Powered by Cummins
Model:YN(S)-125C
*Drawing above for illustration purposes only
Ⅰ . GENERAL DATA
Standby Power kVA/kW 125 100
Prime Power kVA/kW 114 91
Frequency Hz/rpm 60 1800
Voltage V 220 127
Current A 298
Connection / 3P 4W/Y
Rated Power Factor / 0,8
Open Type(L×W×H) mm 2200x940x1564
Open Type(Weight) kg 1170
Base tank capacity Gal 71,4
[Link]
Silent Type(L×W×H) mm 3200x1100x1470
Silent Type(Weight) kg 1780
Base tank capacity Gal 60,8
Noise level@1m(dBA) 75
Noise level@7m(dBA) 66
■Available for voltages 400/230V, 480/277V, 380/220V, 440/254V, 416/240V,220/127V, 208/120V
■All datas based on ISO 3046, alteritude 1000m (3281ft), barometric pressure 100kPa (29.53inHg), air temperature 25℃
(77°F), relative humidity 30%.
■Please contact with YANAN engineer for correct generator capacitity selection when the load application can't meet with
the standard reference.
■YANAN diesel generators comply with standards :ISO8528,ISO 14000,ISO3046,GB755,BS5000,VDE0530,IEC34-1
All data is subject to change without notice, sorry for inform. Page 1,of 6
Ⅱ . ENGINE DATA
Engine Model 6BT5.9-G2 Engine power 110 kW
Aspiration Turbochanger Displacement 5,9 L
Type In-line Bore×Stroke 102×120 mm
No. of Cylinders 6 Compression Ratio 17.3:1
Governor Type Electronic Governor Rated Speed 1800 RPM
■ Fuel System
ASTM D975 No.2-D or
Fuel # Injection System BYC A
BS2869 1998 Class A1, A2
Prime Power Fuel Standby Power Fuel
2,38 US gal/hour 8,26 US gal/hour
Consumption(25%) Consumption(100%)
Prime Power Fuel
3,80 US gal/hour
Consumption(50%)
Prime Power Fuel
5,4648 US gal/hour
Consumption(75%)
Prime Power Fuel
7,52 US gal/hour
Consumption(100%)
■ Lubrication System
Lub Oil Capacity 16,4 L Lub Oil Consumption 0,086 l/h
Lub # API CF-4 15W40 [Link] 121 ℃
■ Coolant System
Coolant Capacity 22,4 L Max. Top Tank Temp. 100 ℃
Std. Thermostat
82 - 95 ℃ Fan Drive Type Shaft drive
(Modulating) Range
[Link]
[Link]
Exhaust air volume N/A m3/min Fan Power 3 kW
■ Air Intake System
Air intcke capacity 6.66/6.72 m3/min Air Pressure 3,7 kPa
■ Exhaust System
Exhaust Gas Flow 18.72/19.14 m3/min [Link] Pressure 10 kPa
Exhaust Gas Temp。 ≤577 ℃ Exhaust pipe size φ76 mm
■ Starting System
Start Mode DC24V Electric start Battery 120x2 Ah
All data is subject to change without notice, sorry for inform. Page 2,of 6
Ⅲ. ALTERNATOR DATA
Alternator Model TAL-A44-E Rate Power 109/137 kW/kVA
PF. 0,8 Voltage 220/127
Phase 3 Frequency 60 Hz
Connection 3P 4W/Y Bearing Single Bearing
Winding Pitch 2/3 Proteccion Class IP23
Insulation Class H/H Efficiency 89,40%
Tel. Influence TIF:<50 Voltage Regulation ±1.0%
Harmonic Coefficient THF:<3.5% AVR R120
Voltage Adjust Scope ≥±5% Excitation System Self excited
Ⅳ . STANDARD CONFIGURATION
Engine Cummins, including air filters, fuel filters, oil filter, starting motor and charging alternator etc.
Alternator LEROY SOMER brushless AC alternator
Radiator 50℃, fan protective shroud
<500KW: base mounted fuel tank, anti-vibration pads, battery holder
Base frame
≥500KW: channel steel base frame, anti-vibration pads, battery holder
Circuit Breaker ≤1250A : Molded case circuit breaker(MCCB)
Control System DEEP SEA 4520
[Link]
Start Battery Dry charged battry, available for 6 times starts under standard condition; connection cables.
[Link]
Installation Accessories Bellow, Elbow and flange, Exhaust silencer, etc.
Tool YANAN standard
Documents Electric drawing, operation & maintenance manual, certification etc.
All data is subject to change without notice, sorry for inform. Page 3,of 6
Ⅴ . OPTIONAL CONFIGURATION
Engine accessories ◇Heavy-duty air filter ◇Coolant heater ◇Lub oil heater ◇Fuel and Water Separator
◇Stamford ◇YANAN SLG ◇Marathon ◇Anti condensation heater ◇PMG kV
Alternator and
accessories
◇High voltage
◇50℃radiator ◇Heat exchanger + water cooling tower + External water circulation pumping
system
Cooling system
◇Remote horizontal water tank system
◇AMF ◇Parallel ◇Practical type in low temperature environment ◇Control Screen Heater
Control System
◇Other(Comap、DEIF)
Circuit Breaker ◇3/4 poles ◇Fixed/handcart type ◇Electric mechanism
Automatic Transfer
◇ATS cabinet
Swtich
◇Nickel-cadmium battery ◇Maintenance-free battery ◇Power charger and selector
Start Battery
◇Charging current meter
External Fuel Tank ◇500L ◇1000L ◇1500L ◇2000L ◇2500L ◇3000L ◇4000L ◇5000L
Others
[Link]
[Link]
All data is subject to change without notice, sorry for inform. Page 4,of 6
Ⅵ . CONTROL SYSTEM DATA MODEL DSE4520
■ Main feature
Electronic engine J1939 (CAN)(only DSE4520) and non-electronic engine(only DSE4620)
and alternator sensing engine support for diesel, gas and petrol engines
all in one variant. With a number of flexibleinputs, outputs and protections, the modules
can be easily adapted to suit a wide range of applications.
■ Key Function
▲Utility voltage sensing ▲3 engine maintenance alarms ▲Alternative configuration
▲Generator/load powermonitoring ▲Engine speed protection ▲Alarm including common alarm,
(kW, kV A, kV Ar, pf) ▲Engine pre-heat common electric and common shutdown
▲Generator overload protection(kW) ▲Multiple date and time scheduler ▲LCD and LED alarm indication
▲Efficient power save mode ▲Engine idle control for starting & ▲Configurable event log (50)
▲4 configurable DC outputs stopping ▲Heated display option available
▲3configurable analogue/digital ▲Fuel pump control ☆For more information, please visit the
inputs ▲Battery voltage monitoring official website
▲4configurable digital inputs ▲Start on low battery voltage
▲Configurable staged loadingoutputs ▲Configurable remote start input
▲Support for 0-10 V & 4-20 mAoil ▲Battery voltage monitoring
pressure sensors ▲Start on low battery voltage
[Link]
[Link]
Ⅶ . WARRANTY POLICY
[Link] for one year or 1000 hours (accord to whichever reach first)from ex-factory date. Refer to
《YANAN Diesel Generator Warranty Manual》 for more details.
[Link] parts( filters), incorrect man-made operation, maintenance failures are excluded from the warranty policy
All data is subject to change without notice, sorry for inform. Page 5,of 6
Ⅷ . DRAWING (for illustration purposes only)
[Link]
[Link]
All data is subject to change without notice, sorry for inform. Page 6,of 6