A B C D E F G H I J K L M N O P Q R S T U
01 01
Power System Stabilizer (PSSB) with Biquad Filters and Switchable Washout
02 Overview 02
Arm PSS Input PSS Armed Output
<PSS_ARM> <PSSARMD>
03 Power Level Enable 03
and Disable
(In Auto) PSS Active
<PSS_ARM> <AUTOMAN> <PSSACT>
PWRENB
04 |u| 04
<PSSACT>
<PSSOP>
05
PSS lo watts disable
0.1 pu
PSS hi watts enable
0.15 pu
0 05
Final Output
Adjust polarity for generating or motoring
06 06
1
PSSGLMO
-1
PSSSWOI Switchable Washout Gain PSS out upper limit
Lead/Lag Compensation 0.1 Vpu
07 ( V pu / slip pu) 07
s+1 s+1 s+1 s T PSSLLO PSS Gain
s+1 s+1 s+1 s+1
10
08
SwWashOutEnab Output Limits 08
SWOACT PSS out lower limit
PSS Lead 1 PSS Lead 2 PSS Lead 3 SwWashOutSec
1 = 0.15 sec = 0.15 sec 10 = 0 sec 5 sec
-0.1 Vpu
SwWashOutTC1
PSS Lag 1 PSS Lag 2 PSS Lag 3 1
09 2 = 0.03 sec = 0.03 sec 11 = 0 sec
20 sec
Timer 09
SwWashOutTC2
3 sec
SwWashOutNegLim SwWashOutPosLim
Switchable Washout
-0.035 Vpu 0.035 Vpu
Settings
10 10
11
PSS max power limit Washedout Integral of Watts Path 11
1.5 pu Biquadratic Filters
Watts s WATTINT EXDSPD
BQD1OUT BQD2OUT BQD3OUT
12
s+1 s+1) PSS KS3 PSS biquad1 num damp PSS biquad2 num damp PSS biquad3 num damp 12
1 RTFOUT 1 = 0.5 damp 1 = 0.5 damp 1 = 0.5 damp
PSS max slip limit
Washedout Slip Path
0.1 pu
<SLIP> s s SLWOOUT
+ +
s+1 + -
s+2s+ s+2s+ s+2s+
13 13
s+1 s+1 + s+1)5 + s+2s+ s+2s+ s+2s+
Xq for slip calc TEST1 PSS Ramp Track Filt PSS biquad1 den damp PSS biquad2 den damp PSS biquad3 den damp
0.6689 pu =
PSS Washout
2 sec
= 0.1 sec TEST2 = 0.5 damp 2 = 0.5 damp 2 = 0.5 damp
14 RTFIN 14
PSS biquad1 nat r/s PSS biquad2 nat r/s PSS biquad3 nat r/s
M=
PSS Inertia (M=2H)
1 = 62 r/s 1 = 62 r/s 1 = 62 r/s
6.56 pu Ramp Tracking Low Pass Filter
Above limits are applied as
15 negative values for the lower limit 15
PRODUCT: File name:
General Electric g EX2100 Excitation Control [Link]
Firmware Revision: Issued Date --- Initials:
Salem, Va. USA
16
Revision Date
A B C D E F G H I J K L 6/8/16 5:09 PM