This document lists 13 items in three categories (A, B, C) regarding issues found at an outdoor container unit. Key issues include an additional junction box that prevents access for oil inspections, a non-explosion proof condensing unit that needs replacing, indoor units installed above a panel that need relocating, and missing or incomplete documentation, labelling, and training.

Uploaded by

ahmadtaiyabi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
40 views1 page

Location GC 4 Wko-Viec Container: Punch Category A, B and C

This document lists 13 items in three categories (A, B, C) regarding issues found at an outdoor container unit. Key issues include an additional junction box that prevents access for oil inspections, a non-explosion proof condensing unit that needs replacing, indoor units installed above a panel that need relocating, and missing or incomplete documentation, labelling, and training.

Uploaded by

ahmadtaiyabi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd

LOCATION GC 4 WKO-VIEC CONTAINER

PUNCH CATEGORY A,B AND C


SL. NO DESCRIPTION CATEGORY CLOSED BY AND DATE REMARKS

AGI KOC

In outdoor unit addistional JB (IP66) box installed, no access to open oil inspection. Should change JB
1 A
location
2 AC NO 2 condnesing unit not explosion proof - replace with expolsion proof unit. A

3 Indoor units installed above panel, relocate indoor units. A

4 Main untility panel reset push button operation tag should be provided in panel. A

5 Approved drawing (unit selection and approved units capacity)should be provided at site. B

6 Utility panel indication lamps not working - should be replaced. A

7 Need apply, change over program while one unit trip by any fault - must be change over stand by unit. A

8 Louver with filter as per approved schedule need fix in let pressurization fan. A

9 Need recheck with full load operation time. C

10 Cable tray cover must be fix in all cable trays. B

11 Drain water pipe work incomplete - should be completed. A

12 Operation training with all change over, trip, fault details with vendor to maintenance team at site. C

Warranty period certificate spare parts such as PC board,contactor, condenser fan motor,blower motor blade
13
and blower must be supplied to KOC store.