LOCATION GC 4 WKO-VIEC CONTAINER
PUNCH CATEGORY A,B AND C
SL. NO DESCRIPTION CATEGORY CLOSED BY AND DATE REMARKS
AGI KOC
In outdoor unit addistional JB (IP66) box installed, no access to open oil inspection. Should change JB
1 A
location
2 AC NO 2 condnesing unit not explosion proof - replace with expolsion proof unit. A
3 Indoor units installed above panel, relocate indoor units. A
4 Main untility panel reset push button operation tag should be provided in panel. A
5 Approved drawing (unit selection and approved units capacity)should be provided at site. B
6 Utility panel indication lamps not working - should be replaced. A
7 Need apply, change over program while one unit trip by any fault - must be change over stand by unit. A
8 Louver with filter as per approved schedule need fix in let pressurization fan. A
9 Need recheck with full load operation time. C
10 Cable tray cover must be fix in all cable trays. B
11 Drain water pipe work incomplete - should be completed. A
12 Operation training with all change over, trip, fault details with vendor to maintenance team at site. C
Warranty period certificate spare parts such as PC board,contactor, condenser fan motor,blower motor blade
13
and blower must be supplied to KOC store.