Line distance protection REL670
Relion® 670 series Ver. 2.0
Features
• Fully IEC 61850 compliant, Edition 1 and Edition 2
• Extensive I/O capability
• Protection, monitoring and control integrated in one IED
• Extensive self-supervision including analog channels
• Six independent parameter setting groups
• Ethernet interface for fast and easy communication with
PC
• Large HMI for visualization of single line diagrams
• Cyber security support for compliance to NERC CIP and
IEC 62351-8
• Protection of several primary objects with a single IED
Pre-configured solutions
• Pre-configured and type-tested solutions for:
− − Single breaker with single phase tripping
− − Single breaker with three-phase tripping
− − Multi-breaker with single phase tripping
− − Multi-breaker with three-phase tripping
− − Single breaker for high impedance earthed systems
− − Broken conductor check
Most important protection functions −− Thermal overload protection
• 6 zone full-scheme high-speed line distance protection −− Breaker failure protection
− − Quadrilateral characteristic −− Stub protection
− − Mho characteristic −− Pole discordance protection
− − Series compensated lines • Power functions
− − Scheme communication logic − − Directional under- and overpower protection
− − Load encroachment discrimination • Voltage
− − Selective phase selection and automatic switch on to − − Two step phase- and residual overvoltage protection
fault logic with definite and inverse time characteristics
− − Current reversal and weak end infeed logic −− Two step undervoltage protection with definite and
− − Power swing detection and blocking inverse time characteristics
− − Phase preference logic −− Radial feeder protection
− − Pole slip protection −− Overexcitation
• 3-phase high impedance differential protection for tee- −− Loss of voltage check
feeders • Power system supervision
• Current − − Loss of voltage check configured based on
− − Instantaneous phase overcurrent protection undervoltage protection
− − Instantaneous residual overcurrent protection −− Dead line detection included in fuse failure
− − Four step phase overcurrent protection with definite supervision and switch on to fault logic
and inverse time characteristics • Secondary system supervision
− − Four step residual directional overcurrent protection − − Fuse failure supervision
with definite and inverse time characteristics −− Fuse supervision based on voltage differential
− − Four step directional negative sequence overcurrent principle
protection −− Current circuit supervision
− − Directional residual overcurrent protection with • Frequency functions
scheme communication logic − − Under- and overfrequency protection
− − Sensitive directional earth-fault protection −− Rate-of-change frequency protection
• Multi-purpose function Hardware
−− Multi-purpose filter with possibility to detect, alarm, • 1/1 x 19”, 3/4 x 19” or 1/2 x 19”, 6U height case selected
and trip for special operating conditions, e.g. SSR according to the number of required I/O modules
−− General current and voltage protection • Power supply modules from 24 to 250 V DC ± 20%
−− Voltage controlled/restraint overcurrent protection • TRM input module with 12 analog inputs and optional
measurement transformers
Logic • Up to 14 I/O modules in 1/1 x 19” case
• Tripping logic • Binary input module with 16 inputs
• Trip matrix logic • Binary output module with 24 outputs
• Extensive logic block library for application customization • Static binary output module with 6 static and 6 change-
over outputs
1MRK506345-SEN 04/2014
Monitoring • Binary input/output module with 8 inputs and 12 outputs
• Adjustable breaker monitoring with capability to handle • mA input module with 6 transducer channels
multiple breaker types • Connector types: compression type or ring-lug type
• Disturbance recorder • Accurate time-synchronization through GPS time module,
−− 100 disturbances SNTP, DNP 3.0 , IEC 60870-5-103, or IRIG-B-module
−− 40 analog channels (30 physical and 10 derived) • Remote end data communication modules for C37.94,
−− 96 binary channels direct fiber up to 130 km or via multiplexer
• Event list for 1000 events • Supports highest EMC requirements
• Disturbance report • Independent laboratory certified
• Event and trip value recorders
• Fault locator Accessories
• Event counters • COMBITEST test system
• Supervision of AC and mA input quantities • COMBIFLEX auxillary relays
• Large HMI with virtual keyboard, function push buttons, • Mounting kits
and three color LED indications with alarm descriptions
Documentation
Measurements • Role based documentation for high efficiency in
• U, I, P, Q, S, f and cos ϕ engineering, commissioning, operations and maintenance
• Frequency measurement with accuracy of ± 2 mHz
• Inputs for mA measuring
Technical details are available in the REL670 Product
Metering Guide.
• Energy metering function for energy statistics
• Pulse counting support for energy metering
For more information please contact:
Control functions ABB AB
• Autorecloser for single or multiple breakers Substation Automation Products
• Synchronizing, synchrocheck and energizing check 721 59 Västerås, Sweden
• Control and interlocking for up to 15 switching devices Phone: +46 (0) 21 32 50 00
• Selectable operator place allocation
[Link]/protection-control
• Several alternatives for reservation functionality
• Software based multiple position selector switches
Communication Note:
• IEC 61850-8-1 including GOOSE messaging We reserve the right to make technical changes or modify the
• IEC 62439-3 parallel redundancy protocol (PRP) contents of this document without prior notice. ABB AB does
• IEC 61850-9-2 LE Process bus not accept any responsibility whatsoever for potential errors
• IEC 60870-5-103 serial communication or possible lack of information in this document.
• DNP 3.0, SPA, LON protocols We reserve all rights in this document and in the subject
• Remote communication for transfer of up to 192 binary matter and illustrations contained herein. Any reproduction,
signals in each direction disclosure to third parties or utilization of its contents – in
whole or in part – is forbidden without prior written consent of
Engineering, testing, commissioning, and maintenance ABB AB.
• Forcing of binary outputs
• Protection and control IED manager PCM600 for setting, © Copyright 2014 ABB. All rights reserved.
configuration and disturbance handling
Scan this QR code to visit our website