GENERAL NOTES AND SPECIFICATIONS
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE RULES 8. PANEL BOARD SHALL BE COMPLETE WITH BUS, ENCLOSURE AND TRIM, COMPLETE
AND REGULATIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRIC CODE, AND MOLDED CASE CIRCUIT BREAKER, WITH RATING AS INDICATED. PROVIDE
APPLICABLE ORDINANCES OF THE LOCAL GOVERNMENT AND WITH THE REQUIRE- A TYPED CIRCUIT DIRECTORY.
MENTS OF THE LOCAL POWER COMPANY. 9. ALL ELECTRICAL DEVICES AND EQUIPMENT EXPOSED TO WEATHER SHALL BE
2. METALLIC ENCLOSURES, RACEWAY AND ELECTRICAL EQUIPMENT SHALL BE WEATHERPROOF.
GROUNDED. 10. ELECTRIC SERVICE FOR THE PREMISES SHALL BE 230V 1, PHASE, 2 WIRE.
3. MINIMUM SIZE OF WIRE SHALL BE 2.0mm2 TW AND THE MINIMUM SIZE OF CONDUIT
SHALL BE 20mm DIAMETER, UNLESS OTHERWISE INDICATED ON PLAN. 11. TEST: THE FOLLOWING SHALL BE TESTED IN PRESENCE OF ENGINEER, AND RESULTS
SUBMITTED TO ENGINEER FOR APPROVAL.
4. WHEREVER REQUIRED AND NECESSARY, PULL BOXES AND JUNCTION BOXES OF
A. OPERATION TEST
OF PROPER SIZES SHALL BE INSTALLED AT CONVENIENT AND INCONSPICUOUS
B. INSULATION RESISTANCE
LOCATIONS ALTHOUGH SUCH BOXES ARE NOT SHOWN ON THE PLANS NOR MENTIONED
C. GROUND RESISTANCE (IF TRERE IS GROUND ROD)
IN THE SPECIFICATIONS.
5. ALL LIGHTING CIRCUIT HOMERUNS AND CONVENIENCE OUTLETS SHALL BE WIRED 12. THE DRAWING AND SPECIFICATIONS ARE MEANT TO BE COMPLEMENTARY TO EACH OTHER
WITH NO LESS THAN 3.5 mm2 TW IN SIZE. ALL 15 AND 20 AMP. CIRCUIT HOMERUN AND WHAT IS REQUIRED BY ONE SHALL BE BINDING AS IF CALLED BY BOTH. ANY
TO PANEL BOARD MORE THAN 30 MTS. IN LENGTH SHALL BE WIRED WITH NO LESS THAN APPARENT CONFLICT BETWEEN THE DRAWINGS AND SPECIFICATIONS, AND ANY CONTROVERSIES
5.5mm. IN SIZE, UNLESS OTHERWISE INDICATED ON THE PLAN.
OR UNCLEAR POINTS IN EITHER, SHALL BE REFERED TO THE ELECTRICAL CONSULTANT OR
6 ALL WIRING SHALL BE INSTALLED IN STANDARD MOLDFLEX OR PVC ELECTRICAL
DESIGNER FOR FINAL DECISION.
CONDUITS RUN EMBEDDED INSIDE THE CONCRETE AND HOLLOW BLOCK STRUCTURES,
SLABS, COLUMNS, WALLS, PARTITIONS AND INSIDE THE CEILING SPACES. WHERE 13. ALL REVISION OR ADDITIONAL WORKS ON ELECTRICAL PLANS SHOULD BE CONSULTED
THE USE OF CONCEALED CONDUIT WIRING IS IMPRACTICABLE SURFACE METAL, PVC TO THE DESIGNER ( P. E. E.)
MOLDING MAY BE USED.
7. ELECTRICAL WORK SHALL BE DONE UNDER THE DIRECT AND FULL SUPERVISION OF
A DULY LICENSED ELECTRICAL ENGINEER OR REGISTERED MASTER ELECTRICIAN.