File 1620307458
File 1620307458
Hybrid Inverter
User Manual
Contents
1. Safety Introductions ……………………………………………… 01
2. Product instructions ……………………………………………… 01-04
2.1 Product Overview
2.2 Product Features
2.3 Basic System Architecture
3. Installation …………………………………………………………… 04-16
3.1 Parts list
3.2 Mounting instructions
3.3 Battery connection
3.4 AC Input/Output Connection
3.5 PV Connection
3.6 CT Connection
3.7 Earth Connection(mandatory)
3.8 WIFI Connection
3.9 Wiring System for Inverter
3.10 Single phase parallel connection diagram
3.11 Three phase Parallel Inverter
4. OPERATION …………………………………………………………… 17
4.1 Power ON/OFF
4.2 Operation and Display Panel
5. LCD Display Icons …………………………………………………… 18-27
5.1 Main Screen
5.2 Solar Power Curve
5.3 Curve Page-Solar & Load & Grid
5.4 System Setup Menu
5.5 Basic Setup Menu
5.6 Battery Setup Menu
5.7 System Work Mode Setup Menu
5.8 Grid Setup Menu
5.9 Generator Port Use Setup Menu
5.10 Advanced Function Setup Menu
5.11 Device Info Setup Menu
6. Mode …………………………………………………………………… 27-29
7. Fault information and processing ………………………………… 29-31
8. Limitation of Liability ………………………………………………… 32
9. Datasheet ……………………………………………………………… 32-33
1. Safety Introductions
・This chapter contains important safety and operating instructions. Read and keep this
manual for future reference.
・Before using the inverter, please read the instructions and warning signs of the battery
and corresponding sections in the instruction manual.
・Do not disassemble the inverter. If you need maintenance or repair, take it to a
professional service center.
・Improper reassembly may result in electric shock or fire.
・To reduce risk of electric shock, disconnect all wires before attempting any maintenance
or cleaning. Turning off the unit will not reduce this risk.
・Caution: Only qualified personnel can install this device with battery.
・Never charge a frozen battery.
・For optimum operation of this inverter, please follow required specification to select
appropriate cable [Link] is very important to correctly operate this inverter.
・Be very cautious when working with metal tools on or around batteries. Dropping a
tool may cause a spark or short circuit in batteries or other electrical parts,even cause
an explosion.
・Please strictly follow installation procedure when you want to disconnect AC or DC
terminals. Please refer to ”Installation” section of this manual for the details.
・Grounding instructions - this inverter should be connected to a permanent grounded
wiring system. Be sure to comply with local requirements and regulation to install this
inverter.
・Never cause AC output and DC input short circuited. Do not connect to the mains
when DC input short circuits.
2. Product Introduction
This is a multifunctional inverter,combining functions of inverter, solar charger and
battery charger to offer uninterruptible power support with portable size. Its comprehensive
LCD display offers user configurable and easy accessible button operation such as battery
charging ,AC/solar charging, and acceptable input voltage based on different applications.
- 01 -
2.1 Product Overview
1
2
3
6
4 7
5
8
9
10
11
12
13
14
15
16
1: Inverter Indicators 7: DRMs Port 13: Power on/off button
2: LCD display 8: Parallel port 14: DC Switch
3: Function Buttons 9: Function Port 15: PV input with two MPPT
4: Battery input connectors 10: Generator input 16: WiFi Interface
5: RS 485 Port 11: Load
6: CAN Port 12: Grid
- 02 -
2.2 Product Features
・ -220V Single phase Pure sine wave inverter.
・ - Self-consumption and feed-in to the grid.
・ - Auto restart while AC is recovering.
・ - Programmable supply priority for battery or grid.
・ - Programmable multiple operation modes:On grid,off grid and UPS.
・ - Configurable battery charging current/voltage based on applications by LCD setting.
・ - Configurable AC/Solar/Generator Charger priority by LCD setting.
・ - Compatible with mains voltage or generator power.
・ - Overload/over temperature/short circuit protection.
・ - Smart battery charger design for optimized battery performance
・ - With limit function,prevent excess power overflow to the grid.
・ - Supporting WIFI monitoring and build-in 2 strings of MPP trackers
・ -Smart settable three stages MPPT charging for optimized battery performance.
・ -Time of use function.
・ -Smart Load Function.
・ -Parallel function On-Grid&Off-Grid.
- 03 -
AC cable DC cable
WiFI
GPRS
CT
3. Installation
3.1 Parts List
Check the equipment before installation. Please make sure nothing is damaged in the
package. You should have received the items in the following package:
1 2 3 4 5
6 7 8 9
No Description Qty
1 SUN-3.6K/5K-SG01/03LP1-EU hybrid inverter 1
2 Stainless steel mounting screws M6*12 2
3 Stainless steel expansion bolts M8*80 4
4 User manual 1
5 WiFi plug 1
- 04 -
6 Current transformer (Optional) 1
7 Battery sensor 1
8 L-type Hexagon wrench 1
9 Wall mounting bracket 1
Chart 3-1 Parts List
3.2 Mounting instructions
Installation Precaution
This Hybrid inverter is designed for outdoor use(IP65),Please make sure the installation
site meets below conditions:
・ Not in direct sunlight
・ Not in areas where highly flammable materials are stored.
・ Not in potential explosive areas.
・ Not in the cool air directly.
・ Not near the television Antenna or antenna cable.
・ Not higher than altitude of about 2000 meters above sea level.
・ Not in environment of precipitation or humidity(>95%)
Please AVOID direct sunlight, rain exposure, snow laying up during installation and
operation. Before connecting all wires,please take off the metal cover by removing
screws as shown below:
- 05 -
・ The ambient temperature should be between -25~60℃ to ensure optimal operation.
・ Be sure to keep other objects and surfaces as shown in the diagram to guarantee
sufficient heat dissipation and have enough space for removing wires.
≥500mm
≥500mm
For proper air circulation to dissipate heat, allow a clearance of approx. 50cm to the side
and approx.50cm above and below the [Link] 100cm to the front.
[Link] that the position of the installation holes on the wall (A, B, C, D) are the same
position of the install plate, and the mounting level is guaranteed.
3. Hang the inverter to the top of the mounting rack and then use the M4 screw in the
accessory to lock E and F to ensure that the inverter does not move.
- 06 -
Inverter hanging plate installation
- 07 -
All wiring must be performed by a professional person.
Connecting the battery with a suitable cable is important for safe and
efficient operation of the system. To reduce the risk of injury, refer to
Chart 3-2 for recommended cables.
3. In case of children touch or insects go into the inverter,Please make sure the inverter
connector is fasten to waterproof position by twist it clockwise.
- 08 -
3.3.2 Battery temperature connection
1 2
Temp. CT
- 09 -
3.4 AC Input/Output Connection
・ Before connecting to AC input power source,please install a separate AC breaker
between inverter and AC input power [Link] will ensure the inverter can be securely
disconnected during maintenance and fully protected from over current of AC [Link]
recommended of AC breaker is 25A for 3.6kw and 32A for 5KW.
・ There are three terminal blocks with “Grid”“Load”and “GEN”markings.
Please do not misconnect input and output connectors.
GEN PORT
Load
PE
L Grid
N
- 10 -
Be sure that AC power source is disconnected before attempting to wire it to
the unit.
3. Then,insert AC output wires according to polarities indicated on the terminal block and
tighten terminal. Be sure to connect corresponding N wires and PE wires to related
terminals as well.
4. Make sure the wires are securely connected.
5. Appliances such as air conditioner are required at least 2-3 minutes to restart because it
is required to have enough time to balance refrigerant gas inside of [Link] a power
shortage occurs and recovers in short time,it will cause damage to your connected
[Link] prevent this kind of damage,please check manufacturer of air conditioner
if it is equipped with time-delay function before [Link],this inverter will
trigger overload fault and cut off output to protect your appliance but sometimes it still
causes internal damage to the air conditioner.
3.5 PV Connection
Before connecting to PV modules,please install a separately DC circuit breaker between
inverter and PV [Link] is very important for system safety and efficient operation to
use appropriate cable for PV module [Link] reduce risk of injury,please use the
proper recommended cable size as below.
- 11 -
It is requested to use PV junction box with surge protection. Otherwise,it
will cause damage on inverter when lightning occurs on PV modules.
Chart 3-5
- 12 -
3.6 CT Connection
Inverter
3
4
CT
L
Grid
- 13 -
Earth-BAR
Inverter
Ground
PE
N
3.9 Wiring System for Inverter
L
Breaker
CAN Grid
- 14 -
3 Breaker
Solar Battery 4 CT
Breaker
Breaker
Generator
Arrow pointing
or
to grid
Microinverter
or
Loads
Inverter
No.3
DSM 485 DSM CAN DRMs (slave)
Parallel A Parallel B
Ground
Inverter
Inverter
No.2
(slave)
PE wire
Inverter
No.1
N wire
(master)
L wire
L
N
+ - PE
CAN
Battery pack
Grid
Load
- 15 -
CAN L wire N wire PE wire
DSM 485 DSM CAN DRMs
CAN
L3
3.11 Three phase Parallel Inverter
L2
L1
+ - N
PE
- 16 -
Battery pack
L1
L2
L3
N
PE
Grid
4. OPERATION
4.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected well,simply press
On/Off button(located on the left side of the case) to turn on the [Link] system without
battery connected,but connect with either PV or grid,and ON/OFF button is switched off,
LCD will still light up(Display will show OFF),In this condition,when switch on ON/OFF
button and select NO battery,system can still working.
- 17 -
5. LCD Display Icons
5.1 Main Screen
The LCD is touchscreen,below screen shows the overall information of the inverter.
05/28/2019 [Link]
0 4.50 5 0 -1.54 5
KW KW
ON
25%
0 -1.40
KW
5 0 1.46
KW
5
[Link] icon in the center of the home screen indicates that the system is Normal operation.
If it turns into “comm./F01~F64” ,it means the inverter has communication errors or
other errors,the error message will display under this icon(F01-F64 errors,detail error info
can be viewed in the System Alarms menu).
[Link] the top of the screen is the time.
[Link] Setup Icon,Press this set button,you can enter into the system setup screen which
including Basic Setup,Battery Setup,Grid Setup,System Work Mode,Generator port use,
Advanced function and Li-Batt info.
[Link] main screen showing the info including Solar,Grid,Load and [Link] also
displaying the energy flow direction by [Link] the power is approximate to high
level,the color on the panels will changing from green to red so system info showing
vividly on the main screen.
・ PV power and Load power always keep positive.
・ Grid power negative means sell to grid,positive means get from grid.
・ Battery power negative means charge,positive means discharge.
- 18 -
5.1.1 LCD operation flow chart
Inverter Page
Main Screen
Battery Page BMS Page
Battery Setting
Grid Setting
System Setup
Gen Port Use
Basic Setting
Advanced Function
Device info
- 19 -
5.2 Solar Power Curve
Power2: 0W
- 20 -
Li-BMS
U:50.50V
I:-58.02A
Li-BMS
Power: -2930W Volt Curr Temp SOC Energy Charge Fault
Volt Curr
1 50.38V 19.70A 30.6C 52.0% 26.0Ah 0.0V 0.0A 0|0|0
Temp:30.0C
Li-BMS 2
3
50.33V
50.30V
19.10A
16.90A
31.0C
30.2C
51.0%
12.0%
25.5Ah
6.0Ah
53.2V
53.2V
25.0A
25.0A
0|0|0
0|0|0
Sum
4 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0 Data
5 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
6 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
7 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
8 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
This is Battery detail page. 9 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
Details
10 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
11 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0 Data
if you use Lithium Battery,you can enter BMS page. 12
13
0.00V
0.00V
0.00A
0.00A
0.0C
0.0C
0.0%
0.0%
0.0Ah
0.0Ah
0.0V
0.0V
0.0A
0.0A
0|0|0
0|0|0
14 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
15 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
CANCEL Day Month Year Total CANCEL Day Month Year Total
CANCEL Day Month Year Total CANCEL Day Month Year Total
Solar power curve for daily,monthly,yearly and total can be roughly checked on the LCD,
For more accuracy power generation,pls check on the monitoring [Link] the up and
down arrow to check power curve of different period.
- 21 -
5.4 System Setup Menu
System Setup
This is System Setup page.
System Work Mode
Battery
Setting Gen Port
Grid Setting Use
Basic Advanced
Setting Function Device Info.
Basic Setting
This is Basic Setup page.
Time Syncs Beep Auto Dim
Hour Minute
24-Hour 09 15
- 22 -
Battery Setting This is Battery Setup page. ① ③
Start 30% 30% ② Start =30%---It indicates that the Generator will start when
the Battery capacity is less than 30% in Off-grid mode.
A
① 40A 40A
Batt
Set2 A = 40A---It indicates the Current that the Generator
Gen Charge Grid Charge charges the Battery after starting.
Battery Setting
Lithium Mode--This is BMS [Link] reference the
document(Approved Battery).
Lithium Mode 00
Shutdown 10%--It indicates the inverter will shutdown if
Batt
Shutdown 10% Set3 the SOC below this value.
Low Batt 20% --It indicates the inverter will alarm if the
Low Batt 30%
SOC below this value.
Restart 80% Restart 40% --It indicates the restart level when inverter
shutdown.
- 23 -
Battery Setting There are 4 stages of charging the Battery . ①
Float V ① 55.2V Shutdown ③ 41.0V
This is for professional installers,you can keep it if you
Absorption V 57.6V
Low Batt 45.0V
Batt do not know. ②
Restart 52.0V Set3
- 24 -
5.8 Grid Setup Menu
Grid Setting
Please select the correct Grid Mode in your local area. If
Grid Mode General Standard
you are not sure, please choose General Standard.
UL1741& IEEE1547
Grid
CPUC RULE21 Set1 Please select the correct Grid Type in your local area,
SRD-UL-1741 otherwise the machine will not work or be damaged.
Grid Type 220V Single Phase
120/240V Split Phase
120/208V 3 Phase
120V Single Phase
Grid Setting
For California only.
Q(V) FW VW
Grid Setting
For California only.
L/HVRT L/HFRT
- 25 -
5.9 Generator Port Use Setup Menu
GEN PORT USE Generator Input: use Generator
SmartLoad Output: if the SOC is up than “ON”and solar power
Mode is high than 1000W. the inverter will open smartload.
Generator Input On Grid always on: mean when have Grid, the smartload will always on.
Rated Power PORT Micro Inv Input: Inverter will open Microinverter. if the SOC is
8000W Set1
below the“ON”and close if the SOC is up than the“OFF”.
SmartLoad Output On Grid always on
AC Couple Fre High: If choosing“Micro Inv input”, as the
Power AC Couple Fre High
battery SOC reaches gradually setting value (OFF), During the
process, the microinverter output power will decrease linear. When
500W 52.00Hz
OFF 95% the battery SOC equals to the setting value (OFF), the system
Micro Inv Input ON 100%
frequency will become the setting value (AC couple Fre high)
and the Microinverter will stop working.
Ml export to Grid cutoff
MI export to grid cutsoff: stop exporting power produced by the
microinverter to the grid.
Advanced Function
This is for Wind Turbine
DC1 for WindTurbine DC2 for WindTurbine
V1 0V 0.0A V7 0V 0.0A
Wind
Set2
V2 0V 0.0A V8 0V 0.0A
V3 0V 0.0A V9 0V 0.0A
- 26 -
PassWord
Factory Reset: 9999
X--X--X--X DEL Lock out all changes:7777
1 2 3
4 5 6
7 8 9
CANCEL 0 OK
Li-BMS
Device Info.
Volt Inverter
Curr Temp SOCID: 1601012001
Energy Charge Fault
This page show Inverter ID, Inverter version
HMI: Ver0302 MAIN:Ver1400
Volt Curr and alarm codes.
1 50.38V 19.70A 30.6C 52.0% 26.0Ah 0.0V 0.0A 0|0|0
Alarms Code31.0C 51.0% 25.5Ah
Occurred
2 50.33V 19.10A 53.2V 25.0A 0|0|0 Device
Sum
3 F64 Heatsink_HighTemp_Fault
50.30V 16.90A 30.2C 12.0% 6.0Ah2019-03-11 15:56
53.2V 25.0A 0|0|0
4 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
Info
Data
5 F64 Heatsink_HighTemp_Fault
0.00V 0.00A 0.0C 0.0% 0.0Ah2019-03-08
0.0V 0.0A 10:46
0|0|0
0.00V
6 F64 0.00A 0.0C 0.0% 0.0Ah2019-03-08
Heatsink_HighTemp_Fault 0.0V 0.0A 10:45
0|0|0 HMI: LCD version
7 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
8 0.00V 0.00A
9 0.00V 0.00A
0.0C
0.0C
0.0%
0.0%
0.0Ah
0.0Ah
0.0V
0.0V
0.0A 0|0|0
0.0A 0|0|0
MAIN: MCU version
10 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0 Details
11 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0 Data
12 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
13 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
14 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
15 0.00V 0.00A 0.0C 0.0% 0.0Ah 0.0V 0.0A 0|0|0
6. Mode
Mode I:Basic
Solar
CT
Battery
Grid
- 27 -
Mode II: With Wind Turbine
AC cable DC cable
Wind
Grid
CT
Battery
AC cable DC cable
Grid
CT
Battery
Generator
AC cable DC cable
Grid
CT
Battery
Smart Load
- 28 -
Mode V: With On-Grid Inverter
Grid
Battery
The 1st priority power of the system is always the PV power,then 2nd and
3rd priority power will be the battery bank or grid according to the settings.
The last power backup will be the Generator if it is available.
If any of the fault messages listed in Table 6-1 appear on your inverter and
the fault has not been removed after restarting, please contact your local dealer
or service center. You need to have the following information ready.
- 29 -
Error code Description Solutions
No Utility
1. Please confirm grid is lost or not;
F35 No AC grid 2. Check the grid connection is good or not;
3. Check the switch between inverter and grid is on or not;
4. Seek help from us, if can not go back to normal state.
- 30 -
Error code Description Solutions
Under the guidance of our company, customers return our products so that our company
can provide service of maintenance or replacement of products of the same value.
Customers need to pay the necessary freight and other related costs.
Any replacement or repair of the product will cover the remaining warranty period of the
product. If any part of the product or product is replaced by the company itself during the
warranty period, all rights and interests of the replacement product or component belong
to the company.
Factory warranty does not include damage due to the following reasons:
In addition, normal wear or any other failure will not affect the basic operation of the
product. Any external scratches, stains or natural mechanical wear does not represent
a defect in the product.
- 31 -
[Link] of Liability
In addition to the product warranty described above, the state and local laws and regulations
provide financial compensation for the product's power connection (including violation of
implied terms and warranties). The company hereby declares that the terms and conditions
of the product and the policy cannot and can only legally exclude all liability within a limited
scope.
9. Datasheet
SUN-3.6K-SG01/03LP1 SUN-5K-SG01/03LP1
Technical Data
-EU -EU
Battery Input Data
Battery Type Lead-acid or lithium-ion
Battery Voltage Range (V) 40V-60V
Max. Charging Current (A) 90A 120A
Max. Discharging Current (A) 90A 120A
Charging Curve 3 Stages/equalization
External Temperature Sensor Optional
Charging Strategy for Li-Ion Battery Self-adaption to BMS
PV String Input Data
Max. DC Input Power (W) 4680W 6500W
PV Input Voltage (V) 370V(100V~500V)
MPPT Range (V) 125~425V
Full Load DC Voltage Range 240V~425V
- 32 -
Max Continuous AC Passthrough (A) 35A
Power Factor 0.8 leading to 0.8 lagging
Output Frequency and Voltage 50/60Hz; 220/230/240Vac(single phase)
Efficiency
Max. Efficiency 97.60%
Euro Efficiency 96.50%
MPPT Efficiency 99.90%
Protection
PV Input Lightning Protection Integrated
Anti-islanding Protection Integrated
PV String Input Reverse Polarity Protection Integrated
Insulation Resistor Detection Integrated
Residual Current Monitoring Unit Integrated
Output Over Current Protection Integrated
Output Shorted Protection Integrated
Output Over Voltage Protection Integrated
Certifications and Standards
VDE 0126,AS4777,NRS2017,G98,G99,
Grid Regulation
IEC61683, IEC 62116, IEC 61727