbrick jointing at ground level. Groundlevels are rarely
appropriate size). This would give adequate locationand straight, even allowingfor settlement ofground. The
restraint,unless the studwallis subject to substantial lifting drainage fillet should always drainout anymoisture at least
force. The tendency ofthe strap beneath the sole plate to one course above ground level, preferably two courses.'
overload the dpcmaterial couldbe prevented by housing it Cecil Handisydereplied: 'Certainly care is needed to
in flush, or by using a thinstrap packing between plate and ensure that the levels shown are maintained. 2makes this
dpc. However, theprojection ofthestrap would have to be point with its 150 mm minimum for dpc level above ground.
covered byscreedand dpm. This detail would beunsuitable To implement the GLC suggestion would necessitate raising
for power-floatedconcrete or an asphalt "screed"ofonly thelevelofthe site slabrelative to the ground, which would
12-15 mm. In my direct experience offixing theplate by the increase the cost.'
hanging
Solidfloor amAt she,dksj m%4&SraLA
In 4, iftimber wall frames come prfabricated andwith sofbaamd,m4ti
moisture barrieralready fixed, the bottom ofwall flashing
cannot becorrectly positioned (unless the bottom 150 mm
are left loose, and therefore vulnerable todamage).
o1pIM dpc Ic'-ppaa
QMG S€OAa'4
b€hafnck
*rck bcimgs
faa 5moL4
5
Timberframe/timbercladding
Solidfloor
In6,itis,aumed that timbercladding provides bracing, so bn,aJkey L)lI
- ixLU (.4L,kW \JI hcim
timber shtathing shown next to framing on 1 to 5 is MmShi4'a barrea'
omitted. Ifcladding isinadequate, bracing by sheathing or -1
in the frameconstruction must be included. Battens are not
shown. They would be needed for vertical board cladding cpc hi prcjed cm%i ba
aa seaiaa todpw
a&
and have the advantages offorming an additional cavity
— aa
which would improve insulation.
As with earlier examples the placing ofsite dpm below the Raising the cladding to 200 mmminimum above ground
concrete would cause problems. level reduces the risk ofdamage,butthe exposed bottom
it
As in 2 and 4, may be difficulttu place the fixing bolt edge ofthe cladding is still vulnerable and must be
near the edge ofthe concrete. protected (ie cut ends oftreated timber shouldbe retreated).
28
Suspended timberfloor
In 7, it is assumed that timber cladding provides bracing so
timber sheathing shoyn next to framingon 1 to5 is
omitted. Ifcladding is inadequate bracing by sheathing or
in the frameconstruction must be included.
Battens are not shown. They would be needed for vertical
board cladding andhave theadvantage offorming..an
additional cavity which would improve insulation.
In this detailfloor level inevitably becomes high above
ground level.
29
7
Masonry walls: jarnbs with timberwindowframes
Workmanship
The jamb Some details depend forsuccess upon careful workmanship.
For thejambdetailalone the followingpointsshould be The building type may decide what quality oflabourand
considered; supervision can be expected, and details should be chosen
accordingly.
Degree of site exposure
Order offixing
Types ofprepo,sedmaterials Details suited to frames 'built-in' as the masonry goes up do
Water penetration through masonry can vary considerably. not alwaysworkforframes which are tobe 'fixed' afterthe
Adense 'impermeable' brick may leak through joint masonry opening is complete.
shrinkage and fail to dry out,-whereas an apparently
permeable material may prove less troublesome because, Positionofframe in wall
although itgets very wet, it also dries quickly. Whether ina reveal.
Where in relation towall vertical dpm.
Tmber couldbe durable hardwood or preservative treated
softwood, but not unprotected softwood ofpoor quality. Prevention ofwaterreaching to insideofstructure
All lugs and fixings must be galvanised. Protectionofbackofframe from dampness
either.entering directly into frame/wall joint
Mastic must be backed with plastic foam except on very or penetrating front face masonry and reaching the frame.
small windows where mastic is forming a sal only and is
'/oc I Ii'
not likely to be'stressed bymovement offrame 3. Appàarance and convenience
Appearance is affectedby width ofvisible frame and
distance offrame'fromwallfaces.
3
Positionofdpe
///
Whatever detailofwindow opening, dpc mustbe brought
j/ P"
through to end ofwall as otherwise watercan pass toinner •-
skin causing deterioration ofplaster, 4. - N.
//
proper mastic joint including foam plastic backing, 3.
/ /i/i/
Dpc mustbe fixed tight to frameface as otherwise this may
be damaged when mastic backing pieceis applied. A
flexible type ofdpc is required.
.
.
//i
/ //—/// /
c4?c
.
If .
windows are specials, a detail similar to 7 may be // /7
[- -
.
altered to assist in building brickwork to frame, by rebating
cornerto receive mastic, 8. 8
Straight joint:
dpc projects into frame
It iould seem possible to achieve positive seal by
projecting a fairly stiffdpc into recess inback offrame,9.
But it is difficult tofix the frame in this position. The dpc
material must be wider than the normal halfbrick wall type
it
if is to give full protection to walling andprojectinto
frame.
TT qO.A4(44464d
b4>
-'
/-'
'9
Window can be moved further back, and iffront offrame is
rebated, dpc can project into recess, and the face can be
31
/7
be inserted later andscrew-fixed. S pc
Goodfixing to dry brickwork canbe achieved.
/ frtp
7/ ac
14l5t41d of
//
A wide external sill will result(see detail11, page 52) a'
The previous detail,10, can be modified for fixing frame into
peparedopening but junction with dpcisnot so ppsitive, lj.
(Could be.adapted as 8 to allow mastic to project into groove
in frame.)
Plasterfinish to frame
Whetherdetails13a or b are used, plaster will not be
finished true to frameand will crack when frame shrinks.
/// /TIl
7/ 141
////
///
32
Hugo Mason commented: 'I am surprised bysomeofthe 'I am sorryto be so critical, but I have seen most ofthese
window reveal details youhave shown. Although youmake I
details fail in practice. enclosea sketch (below)ofa window
I
reference to workmanship and site exposure, must say from reveal detailwhich wefind satisfactoryin all conditions.'
I
my ownexperience find many'd(your details
//
unsatisfactory.
'Wemust consider that abuilding is to be permanent and
themastic shown on your details invariably fails aftera few
years. This would almost.crtainlyleadto a failure in 7, 8,
iOn and 11. Ajoint mustbeconsidered waterproof before
the *pplicationofmastic.
'9 does nottakeaccount ofpoorworkmanship or a flexible
dpc. Invariably therewill begaps between the clpc and the
framebecause a.dpcis rarely truly vertical.
'lOb can also be considered as temporary. On exposed sites
slender coverfillets donot standup to waterpenetration and 'AgrémentCertiScate75/291 for theHyload dpcsystem replaces 73/173 and
relates toit, useinbothsolidandcavity con,truction in horizontal,verticalor
acrack between the frame and the fillet inthis instance stepped positions, including cavity trays. Theccrtificatr now covers the complete
system including Hyload pee-formed cloak, forcornerdetails and changesoflevel,
would certainly allow waterpenetration. andHyload Contact Adhesive forsealing alllapjoints.
33
8
Masonrywalls: metal windowsfixed direct
Fixing
Jamb, head and sill details depend bpon whether windows
are fixed as brickwork is beingbuilt, or fixed subsequently
to prepared window openings. In the latter,accurate
masonry dimensions must beobtained andverycareful site
supervision is needed to ensure this.
In domestic work frames are often fixed by the general
contractor as the work proceeds. On largerbuildings,
windowsareusually fixed inpreparedbpenings, sometimes
by the general contractor but often bya window specialist.
BS 990 (Part 11967, Part 2 1972)* givesstandard sizes and
fixing positions for domestic windows. Where non-standard
e
windows are to builtinto prepared openings, it is
essential that full window details (architects' or
manufacturers' drawings) are issued to the contractor so
that openings can beaccurately formed, and, when
appropriate, fixing blocks can be cast into the structure.
it
Where special windows are to be fixed is usually
preferable for themanufacturer to fix as, ifany defect
appears later, there is no risk ofa demarcation dispute
between manufacturer and contractor.
Themainconsiderations are:
1 strengthoffixing
2 efficient weatherprooflngaround theframeperimeter.
Details whichmay have proved successfulin low buildings
onrelatively sheltered sites may be inadequate in a higher
building, or on severely exposed orseaside areas (See Elder,
A. J., and Vandenberg, M., AHandbookofBuilding
Enclosure,page 168ff, IS 'External Walls 9'. The
Archithctural PressLtd. 1974.)
Because ofthe difficultyin thakiga satisfatorymetal,
frame tomasonry joint, steel windows are often fixed ij
timber sub-frames. Fixing ofsUb-framethen followswood
windowsdetailing (detail 7, page 29).
Jamb details
Window manufacturers oftenprovide verygooddetails of
the way inwhichwindowscan be fixed to thestructurebut
they do not alwaysindicatetherelationship oftheframeto
dpm systems.
1 ix atypical example. The fixing is adequate, but ifthe
internalplaster werein contact with external brickwork
disaster wouldresult.
-•;-_- of
Fixing methods
When frame is built in, itis difficulttomaintain a constant
3 mm (theold jin) gap. Invariably brickworkis built
tight toframe.Mastic then becomesonly an applied fillet.
Even with a 3 mmgap the mastic joint is ofdoubtful
efficiency.Betterprotection can be obtained ifthevertical
dpc is extended into theframe,as in 2.
This limits the position oftheframein thethickness of
thewall.
Built-in lugfixing
In 2 thelug is bolted tothe frame and built inas work IL, uc,& ii
b1wei
proceds. Security offixing depends upon careful r.M(diff1al2t adfiaw.',
workmanship when bedding thelugs,as they are at the ckL*aLdo
edge ofa brick joint. A cranked lug would overcomethis 2
difficulty.Not suitable when interior walling is fair faced
(see 3). Lugs should preferably beat centres which are a
multiple ofthe brickcourse dimension.
Built-in lug fixing for fair-facedInsidewail
A rebateis needed, 3. Where space between windows is big /// /
- /// //
enough, the differingplan dimensions ofinnerandouter
leaves ofa cavity wall may be obtained byeasing vertical
joint widths. Where piers between windows are small, the
outerleaf dimension should suitbrick size andtheinner / ,,/
leafmay need cutbricks or blocks'.
Screw fixing
Frames canbe screw-fixeddirect to structure.It isnot
possible todo this withcavitywall constructionas.the
screw fixing would coincide or bevery close tothevertical
dpc. Infixing toconcrete, the framecan be'screw-flxed
////
d
-
:
p(L59
p(uq&
,/// Ii
•.:I.!td
5C4W
rf
1Th4M
' Otdside
r1a5c
4a
4b
35
4c
5'
5b
36
Sill details
Bricksill - Metalsill
Lugs may be built intobrick ortile sills, 6. It is difficult to Pressedmetalsills may be used,bolted tothe frame using
hold the dpc inposition while frame is beddedandto fill lug fixing bolts, 7. As the upstanding dpcmay be damaged
the bottom section withmortar.Dpcs across bottom of while the windowis fixed, a flexible type such as polythene
window opening must lap behind vertical dpcs at jambs. is preferable.
Quck
7,
6
Concretesill
In cavity wall construction, the position offrame relative
to sill is contiolledbythejamb detail. The cavity must be
continuous immediately,underthe sill, 8.
37
t
Thesedetails were criticised by P. Ashworth,of
Stocksileld, Northumberland, for being 'ulnerable to water
and damppenetration'. He made followingpoints:
'1 Ifjambdetail, 1, is described alnsatisfactory from a
waterpenetration point ofview, sirfely the same comment
shouldapplyto details 4a, 4c and 9 because the concrete has
not been described as beingwaterproof.
2 In concrete sill detail, 8, the dpc is shown protecting the
inner leafofbrickworkfrom contact wth the 'wet' concrete
sill, but no attempt is made to protect the more vulnerable
timberwindow board from the same source ofdampness.
3 In metalsill detail, 7, theproblem oftheupstanding dpc
is referredto. Surely inview ofthe position ofthe pressed
I
metalsill the dpc only needs to cotne up to the top ofthe
concrete sub-sill anyway?
4 None ofthedetails take account ofthe effect ofcold
bridging, inner leafs are shown as concrete or brick, never
Water OL1O4
Window heads
Concrete lintels
The lintel must be positivelythroatedtoensure that water
does not run back to the vulnerable jointbetween window
andstructure,9.
c' 8°.
No fixings shouldbe made to prestressed lintels without
firstreaching agreement with the lintelmanufacturer. / • . ..
.
-
Metallintels
With steel or pressed metallintels 10 11 itis not usually
possible to screw through the window framedirect to
structure;plugs or fixing blocks are required to allow screw
fixing ata suitable position.
bkx.k5
Ca5
ps1-
10
.// //
/
v4side
11
39
9.
Tile hangingad timber cladding •
Construction
Traditional details which atone time appeared to give
acceptableresults maynot satisf modernconditions. As a
resultconstruction changesmay have been introduced
withoutall implications beingfully appreciated. For example
9in solid walling was commonly used for small buildings,
but as rooms were ventilated by chimneys andill-fitting
windows this not entirely damp-proof construction was
fairly acceptable.Now a cavity wall construction is
regarded as essential for most exposed masonry walls.
Returning to solid wall construction, with cladding on the
outside, mayseemto offer reasonable economy butnow the
a
solid wall mightbe both thinnerand of different material
from the traditional type. The resultmay be entirely
satisfactory for general walling areas but the change may
make traditional detailing arôunctopenings unsuitable.
Careful judgment ofconditions ofsite exposure is required
when considering the details shown below.
tiles, otherwise fixing with one nail only results inend tiles 2a fYs4e
drooping.
5 Ifframehead and side mcmbers are ofsimilar section the
tilingover the head projects beyond the normal tilingline
and an awkward junction occurs,3. (A skilful tiler can
effect the change by sweepingthe tiles from oneplane to
the other.) opa-ro.l ass
Preferred alternative to 2a(jamb) is 4. This overcomesmost
expos4 SS 0-ti
-
oftle drawbacks ofmethod 2 and the flashing can be made 4ik3 fswut dsp
with anysheet dpcmaterial, buta standard-depth frame
maystill not be adequate for easy and secure fixing. Ends
cq fa
b
lxd tisss-f
of
oftilingshould be pointed in amixnot stronger than 1:1:6.
Pointingmayrequire renewal at intervals but this will not d&x4'ass' I&(Wth4
1opofsb.shas.d
be critical ordifficult. The wall side ofthe frame cannot be boftas edge of
repainted. 2b -ltAw
Eaves finish
A top flashing over the tilingis sometimes recommended.
This seems unnecessary iftiles are carried above aneaves
soffit, 11.
/
The eaves soffit is unlikely to finish flushto the tiling. The
ipaceleft may provideuseful ventilation for the eaves but
the gap should not be wide enough for birdsor vermin to
enter: ie not more than 12 mm.
Witha flat roofthe top ofthe tilingmay not be protected
unless some form ofcover flashingis provided.
Externalangles
Mitred plaintiles with soakers and tilingfinishing ona - 11
timber cornerpostare seldom used now. The usualmethod
is to use special corner tiles which bond with ordinary
tilingand present no difficulties.
Abutments
When tilingfinishesagainst a projecting pier or a return
wall a flashing, 12, is usually thebest methodbut a cheap 7
job can be made by pointing only (resulting in higher
maintenance costs).
Properly done, such a flashingwould be in conjunction with
soakers.Traditionally 12a has been used at all intersections
oftilingand masonry. It costs more but is time-tested and
secure.
12
/' a
Theremay be a case for the treatment in 12ifthe
nGke-vs
zia,-i ai.t
s0-tte betwes-4.Ls
waLl
Settingout
Although horizontal spacing oftiles can be slightly
adjusted byincreasingwidthofjoints between tiles, this
increase cannotreasonably amount to more than about
20 mm in a metre length. Tile cuttingis expensiveand often
ugly and should be avoided by carefully calculating all
horizontal dimensions to suittile sizes, withsomeadditional
tolerances for openings..
Cost comparisons
Comparisons between tile hanging and other finishes
depend upon various details in addition to the direct
/
relation ofcostoftilingto other basic wall finishes.For
example: 12a
A cheaper solid wall may be substituted for a cavity wall or,
as in manyold buildings, a frame structuremay be used.
Some dpcs may be eliminated eg over lintels and in jambs,
but in some cases expensivedpcs may be required because
il__-7
ofthe tiling.
Frames may need to be thicker or deeperthan usual and
may beappreciably more expensivebecause they are
V
non-standard, and usemore material.
Horizontal dimensions to suit tilingmay diffcr from
requirements elsewhere: additional expense couldbe caused
bythe need for cuttingbricks orblocks, or for varying sizes
offrames.
13
43
h7ft1H
External corners ofbuildings will normally be made with Ill!. I/I iatslt
cornertiles, as in masonry backing. Abutments to projecting
masonry walls produce the usual timber frame/maonry wall
/Illl
(J/f//Uj__
joint problem but, ifanything, the tilinghelps to shield that
II/IL___
jomt and certainly does not add difficulties.
'i
Timber cladding on
masonrywalls -
There is a choice ofjoint shapes for board-to-board
junctions, whichmay affect the rain-proofqualities ofthe
cladding, but there areimportant differences between
vertical and horizontal boarding. Vertical boarding provides
aodra I
a flat back and flat front surface, an end finish unbroken by
jointsand no exposed end grain. Horizontal boarding can
provide flat frontandback surfaces butas it has horizontal
joints, it mayhave gaps and will then have exposed end Hoy
grain,17.
Jambs
The frame must be wide enough to allow the end board to
/ /
be nailedto it, 18. Thismethodis not suitable for
horizonthl boards because ofend grain exposure.
20 21
Read
Where the framelines withfront ofbattens, 18, cladding
can finish on the front ofthe frame, 22.
Thebottomedge should be chamfered. Anywaterthat
penetrates the cladding maybe trappedand run back
across theframehead. Full protection would mean using a
flashing.A slightimprovement to 22 would be to chamfer
the edge oftheframe,23, ifitithicknessallows andstill
leaves roomfor nailing.
22
23
24
included intable I. costs are for plainareas oftiling, not Oin(225mm) brick
'all in' costs, ie costsofcuttingaroundopenings, angle common,
Machine-made
sand-facedtiles
152
detils, eaves details, etc. Cost offinishes alone (plus battens) onbatten,
is shown in table II. The indices areindependent oftable I, 225mmbrick Itand-mad.esand-faced £13 25—l6 50 166
comm001 tiles onbattena
with machine-made sand-faced tiles taken as 100.
225mmbrick Plain concrete tiles £11 5O—1475 151
Tile hanging commons onbatten,
The labour/material ratio ofthecost oftile hanging 140mmlightweight Machine-made £10—1l 106
concrete block, sand-facedtileson
(using average tiles) is approximately 50:50, so that batters,
the tile cost (which may range from £30 to £67 per 1000) Insulated timberstud Machine-made 50—12'50
£11'
canhave a marked effect on the total. wall with plywood sand-facedtileson -
118
sheathing batten,
Slatehanging In,ulatedtimberstud 25mmsoftwood £10-35--L1250 115
The cost ofslate hanging (unless compared with wall withplywood macchboardlngor
sheathing shiplap boarding.
besthand-madetiles)may be 10to 15 per cent more than tile painted
hanging. A wide variety ofslate sizes is available. With inaulated timberstud 25mmwestern red £1250—l4-25 140
reduction in size, the labour costofslate hanging increases wall withplywood cedar matchbo.rding
while material costdecreases. sheathing or shiplap boarding
* Costs aa,t July 1974
Shingles too can be hungvertically butata cost far in- Besthand-made sand-faced tileronbattens £7-00--Cl-SO 124
Aftercostthemainfactors which determine the choice ofa Zinc(081 mm) £33 per50 kg £059 50
goodflashingmaterial are durability and flexibility. In spite £124iOperlOOkg £095 81
of its high cost lead remains the material most widely used Coppm(OS6mm)
forflashing, in both roofing work and external walling. Aluminium (091 mm) £45 SO per100 kg
commercialquality
£017 14
Cheaper alternatives exist but none has superseded lead in
termsofdurability, reliability and ease ofuse. Nuralite £394per240 x
090m eheet £027 53
£616peri0mcoil
Todaythe prices ofmetals, particularly lead and zinc, tend £061
Zincon 52
150mm wide
to fluctuate almost daily, so it would bewise always to Coats,, at July 1974
check prices orobtain quotations for specificjobs.
Aluminium
Table III gives basic prices ofmetals and materials suitable The relative pricestability ofaluminium compared with
for flashing,with lead as 100 in theindex. othermetals has recently made itmore economic.
Aluminium is malleable, ductile and durablein normal
Lead conthtions. Ease ofworking depends on composition.
Leadis the)nstsuitable flashingmaterial because it is the Commercialquality aluminium (99 per centpure (IC))is
softest ofthe thjnmon metals and has very high ductility, susceptible to work hardening. Superpurityaluminium
malleability andcörrosion resistance. Its low melting point (99 .99 per cent pure (I)) has greater ductility and is not
makes it capable ofbeingshaped with greatease with susceptible to work hardening, but it costs over twice as
simple tools and it can easily be manipulated into muchas normal quality (though less than the othermetals
complicated forms.The extreme durability oflead confirms considered). Intermediate grades are available—lB (99.5
its use as a flashing material. Its use entails no riskof per cent)and IA (998 per cent). The labouritem involved
stainingto stthounding surfaces, and isvulnerable only to in fixing aluminium flashingstendsto be higher, so that
dampcement, oak and cedarr It is ideal for complicated site the fixed cost ofa superpurity aluminium flashing comes
working, whereas copper andzinc canaotbe pre-formed. close to that ofanequivalent zinc flashing. The economics
ofthis choice may then dependon the fluctuations in the
Copper price ofzinc on the metal markets.
Copper is ductile and malleable and can bepressed or
beaten into any shape without difficulty.It is widelyused Aluminium sheet is liableto become corroded ifin contact
inspite ofbeingsecond,in costonly to lead. Like lead.it with wetwestern red cedar or Douglas fir. In polluted
can beformedto anyreuired shape and will not become atmospheres it forms an oxide film whichis not easy to
It
displaced. niay not alwaysbe suitable for flashingsto clean offand which in timewill turn into amattblack
external wall tilingbecause its greenoxidation can cause finish. In arural atniospkere thesurface will eventually
greenstaining ofthe wall with which themetalis in contact. acquire asmooth lightgrey tarnish.
Zinc Proprietaryflashing materials
Zinc is cheaper than both lead and copper but is less Nuralite is anasbestos/bitumen felt material which costs
durable and not soeasily worked. Although zinc forms a aboutthe same as metals to fix. Ifacceptable it provides an
protective film whenexposed, atmospheric pollution causes economic alternative to metalflashings.
itto weather awayrapidly. Nevertheless in urban areas a
lifeof40 years can still be expected. Zinc possesses good The price ofZincon strip (introduced in March 1972) is
working resistance to fatigue which enables it tobe used for abouthalfthat oflead and, beingsoft,ductile, easy tocut
most flashingdetai1s Zincshouldflot be fixed in direct and work, it costs thesame to fix. Zincon has an Agrément
contact with estern umbercladdings Where it is used certificatestating that the maintenance-free life will be at
with wallingmaterials containing soluble salts (notably least 25 years, longer in non-industrial areas. Its scrap
chlorides andsulphates) the embedded portions need to be value is nominal and losses from site by theft are less likely
coated with bitumen. than with lead
Maintenance
With the exception ofrepointingevery20 to25y,
brick-finishedwalls will be unlikely to incur any
maintenance coststhroughout their life. Most timber-clad
wallsrequire more periodic maintenance in theform of
painting, varnishing or staining iftheir life is to be
prolonged an4their appearance retained (see AJ Handbook
on the dsign andcleaning ofwindowsand façades:
Information sheet 2, tableI, The Architects' Journal, 7 March
1973,pages 583-85) Tiledwalls maybe more susceptible to
damage, egthroughimpact, than other finished walls and so
may incur maintenance costs at sometime. Replacing broken
tiles and matching new with old causesproblems.
47
10
Cavity wall lintels
Although thegeneral requirements for cavity wall lintels 4cishi aawy
i
are well known, faulty detailing or workmanship still 4vi44t-
5O YW$Wo4d€d
occurs, iffaUlts at this position cause rain penetration
the trouble is usually very difficult to cUre.
In additionto ensuring protection against rain penetration
c
omit
I&2AAL
aJtott t4d7t1
4%,cz*dciwa
/ 9
va'cA
Qok5
behi4 fashj
Ma-e'aA ,yM The
general pointsto be kept in mind include: vuJ.rkq,,-tt -iv da4,a
dva
Appearance (especially'ears' at each side ofopening).
Effect oflintels uponthermalinsulation (ie 'cold bridges'). _r'.
Provision ofadequate fixings for frames, blinds and curtains.
The need to consider suitable frame positions at lintels in
relation to requirements at jambs (see detail7, page 29)
and sills (see detail 11,page 52).
3
With blockworlc inner walls the normal (150 mm) rise of
flashing will not reachthefirst blockwork joint, 4*.
Eitherincrease the depthofflashing,4b or start inner wall
in brickwork or 150mm course ofblocks (usually
available), 5.
4* 4b
48
7
With the introduction ofthin presiressed concrete lintels
there is somedanger ofthe flashingbeingfinished at the
top ofthe inner lintel, Sa. It must rise up the cavity the
normal 150mm,8b. Check specificationsfor this and
check again duringsite supervision. 8a also shows the outer
lintel withoutany throating. This oftenhappens when
extralintelsneed tobe supplied quickly; they are made up
onsite, and the throating is omitted. Opinions differabout
thevalueoflintelthroatings. They are shown in BS 1239,
and are essential on exposed sites or when the wallfaciflg
above is ofanimpervious type whichresultsin Sa Sb
considerable run-off ofrain, butare advisable in all
situathyns, Sb.
'BritiihStandarda Inititnuon,2ParkStreet,LondonW.i
49
ELEYATIOJ
10$
lOb
Lintel appearance
As flashingsmust beextended at the ends oflintels,and as
they should always bebeddedwith mortarabove and
below, a thickjoint mayresultwhich does not matchwith
the normal jointing, 11. A thickflashing material increases
this effect. This occurs with all 'through-the-wall' lintels.
Withthin flashings and careful workmanship, a joint of
normal width ispossible. Alllintels should have heights
which are not a multiple ofbrick courseseg a 'two-course' 12
lintel shouldbe twbrickheights plus onlyonejoint.
,13c 13d
50
k
that inPart 10 you perpetuate the detail ofa steel angle
supporting the external brick skin across an opening ina
cavity wall. Suchangles are structural steel members, and,
since they lack any protection from weather and fire,they IL,:.,
clearly do not comply with good practice or with by-laws, in
the majority ofbuildings.
'District surveyors intheinner Londonboroughs have
refused to accept this detail for many years, hence,no doubt,
your caution'regarding acceptance by local authorities. But
surelyacceptanceby a building inspector is no automatic of bka
guarantee ofsafety, as recentevents have broughthome.' li'&id€ii "\*0 OSftS( 'oo(
15
Cecil Handisyde replied:'Eventhough,as we said,local
authority acceptance ofsuchmethods should be confirmed
before use, these angles are made andused as lintels, and so
mustbefoundacceptableby thany authorities.'
For long spanwindows, an alternative tothesteel angle
spanning full width ofopening is tobolt it back at intervals ndt+0
to the inner rc lintel. Even ifgalvanised,as it should be,
the angle still needs painting and, when painted, may
appear muchmoreintrusive on thejob than it appeared on
I/sw ser
aiok kIs(
.loLv4• Iat
drawings. Some flashingmaterials would make satisfactory r1ttie
bedding ofbricks difficult. A,thin andvery flexible btd
flashingisneeded.
18
Fixings.
BS 1239includesprovisionfor inserts in concrete lintels
toprovide fixings forwindow frames, curtaintracks,
It
blinds,etc. is not easy topredetermine all requirements
precisely or toensurethat inserts areputin accurately. For
this reason some people prefer to drill for fixings when
positions can be accurately determined. Iflintelinserts
are tobe used,lintel schedules should contain complete
information. Timber inserts should not be placed close to 19
corners or too close to reinforcement, 19. Preferably they
shouldnot be used at all; thereare manyalternatives now
availablewhichdonotshrinkorrot.
Withthin prestressed concrete lintels, fixing inserts are not
practicable. Drilledfixings are also unlikely to be suitable
and should not be made withoutchecking that theywill
not weaken the lintel.
Steellintels whichsupportboth outer and inner leaves of
cavity wallsmay produce fixing problems in soffit
positions, thoughshot-fixed or drilled and threaded fixings
maybe possible.
N
52
ii,
Window sills
Damp on inside of wall
beneath window
Although detailingmust preventrain penetration, dampness
is also caused by condensationrunningoffglazing.With
double glazing the risk is very small, butwith single
glazing trouble ofthis kindhas increased, sometimes
because ofoccupancy conditions but also because ofthe
increasing use ofdraught-proof windows and the use of / 5Jpt4l9 S(m$
largeareas ofglazing. Where thereis fairly continuous pr5%4.s 'JO1cV
c&1a4i,,
heating from a heat source immediately below the window,
condensation maybe quickly dispersedandcause little
trouble, but inother cases single-glazed windowsshould
have drainedcondensation channels.
6
53
9 10
Sill to sub-silljoint
Ifthewindow isin a forward position, as in 16, a sub-sill
is unnecessary, but awindow setback fromthe wallface
may need a sub-sill, 11. (In normal sections a woodsill
'shouldnotexceed 175 mmwidth.)
Some movement between thewoodsill and the sub-sill is
likely, and the top surface ofthe sub-sill is very exposed
/ // 7/
both to direct rain and snow and to concentrated water
run-offfrom glazing. So'water penetration between sill and
sub-sill is morelikely than at bed joint between a
projecting sill and wall below.
11
12
54
Jointed sills
With brick or other small unit sub-sill materials, joints form
a weakness even ifthe basic material is impermeable.
Water is prevented fromreaching the inner face either a i4
dpc, 14a, or by taking thecavity up to the underside ofthe
sill, l4bc. In l4ab thesub-sill, being flatand so exposed
to frost,must be ofspecial quality, whereas the sub-sill in
14c is less vulnerable.
14c
Wherelong ranges ofwindowsresultin jointed sills, wood, e*vAs -tvrzzk4 a.&,
16
in
Sill projection
Sills collect a lot ofrun-offwaterfrom glazing and it is
seldom sensible to design withouta sill projection, 18.
H.
//
,
Stone and concrete require 25-35 mmsill pmjection, 19b, -
/ /
butthisdependsuponaccuracyofwaiingandeui
.
placingthesill.
Timber requires about25 mm, 19a, but this also depends
upon wall and workmanship.
' 19*
// -
19b
Metalneedbeaslittieasl5mmifwallisstx.aightand
workmanship good 20a (steel or aluminium) 20b (zinc)
20*
6 20b
Endofsill waterrun-off
Serious disfigurement often occurs fromconcentrated water
run-off at the ends ofthe sills. Occasionallythis showsas
darkdirt streaking but more often as light colour streaking
due todirt beingwashed offthe wall. Soluble limestone
sills mayresultinconsiderable whitestreaking ifthe sill is
incorrectly detailed, 21.
21
57
22 .23
Aluminium andsteel sills do not normally have any
protection at the ends but a flashing maybe usedto
providea similar effect, 24.
On wood sills a groove aaoss the top ofthe sill may help
to prevent muchofthe run-off bydirecting waterto the
front edge, 25.
24 25
Withtile,and possibly also with brick,sills the end units
can be slightly tilted,26.
aI(&ct1 4ttls
.
26
Proprietarysills
Proprietary slatesills can beused, 27, but must have a
dpc beneath iftheyare jointedon long ranges ofwindows.
27
58
12
External,doors: position of frame
Theposition ofwindow frames in thethickness ofwalls
usually depends ontheappearance required, the external sill
andinternalwindow board size, and(in cavity walls) the
need to relateframe position and vertical dpc. (See
details 7, 10, 11, pages 29, 47 and52 respectively.)
For external doors, threshold detailing may be a deciding
factor(see detail 13, page 60). The effect offrame
position uponthepossible opening angle ofthe door can
also be veiyimportant, especiallyfor some outward
opening doors.
For composite door/window units a compromise between
conflictingrequirements may be necessary; this means that
designsfor doors andwindows mustbe considered
together throughout the building.
8
''I hookt#-
Wheredoorscannotoen much beyond 90°, a post is often A better arrangementis to form eithera solid barrier, 10, or
added as an afterthought, 9, and canbea hazard whenthe atleastan easily seen check.
door is shut.
Itis betterthat cabin hooks shouldbe fixed to thewall
than to thedoor. Builders seem todo the opposite unless
specially instructed. Hooks swing in the windand usually
do less damage to thewallthan to door finishes.
9 10
Hadap'ssolution.
60
13
External doors: thresholds
Failures ofexternal door thresholds often occur because
traditional details are usedfot unusual or changing Design check list
conditions, such asthefollowing: In orderthat reasonabledetailing may later be possible
consider the factors below.
an increasingrequirement for unobstructed access (ie a
level platform outside the door and no upstandthreshold); Severity ofsite exposure
an increasing demand for effectivedraughtexclusion; Is porch or lobby protection
possible?
doorways to exposed upperfloor balconies where the essential?
threshold must prevent not only rainpenetration to the desirable?
floor at that level, butalso leakage beneath, affecting ràoms unimportant?
below;
Is unobstructed entry (ie no step,no threshold upseand)
increased use oftypes Qfinternal floor finish which are requiredby regulations?
particularly vulnerableto damage ifwater reaches the desirable?
fixing adhesive. unimportant?
Is door inwardor outward opening?
Threshold details
Weatherboard
Outwardopening doors
Itis possible to put the step in 1 behind the door, as in 3a.
Witharamp,as 2b, an outward opening door will need .
noclearance gap below, 3b.
In1-3, draughtexclusion is assumed to be unimportant.
Where it does marter,arisingdraughtexcluder fixed to the
j : •••••
Metalweatherbarthreshold
A detail ofthe type in4is sometimes usedin an effort to
provide an 'unobstructed' entry, but it forms a nastyhazard
ra
and is especiallydangerousfor usein positions when the
door maysometimes be fixed open.Itwill keep out rain in
moderate exposures but is not proof against driving,rain or
snow. It may alsobe unsatisfactorybecause rain driving
into thespacebetween door and frame runs down the
relateand reaches the floor insidethe end ofthe weather
bar. A vulnerable floor finish immediately inside the
door is inadable.
PM
Ow,..i;etuon a,,dpt,,.
Waterpenetrationbeneath threshold
Although not immediatelyobvious, water gettingin
beneath a threshold may reach the edge or underside of
vulnerable floor finishes. OY
o4
10
63
Upperfloor problems
When anupper floor external doorway has to provide
against any risk ofwaterpenetration to rooms below, a
numberofproblems arise.
nflfl1T4
11
Er
12
4Lck
fak
00
e4 ai
fYWA of ilsp
L4M
p0
15
Whereupper floor construction is oftimber theproblems
are basically the same but with theadditional hazard of
morestructural movement. A substantial step-up inthe
structurebecomes moreimperative. A coverflashing
coming overanddownthe outside oftheasphalt shoulcibe
provided, 16. This is the most sensible type ofdetail for
balconies.
16
17
65
14
Masonrywalls: junctionoftimber Upper floors
Plaster faults Traditional construction New construction
Two faultswhich frequently occur inpresent-day building Heavy cornice prevents No cornice causes weak
are: cracking atjunctionand junction;unevenceiling line
disguises unevenceiling. shows up; no decoration
Good'break-line' for 'break-line',lb.
1 cracking ofplaster; decorations, la.
2 uneven line atjunctionofwall and ceilingplaster. This is
not alwayseasily seen at construction stage butmay
CE
become painfully obvious after decoration, especiallywhen
wall and ceiling decorationsare not similar in material
and/orcolour.
At the end ofthe contract 'defects' periodclients wantthe
faults corrected. Is itfair to blame the contractor? Poor Nati
workmanship or materials may be partially the cause, but lb
architects too have, over aperiodoftime, accepted a Floor joistsgenerous insize Economy intimber; small
number ofchanges indesign and construction that, in and closely ipaced. joists,widerspaced;
combination, cannotbe expected to be trouble free, 1, 2. deflection and movement more
likely.
Timber well seasoned. Poorly seasoned timber;more
movement resulting from
central heating.
2a 2b
3
66
'
Joist deterioration .
:r-a6- f
two-nail fixing, the eccentricity istakenas d/2 (usually
-
?5 mm).
fwo-naU fu
5a
l&
5b
67
;_
blocksthan with smaller brick size units (unless joists are
spaced to accept one standard block between each). cuctuw s,up
Where walling is designed to CP 111, Part 2, 1970,*
brik
positive supportfrom intermediate floors is often required.
The code gives examplesofhow to achieve this, 6ab. For
cavity walls the illustrated methods seem to have possible \ k U4t6'/6
Ma4 reu.Lt'
csct
bteec ais4i'Y
waA4
04i51
snags,7ab. :3'oisis 0* YLf*OM +0 'J4JA paxo1L4 +0
7a 7b
In 7b,because strapsare 6 mm thickthey need pre-drilhing.
The resultmay be that the turndown ofstrap is loose in
thecavity.
Also,Sunless the joist is packed tothe wall, the wall is able 0x5o
to move inward. a*6t4u4
3aAv #*ttJJ QC45VS
!4CXS
Since under the code bracing is required 'only at 1 2m or 3o5 i'.r5tJc,1S17
15'
Masonrywalls: junctionwith concrete upperfloors
Based uponBS CP 3: Part 2: 1970, calculated loadbearing illustrates threepoints ofdetailing:
masonry walls ofnormal cavity typeoften provide an 1 preventing damppenetration;
economic structure,especiallyfor domestic or similar 2 the use ofbrick 'tiles';
buildings with shortfloor spans. Intermediate upper floors 3 the 'cold bridge' effect resulting from loss ofcavity
ofconcrete may be required, andsometimes these may insulation value.
extendthrough to the exterior face ofthe walling, or at least Very similar pointsofdetail,would applyifthe
part-way through to support upper walling, construction included a ring beairi, but as abeam is often
Thissection does not consider the structural aspects ut deeper than floor thickness the prcblem of safely securing
'Briti,hStandard, ln,titution,2'ParkStreet,London W.1 thinbricktiles mightbe greater.
L1
type offlashingmaterial may have structural implications.
Ifcompressible'it will affect load transferdownthe walling ,procn$t 'wpr'
andmay cause most or all oftheload to be carried on the
It
inner leaf. will alsoaffect the bondoftheouter leaf to its
supportand so reduceability ofthe walling ttrresistwind
forces. This may be important onexpose4 sites and L trjolW c4tc'K
especiallyso inthe top storey ofa building wherewind
causes negative pressure and tendsto liftthe rOof
top ofthe wall (see detail 17, page 76);
- offthe
Za
Ir
RobertToy, ofFalmouth, Cornwall,suggested that the
'solid backing to supportflashing' in2b is impractical. 'If
the flashingis ofnon-rigidmaterial and does cross the cavity
atan angle (as 2b and 99 per cent ofsimilar details drawn
stt bockorcj fo o.ppos-t
a.bi'f
FvicAt
kehwi co.vv&
de3n 2b c-:: :4=tSwt
5Owo.t tt6pti4 ftce- of ta6yItaf
daoup 'Saucd to 'Ifthebottom ofthe cavity is filled with dampsand to a
ndmi- tda at
turotaa .arotMa(vL4 depthofapproximately 50mm while the wall is beingbuilt,
YOhokS ua then theaccumulation ofmortardroppings whichinevitably
pro
r
oehu occurs can easily be broken up withthe end ofa lath in the
::..g.. traditionalmannerand cleared out withthe sand via
.".-.
core-holes,leaving the bottom ofthecavity perfectly clean
Toy's suggestion.
i/i andtheflashing undamaged.'
Cecil 1andisyde replied:'This proposal is a goodone, if
69
thereis supervisioli which ensures that cavities are cleaned 'Mention shouldbe made that laps need to be s$Ied by a
out. All too often this process seems to be omitted; 50 mm. method suitable for thematerial used. (Thisisarticularly
ofsandwould thenaddtothe height ofthepile-up ofmortar difficultwith polythene.) /
droppings.' 'Consideration should be given to the formation ofcorners
and junctions which has been traditionally left to the
Comments from John Duell, of London: 'The "z" shape in bricklayer's expertise and few architects in my survey were
2b is difficult to achieve on site with the materials most used aware ofhow junctions were formed. With today's standard
today, pitchpolymer and polythene. Haunching is costly ofworkmanship andwith the increased exposure ofmedium
and rarely done today. The "z" shape makes the geometry of and high rise buildings this reliance may not be sufficient.
corners and jsnctions difficult.I would suggest an (Pre-formed corners are availablefrom somemanufacturers
"L"-shapeddp tray which requires no haunching and which or-may be made,up in a site hut.)
gives a simple geometry at corners. Italso allowsfor easier 'Theabove discussion outlines the fact that the detailing and
cleaning ofmortardroppings from the dpc. installation ofsteppeddpcs (cfhorizontal dpcs) is not
'The projection ofa dpc is indeed difficult to obtain on site. properly covered intextbooks, British Standards, BRS
I recently interviewed most ofthe architects ofrecentlarge documents, efc.'
loadbearingbrickwork projects and only in one or two cases
was an attempt made, to project the dpc. I would suggest the CecilHandisyde replied: 'Unless either stuckinto position
dpc is brought just to the face. (Incidentally, the metal drip with adhesiveor provided as pre-formed stiffmaterial, the
in figure 2b should be tucked under the dpc, not over it, and. "L"-shapeddpc is likely, in practice, to finish up more like
it would cost a fortune.) that of the original detair. Mr Duel's other comments aie a
very useful contribution.'
i1L
V.3J6Kt4P4&
ckJlTy
uigeoi,6t...
PbeR. P)cso*a4
pe. To Po ,cooJLt'
to have occurred onexposed cbastal sites in Southand Spence's solution to dampness may have structural
South-West England. It should be noted that in any but implications in ternis ofwall design.'
small domestic buildings Robert Rogerson and Philip
jA
5
Safe fixing for the brick 'tiles' is not easy to achieve. If any
load is transferred to themfrom thewall above thereis a
riskof'bowing' undercompression, 6. In concrete frame
structures this problem requires special precautions, as
differential movement offrameandwall causes difficulties.
Insuch cases the outer brick wails arenot structural and an pritc1 C4tC4'FfI ppciffatw
expansion joint at the top ofthe wall maybe needed to take
up differential movement between wall and column. -
rleec.*
1
The risk of'bowing' will increase as the heightofbrick L
tiling increases.
Thereis somedoubtaboutwhat type ofmaterial should be
used forfixing thetiles. At the present time careful work
usingordinarymortarisprobably the bestchoice.
6
Ifboth high and low building are designed at the same time
°
//
/
this possibility is likely to be foreseen and overcome by a
cavity cloak just above low rooflevel. When the low
building is added lateras an extension there is morechance
//
ofthe problem beingoverlooked.There is also much /1
greater difficulty in forming thenecessary protection to the
existingexternal wall, whichbecomes theinternalwall of
thenewextension.
//
Both levels built at sametime
Low level flat roofabuts cavitywall
to
t
u5u4Dpw15d
da tao
'ta'
bdOMAO
,
c'iaJ.
.3kjA€
OA12pM35
Whenlow andhigh levels are built at the same time,
methods are possible.
cloak, 2.
Ifthis methodis used,the.cavity cloak dpc material
should berobust and site supervisors must ensurecarein
cleaning out. Damage to the dpcmaterial may not be
it it
noticed and, even if is seen, willbe impossible to
repairwithouttaking out brickwork. A metaldpcis
probably best,butsomevery tough bituminous 2
compounds wOuld also be suitable. Laps in the dpc need to
be welted, welded or otherwise sealed together,as water
woOldrun along and drip throughanordinarylap joint.
3
73
'Assuming weillaidbricks ofaverage,or above, porosity and Cecil Handisyde replied:'This does seem tobe ratheran
a relatively softmortar,your detail mightwork, but withan expensivesolution but it doemphasise thar the costof
overlap between trays ofmore like 300mm than the 75 mm doing aproper job on this ofdetailwill always behigh.'
74
I
Kay's expensive
solution.
'/7
/ L4 i,Uxr,,d
I (c'cc'
considered,.togetherwith thetype ofwalling material, eg a
dense impermeable brickin strong mortarmay be more
susceptible to water entry through jointsthan an absorbent
<2 oY
hxrdx-et)
thywM +0 at4x-v
of nes bui k
brick in a weak mortar. //
Ifmethod2is used,some outletatthebottomofthe wall
shouldbeformedas aprecaution against build-upofwater.
Goodventilation totheupper cavity walling,would help
to dry out water, butifadequate forthis purposeitwould
significantlyreducethe thermal insulation value ofthe
cavity and would notpermitcavity fillto be used.
75
ja(cwindspeedV
ihres/seond) .
Greater Londonarea.
38m/s
EastPennines
46rn,s
.i
ii . 1 1122. 4609
038 xO-9 46
47 . 1 0 0= 47 . 1
Designwindspeed 38
=
V5 V S S ' 124 1-22
=
1 24
- 5 ms
0
S,m's 63-2rn/s 16 .0 m's 76 195 m
= 0-613basic
Equivalent
q
prrs,ure
V5 Nm' 2448 N/rn' 157 N m' 3587 Nm' 233Nm' .
4 Possibly adjustfor building life and acceptable risk C Assessment of wind loads on parts of
(S3factor)
This is a statistical exercise. The designer has to decide buildings
frQm the type ofbuilding andits probable life what degree The dynamicpressure(q) has to be multiplied by a
of risk to accept. The code suggests some cases whichmay coefficient that depends uponthe shape and sie of the
need consideration but broadly indicates that a value of building. The code employs two types ofcoefficient:
S3 = 1 is appropriate representing a probability of0 636 1 pressure coefficient(cp)
ina 50 year life, ie thereis a I in 1 6 chance ofthe design 2 force coefficient(cf)
windspeed beingexceededat least once in 50yearsbut The pressure coefficientsapplyto the particular surface of
withoutany assessment ofthe excess, ie the safety factor a building and can be combined to give the total pressure
may or may not prevent afailure. acting on the building as a whole. To avoidthis calculation
the code assesses (his directly and expresses it as a force
Comment:Will theincreasing tendency for clients to sue coefficient.
- architects on thisissuebe defensible onthe grounds of
reasonable professional judgment, or should a designer refer Table 8 ofthe code gives pressure coefficientvalues
the matterto his client—who probably would not be able (Cpe) for pitched roofs ofrectangular buildings.
to judge the situation? (See also oomment in 1 above.)
5 Determine design windspeed (V5) Consnwnts: Since the table covers pitches from 0 to 60
Design windspeed= basic windspeed (V) x S5 S2 x S3 degrees it in fact deals with flatroofs in spite of its heading.
A separate table covers monopitch roofs.
I
Comment:xamplesgiven in table may be somewhat
The term Cpe indicates external pressure. It appears
unrealistic in conibining 'all worst' possibilities and however that the effect of wind enteringthrough open
cornparng to 'all best', but chosen in that way they do doorways,windows etc can have a significanteffect, eg by
emphasise the importance ofdecisions made during this adding an upward pressure to the underside ofa roof.
stage oftheassessment. Table I shows the biildup from A description ofhow to assess this is provided inan
basic windspeed to design windspeed for two cases in the
GreaterLondon region and two similar cases in the appendix to the code. In some cases the additional pressure
may need calculation but for the peace ofmind of
proximity ofLeeds. In the S2factors the high values that architects it may be notedthat where there is only a
would relate only tp rooffinishes and their immediate
negligible probability ofa dominant opening occurring
fixings have not beenapplied in theseexamples.. during a severe storm the coefficientfor internal wind(Cpi)
B Drl1amuc wind pressure (q) should be taken as the more onerous of -+ 02 and 03.
=
The code gives a forni't1 q kV forconverting design The data in table 8 ofthe code divides buildings into
windspeed into dyiaitiicpressurpofwindwhere k is a
factordepen4iig on the type of&nits used eg, for S units threegroups according to height/width ratio. For each
group it gives.,pvessure coefficientsfor winddirections
N/rn2 and mis, the k value is 0613. Table II is a towards the long side or short side ofthe buildings. These
reproduction ofthe code table 4. values refer to the mainareas of a roof. Additional, higher
value coefficientsare given for local areas ie eaves, verges
Part2,table 4)
:
'Tabig IiValue, of qinSIunit, (N/rn') (Takenfrom (2J' Chapter V; and ridges.
Since on most sites it must be assumed that wind may
Va 0 1-0 2-0 30 40 50 60 70 8-0 90 blowfrom any direction acomposite picturemust be
formed, allocating tO each roofarea theworst Cpe that
10 61 74 89 104 120 138 i57 177 199 221
20 245 270 297 324 353 383 414 447 48i 516 could apply.
30 552 589 628 668 109 751 794 839 880 932
40 i03 1080 5i30 ii9O i240 1300 i350 1410 1470 'Complications. It must not be assumed that a satisfactory
50
60
98i
1530
22i0
i590
2280
1660
2360
1720
2430
1790
2510
i850
2590
1920
2670
1990
2750
2060
2830
2130
2920
assessment has now been achieved: uplift to eaves du
projection will need to be allowed for. Parapets and other
70 3000 ' roofprojections can raise further complications.The code
78
(a) To determine how load transfer occurs through a roof D. EvansPalmer'wrØte: 'Theonly winddamage to the
structureandtherefore what load conditions need to be buildings designed by this practice in seventy-five years
met for positions 2 or 3 above. occurred about 1956,*hen a narrow belt ofhigh wind,
(b) To determine a realistic value for various typesof which took out trees, ifted a bus shelter and a stadium roof,
fixing. Steel bolted to steel can be reasonably assessed but also lifted an asbestos: cement sheeted roof complete with
what is the value of a nail? How can a laboratory test rafters offa row ofa dozen garages and laid it upside down
result be translated to the probable value of a haphazardly on the ground. The ur1ins pulled out ofthe stonewall,
driven nail put in by a disgruntled workman operating on a breaking the bed;ointsin the process and the upward force
cold and windy site? What.s the achieved value for the not was later calculated to be ofthe order of80 lbs per sq ft.
altogether unusual 'fixing' ofa waliplate which according to
some construction books is 'bedded in mortar'? 'The client's insurers paid,without question, for direct and
consequentialdamage. This was an exceptional gale; it
The effect of roof uplift on wall stability causedmassive damage to property but not—and this is the
This discussion has been directed to winddamage to roofs point—not to the reputation ofany aichitects. And why
but the code is also aguideto design for walls. Lateral should it?
stability ofwalls is often dependent uponroofsupport. If
wind lifts the roofthen supportto walls may be lost. The 'The threat to reputation arises at two levels: call them
locationand detailed design ofroofto wall fixings must ludgment and coinpetence, judgment bearing on what we do
take this aspect into account. To what extent must roof to andcompetence on howWe do it. The "Comment" at 4
wallanchorage do more than just overcomethe roof (page 77) sums the problem up but until we sort it out it is
uplift force? not easy to know the basis on which further information on
this, and similar subjects, should be published.
Comments: Two letterssent in response to detail 17 as
originallypublished in The Architects'Journalare printed 'Easier for the architect and more profitable to (over) design
below. Correspondencewas also received from the Marley for any and every risk,even catastrophe. More difficultand
Tile Company, thawing attention to advice they have more expensiveto work to the hazy limits ofCF 3 and the
prepared intheform ofa roofing specification.This design ofthe tonstruction details themselves, to follow.'
tabulates fixingfor tiles by clipping andby nailing, taking
intoaccount building height, ite exposure andwind speed. 'My contention is that the reasonable exercise ofprofessional
judgment shouldafford a defence against an actionfor
From BernardWarren: 'With reference to winddamage negligencein all but exceptionalcircumstances, while a
to roofs, the experience ofthis corporation may be ofsome failure ofcompetence, in the implementation ofthat
interest to you. You may recall that in February 1962 there judgment, shouldbe fair game.
was a considerable amount ofdamage by wind in this city
[Sheffieldjand the city architect's department at that time 'There is a distinction between the two which, though
produced a report on the damage which occurred, together difficultto describe is, like the elephant, easy to recognise.'
with recommendationsforfutige construction which
endeavoured to reduce the risk ofsome otherdamage in
future. This report was published in The Builder on 5
October 1962.
18-'
,
'
.
Minimum falls
- Itis suggested that minimum falls should be 1:80 for
smooth surfaces and 1:60 otherwise. These are to be
achieved-falls after allowing for building inaccuracy, main,
structure and roofdeck deflectionor creep (all ofwhichare
difficulttoestimate so allowancesmust be generous).
Note,fOr example, that on floor screeds a tolerance of —-
±3mm over 3m5and ±1.0mm across largeareas is a
normal specificationallowance
Care in detailing is needed to avoid checksto the flow of
water,lab,-Zab. 2*
Thisis aproblem'which occurs not only at the eaves. It '
can happen on joints running across the fall, 2a. Ifthe lap avZ ro-'2.,
'.,
-Fu,LA
Ialicv( —: . )ae,
causes'a 3 mm upstandat a slope of1:60 the ponding ,
couldextend60 > 3 = 1 8m back from the'lap. .
Rooffallarrangements
The feasibilityofa rooffal' arrangement is often related to
roofconstructiors. Internalrwps must be related to
internalplanning and all rwp positioning affects
underground drains. Itis essential therefore to determine
roofarrangements atan earlydesign stage.
The followingdiagrams show various arrangements ofroof
falls and water disposal with noteson some ofthe
advantages and disadvantagesofeach type.
&op v€ %ps%
One-way fallto external gutter Jout
3
Structure -
Shaped beams or joists, flat ceiling, 4a.
TffttttEi,
4b
4c
Slopingslab, slopiig ceiling, 4d.
4d
Flat slab screeded, 4e.
This may resultin very thickscreed. Heavier and more
expensivethan 4d.
-Sloping slab,the
suspended ceiling, 4g.
Structurally one-way fall is most likely to suit shortor
medium span buildings. On long buildings a roofexpansion
joint can run in direction offalls.
Guttersand rwps
Minimum numberand cost. Blockageimmediately obvious.
Drains
Minimum number. None beneath building.
Appearance
Visible gutterand rwps (unless behind a parapet).
End verges slope unless detailed with a parapet or
upstand. Ifndverges are detailed with parapet r
upstand,the corner junctionwith the external gutter may
be unacceptable in appearance.
5
Two-wayfalls to external
gutters
The basic arrangement is shown in Sa. Ways of achieving !Q4VCi opw
itare described below. rwP
Structure
.
Normally used for wider spans than For similarspans,
thereis less build-upofscre.edsor firring than 3. For
Ht.
unshaped joists or beams, laying to fall is only possible if
two members meet over an intermediate support, 5b.
Expansion joints can run with falls.
i_i
rp — rwp
5a
Guttersand rwps
Gutters are double the length ofroof3. Rwps probably
more than roof3.
Drains
From two sidesofbuilding. Expensive ifto maindrain
disposal but less important withsoakaway system.
Appearance
Roof3 factors apply, but end verge slopes are two-way
balanced.
Four-wayfalls to external
gutters
The basic arrangement is shown in 6.
Structure
Except for screeded roofs, the cross fallsintroduce
complicationsbut taperedtimber or lattice steel girders
can befixed to forjn hips.
Gutter and rwps and diains
[>
rwp
i2i rp
Rwps and drains may be similar to rooftype 5. Gutter
length is increased. The tendency i's to limit gutter falls to
absolute minimum and extreme care is needed to maintain
line and avoid backfalls.
- Appearance
Gutter is similar all round. Obviates sloping verges of
types3 and 5.
83
Drains
Economicalsingle point drain, but earlyinstallation
nt involvesaccurate positioningfor later
connectionrwp.
0
Appearance
/
All verges similarj
Four-wayfalls to multiple
it,t'nal outlets
basic arrangement is shown in8.
Te
Struètu4e
Generally similar to type 7 but location ofexpansion
joint is easier.
Rwps
The introduction ofmultiple rwps does not substantiilly 8
reduce riskofwaterbuild-up from blockagebecause
outlets are separated by a highridge line(largeoutlets
again advisable).
Drains
More drainage needed than for type 7.
Appearance
All verges similar.
Structure
Simple rooffalls, but structure must be able to accommodate
gutterdepth including falls.This may be difficultifroof
trucrure is basically at rightangles to gutter.Expansion lOa
'— .
.
/I
single rwp blockage. Some reliefmay be obtained by weir
oerflows at external elids ofgutter.
Twocps>. lob, are better-.thai lOa for blockage ofouliets . I
but there'i'eitraost for rwp and drains. —— a — —
Locationofexpansion joint does not cause problems.
Both lOaaxd b are acceptable ifthere' is structural support
4
I
\
alongand unfler theinternalguttei.- lOb ,
I
19
Flat roofs: timber joist construction
Detail 18 considered in general termsthe need for falls on
'flat' roofs and how the arrangement offalls affects
efficiencyand appearance. In this detail the provision of
falls to roofs oftimber construction is considered in more
detail.
kp r4
fJJ fd
deL5
5x
Thereare three basic methods:
.1 to provide sloping roofdeck by forming falls in the
below-deck structure, I; -
6,tt LAS
LLA be de,4(
t
3 to form a level structure by using unshaped joists and
forming falls by firring timbers below the deck, 3.
3
Inhe second and third methods the basic roofconstruction
can be designed virtually withoutregardto rooffalls except
where.internal gutters are reqi.ac1 which must be able to\
runparallel to add withid the dih ofroof members. .'
Until recently, roof falls fori'ncd above deck lreel were
generally restricted to screeded roofs, 2(a system more
suitable for concrete deck systems). Lately, lightweight
wedge shaped roofinsulating slabshave been used. It is
worthnoting that to meet a need for muchhigher standards
ofthermal insulation, and as a precaution against
interstitial condensation onth underside ofimpermeable
rooffinishes, theremay well be an increase in methods
stsing thick insulation on top of a vapour barrier laid on the
roofdeck, 4. This may prqa'ide ad attractive method for LI LI—
forming rooffalls although it will be important to resist a
temptation to reduce insulation too much at the 'low' ends,
offalls. It is also offhe greatest irrtportance to ensure that
whatever light preformed insulation is used it has a surface
ofnfficient density to standup to people,walking on the
roof finish (even ifonly for maintenance). Considerable
probleois have been experienced in the use oflightweight
pQl.ystyrene screeds because ofindentation ofthe roof
TJhe remainder
beneath the roofdeck.
'
ofthis detail relates to-the fbrming ofroof
, ,
lls
Methods of forming falls below
the roof deck
1 Firring parallel with, andon top of, joists.
2 Cross firring (battensof differing thickness—or tapered,
depending on the direction offall) above joists.
3 Joists cut to falls.
(All the above provtde level cilings.)
4 Joistslaid to falls. (Resulting in sloping ceilings.)
5 Joisrs laid to falls plus suspended cross battent or other
means to obtain level ceilings.
_c
Slope is especiallynoticeable abeve.nearby window heads, 6.
Curtain tracks simply set in ceiling Will mit work.';
6-
Tv'o-way rooffalls are feasible.only ifan internal beaFing
wall or beam occurs coiivenicntly,7. Thi ftiethod-does not
providconvenenefor servicespr help roofspace
ventiFanoninherent in methods using cro.firring or
suspended ceilings. Roofventilation ii4ghtbc prvide.4 at
the ridge through. the roofcovering.
iOn lOb
p4
16
20
F!ät roofs: verges of timber joist roofs
criteria
is not feasible to illustrate all the possible roofverge
ariations but any proposed design shouldbe checked
gainst the followingcriteria:
UT
1 adequacy offixing ofroofto wallsor structureto prevent
damageto the rooffrom windsuction, 1;
Sk:nner' suggestion.
10
The introduction ofa wall plae, 11,shouldenable better
fixing ofjoists than 10 (providing the wall plate itselfis
adequately fixed down). The wall plate should ensure good
levelling ofloists to receive ceiling. With 10 method levels
may vary. Ifwall fimsh is plaster, thewall plate adds to
movement problems and reinforcement is necessary.
Although better thanlO, fixing may still be insufficientif
wall plate is secured only by bedding in mortar..
I'
On exposed sites wherewinduplift is considerable,
holding-downstrapsmay be needed, 12. The length and
frequency ofstrap fixings will depend uponwind load
assumptions (seedetail 17, page 761 /
With this arrangement the val9e ofa wall plate would he
to ensure joist levels. An alternative method is to 'strap'
downthe wall plate and fix joists to it.
I
12
1 /j
91
13
14
T'1 //
15
A vapour-proof membrane, stuckwith adhesive, would
form an effectiveseal to the cavity, 16. Roofventilation
can be obtained as required. Thermalinsulation ofwalling v4-iai -
is maintained. Longitudinal jOintsin the membrane should
belappedand sealed. Holding'down straps(as in 12)
would piercethe membrane, but this would be acceptable
y prcf AbYaMe
Clause 11(6) e. .
Detads where
to
rf
'laP
-JoHsts are at
and project
right angles
to form a roof overhang
The introductionofthe overhang, 17,exposes the roofto
more windforce, so better fixing will be necessary
-T-,-
-
1 1
K'--KKX> -
(as in 12).
S
-
'
The overhangprovides someprotection tothe upper wall -
and, except on very exposçd sites, probably obviates the - , •-
risk ofrain penetration throughsolid bridging
immediately below the roof. Closing the cavity in the way . -'
ihown would resultin aline ofexposeJ headers just under
the eaves. This change in bondappearance shouldbe
considered.
/77%
c'. ..-
'- ''
/7/
17
1
mid-span is obtained.
V//I'i "/1
7_;
Cyu.c*toi. Q//d Lke
19
93
20
21
23
94
Water overflow
Itisgenerally recognised that in the absence ola parapet
someedge upstandshould be provided topreventwind Wcs' ovapcM
blown waterspilling oveQ flat rQofverges. There is evidence
that upstands needto behigherthan they often are, 24.
Cases are known where an upstand of50 mm has been
insufficientto prevent soaking ofwalling below the verge. drake
//////
cnlcECçtfj _____________
Aisuming that construction details are adequate to prevent
water penetration into a building the consequence ofwater vece /
overspill may be: Bftnvkwjamd
/
/ ///
/// //
••
1'Increasedrisk ofdeterioration
notably to paintfinishes;
decay ofnon-durable timber fascias or cladding;
of
-
• possible trouble fromincreased risk offrost action on
masonry walling.
24
2
•• Disfigurement
extrarisk ofefflorescenceon walls;
permanent streaking, at concentrated run-off positions;
• transient discolorationegon light-coloured alcium
silicate brickwork.
Upstid debils
Supportfor upstand
Ifupstands were to occur oniy where joistsare at right
angles, fixing couldbe direct to joists with the deck stopping
against the upstand, 26. 27
An objection to this method isthat, unless the deck material
45 very stiff, deflection occurs'this may cause cracking in the'
waterproofing along the junction between deck and upstand.
The method shown in 27 is therefore preferred even where
joists are atright angles.
95
5ectm at hijs'f —
31
I
tops, presents difflculties.oSimplènailing would beadequate
__
_33
in only a fewofthe above examples. 34
kos-b f
a
I
.joa-ts 10LAs
35 36
ISVE4
c,to f*L2,
( CorlO-#M.t
fwu*9fe,o.b*
L4SO24
fvwo4a2Is 4Thig coot ±o fnf4o
37 38
I6M Ive
co,olzw,t
J_qii
I
arou bqt,,s OYStO4Ot tOI46O...1 4pTh
JooO
ba.is ruj.f
(M ou of
poubLk43 of
kO9 ftq
faLts yo* csoso ba4aos Vooo Cross a.6ss coot o fcoL4s
39 40
91
Fixing 1ecommendations
It is fairly common practice for nail flxins,and sometimes
screw fixings, to be left to thecontractor with a 'cover'
specificationsuchas 'securely fix'. In suchcases the site 0ppca 1k)
supervisor should have at least some idea ofwhat to regard
f
as acceptable.The followingexamples are intended to give
this sort guidance.
For kerbs not exceeding 50 mminthickness, opposed skew
nailing, with 100 mm headlessnails well pusheddownat
about 500 mm centres, should be adequate when fixing is to
a firmbase,41.
41
Pre-drilling andvertical screwingatabout 500 mm centres
can beused wherea screw would ensurea 'bite' ofnot less
than 35 mm into a firmbase, and where the whole length
ofthe screw is through firm material, 42. fixing cetitres
'shoul4depend on the total construction, eg on whether or
not extra stability is obtained from afascia applied to the
basiy,structure. If 150mmmaximum screw length is assumed
the deck is 25 mm,thekerb height would be 135 mm.
an
42
___t
43
FOr kerbsmore than 135mm in height some form ofmetal a1iws& scs& +o &'b
support is necessary,44. Galvanised iron angle straps of — c+ed< ads1vps
cous-isi&&k kb
w+D
L>('
LV -J no *ct cv'
I —de,k prw4e-S
00
44
98
//
Whereasjihalt or a sheet membrane is carried over a kerb p(4 np d€K
and turneddoi,n to form a drip,the drip should be well 5O26R'S
forward ofthefascia,45, 46. The bottom ofthe asphalt or
felt drip sh9uld be kepras level as possible to avoid wv5 1tp ed
concentrated drip-offpoints.
.
Criteria
Parapets.should be designed for:
.
'
Safety: height and structural stability.'
.
Copings
Coping material
Copings are exposed toextremes oftemperature and a
frequent cycleofwetting and drying They need to have a
greaterresistance to frost than'isnecessary for ordinary
walling andthey shouldbe resistant to,sulphate action.
Waterentry throughcopings
Watermay enterthroughthe copingniaterialor through
joints. Thermalmovement especiallyis likely to be
considerable and will almost inevitablyresultin water
penetration through,jointing ofbricks, stones or precast
concrete units.
P.,
Water run-off from coping may add to the risk ofdamage
andoften causes disfigurçment towalling below the
coping, especiallyifthe coping material is slightly soluble, 2.
White staining from limestone and from some precast
concrete freuent1y occurs.
2
100
Dpcbeneath copings
Unless the copingmaterialand its jointsare completely
impervious a dpc beneaththe coping is essential, 5.
The dpc should extend'at lec?stto full width ofthe wall.
Because any material above a dpc will becomewet, is it
desirable to locate the dpcimmediately beneaththecoping,
although a disadvantageis that movement inrhe coping
may loosen individual units. It is probably forthis reason
that, where copings areofsmall units such asbricks,the
dpc is sometimes placed one or two courses down. Where
this is donethematerials above dpc should all be resistant '5 pd vn
to the sulphate action and frost damage liableto occurin
situations of severe exposure; clay bricks, for example,
hoWd be to BS 32l 'special' quality. Ifa sheetmaterial
it
dpc is used should befully bedded1with mortar above,
b
and below, and preferably should ofatype with rough a
or granularsurface whichhelpsto ensure goodbonding.
305
Because mortarjointing in the projecting,part ofcopings
is very liable to fail, throughcoping movement, dribble
marks are' especiallylikely to occur onwalling beneath
joints, 6. V
8
101
jJ
atjoints, 9.. ,
13
A
102
17
22
!itched roofs: eaves
Keeping out the rain
Faults
Withpitched roofs, trouble from water in the wrong place
is most likely to occurat the eaves, 1. Faultsinclude:
1 Failure to discharge mainrun-off watercorrectly into
gutters.
2. Failure to ensure that waterreaching the top surface of
sarking is carried clear ofroofor wall structure.
3 Dampness caused by condensation. Condensation within
pitched roofspaces is likely to be worst near the eaves.
lobt
It is worth notingthat faults oftypes I and 2 have
'probably increased in frequency followingthe trend
towards low pitched roofs. One ofthe factors influencing
condensation is roofspace ventilation.
,
2
too far below roofedge. Falls should be 10 mmfor 5 m
to 6 m length.
Ip 9.Mw
The edge ofthe roofcoveringshould project well across the
gutter,4. With very small gutters theremust inevitably
be some compromise between projecting the roof too little,
and as a resulthaving waterblown back over the back of
thegutter, andprojecting too much, with resultant
overshoot ofwaterduringheavy rain. A look ata rangeof
illustrations in text books andbrochures discloses
remarkabledifferences.
r
wateron flat sarking has frozenand caused a blockage,
thus trapping waterfrom higherup with resultant leaking.
With very low pitched roofs it is difficultto avoid almost
horizontal sarking immediately behind the fascia. This
makes careful supervision very important immediately before
9a
tilingstarts.
Detaildrawings, and the work executed before battens are
covered, should be checked to ensure that at no point is
there any possibility ofwater accumulatingalongthe
length of battens, as this syilllead to subsequent rottingof
thebattenand/orwaterpenetration in the roof, 9.
bLMe5 .. f
t*%S
— /
— —i-—
pvdss
c...,i't.k t'-' +0-S*Y +0
—,------------
:' 4:i41
107
Eftect on condensation
The problem rf w44 aq,L& -ph* ra,fs ho.
'Idw.k ,,f .y
Ventilationis only one ofa numberoffactors that affect the w*tw rfz*
incidence ofcondensation irS roofspaces, but since the
difference in conditions which cause serious troubleand
thosewhich are satisfactorycan be quitesmall, the degree
ofventilation may bea decisive factor. General pointsto wl
note are shown in 10 and include: d -tt t.i4 I0
10.
I Tiledor slatedroofs are now almost always relatively
well sealed by sarking, so the general roofspacegets much
less fortuitous ventilation than do manyold roofs.
2 The volume ofroofspace is reducedwhere the roofhas
a low pitch. Water vapour reaching the roofspacetherefore
has a greater immediate effect uponroofspace air moisture
content.
Comments
• No positive eavesventilation shown but ventilation
assumed to occur(compare 11).
____ -
• No ceiling vapour check 'because naturalventilation of
roofspace is sufficient'.
• Ceiling ilation carried part way across wall but still 12
doesnot prevent eaves ventilation reaching mainroofspace.
• Top ofcavity wall not sealed. Probably the external
rende?ing will reduce rain penetration through the outer
wail but, as cavity air is still likely to have high moisture
content at times, it seems curious that the cavity is not
sealed.
Comments
• Except for the addition ofthe ceiling vapour check, this
is similar to 11.
• The reference to areas ofhighhumidity is not
In most areas, including the South, winterair is atexplicit.
high
relative humidity for muchofthe time. Thistypeof 13
weather maypersistfor longer in Scotland and some other
regions.
• Not everyone would agree with the recommendation to
omit ventilation. In fact some fortuitous ventilation
probably occurs anyway,and it may be that this proves
adequate (see the comment to illustration 11).
Low pitchedtile roof
Explanation oforiginaldrawing
In thisexample, 14, the cavity is open to the roofspace.
Comments
• No specificreference to eavesventilation.
• Top ofcavity not sealed.
• Ceiling is foil-backed plasterboard. Withother insulation pboaxd
materials in contact, the refjectivethermalinsulation value
ofthefoil is lost. Presumably therefore the foil is intended
toform avapourcheck. Ifthis is so it seems odd to allow
moistair from the wall cavity to rise unimpeded to the roof
space.
14
Steeppitchtile roof
Explanation oforiginaldrawing
Example 15 has a sealed cavity but witheaves ventilation.
Comments
• Ventilation holes specifiedby size but no information
on how many.
• Ifpositive ventilation is desired why spendmohey on
tonguedand grooved joint at soffit/fascia,when a gap
between a plainedged soffit and fascia will provide
ventilation?
• Note that no &iling or otherthermalinsulation is shown.
15
109
Comments
• Having ventilated the eaves and sealed the wall cavity, it
seems odd to have carriedbrickworkup as beam filling.
This would, ifsolidly carried out, prevent the eaves
ventilation reaching the mainroofspace.
• There is no specific adviceon how to preventwater
vapour from rooms penetrating the ceiling. A vapour check
at ceilinglevel is presumably intended. Ceiling vapour
checksare not completely effectivebarriers, and for this
reason the mainroofspace would have been better ifopen
to benefit from the eavesventilation.
16b
Roofventilation
Explanation oforiginaldrawing
Ifroofspace is ventilated, insulation should be atceiling
level, 8. For goodventilation allow2000 mm2 ofopening
per metre run ofeaves. The ceiling should be free from
gaps orholes.
Comments
• Ventilation recommendationis for twice the quantity
suggested by pther examples (11, 13, 15).
• No proviso aboutnot ventilating in Scotland or 17
similar weather regions.
• Reference to theceiling beingfree from gaps or holes
presumably does not implythe higher requirement of
including a positive vapourcheck at ceiling level.
roofe soe
o4o rn'
L&*t Ias.ptkeI
based on feedback information. Pending this (and as shoM be siev
summarised in 18) it is suggested that:
ea.er5 'koS o.t
leaoi- shouAd be