PIX-36 User Guide VDRB05981-02
PIX-36 User Guide VDRB05981-02
PIX-36
With Roll on Floor Type Circuit Breaker
VDRB05981-02
01/2021
Legal Information
The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS
referred to in this guide are the sole property of Schneider Electric SA and its subsidiaries.
They may not be used for any purpose without the owner's permission, given in writing. This guide
and its content are protected, within the meaning of the French intellectual property code (Code de
la propriété intellectuelle français, referred to hereafter as "the Code"), under the laws of copyright
covering texts, drawings and models, as well as by trademark law. You agree not to reproduce,
other than for your own personal, noncommercial use as defined in the Code, all or part of this
guide on any medium whatsoever without Schneider Electric's permission, given in writing.
gu
You also agree not to establish any hypertext links to this guide or its content. Schneider Electric
does not grant any right or license for the personal and noncommercial use of the guide or its
content, except for a non-exclusive license to consult it on an "as is" basis, at your own risk.
co
All other rights are reserved.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
As standards, specifications, and designs change from time to time, please ask for confirmation of
the information given in this publication.
Set Series
Featuring outstanding medium-voltage (MV) and low-voltage (LV) switchboards, motor control
centres and power distribution solutions for high-performance power applications, Schneider
Electric's Set Series is best-in-class solutions based on high levels of safety and an optimised
footprint. Built on a modular architecture and incorporating smart connected devices for maximum
safety, reliability, performance and energy efficiency, the Set Series is delivered to customers
directly from our Schneider Electric plants or via a global network of licensed partner panel
builders, who are trained and audited to provide quality equipment and support.
Contents
PIX-36
1. Safety provisions 7
5. Assembly 24
5.1. Safety provisions 24
5.2. Important instructions for assembly 24
5.3. Requirements regarding the switchgear room 24
5.4. Transport of the panels and trucks at the construction site 27
5.5. Aligning and fastening panels 27
5.6. Screw-fastening the panels to one another 29
5.7. Busbar assembly 30
5.7.1. Access to the busbar compartment 30
5.7.2. Busbar assembly 30
5.8. Assembly of the earth bus 31
5.9. Mounting the deflectors 31
5.10. Assembly of pressure relief duct 31
6. High-voltage connection 32
6.1. Overview of cable connection variants 32
6.2. Mounting the high-voltage cables 32
7. Low-voltage terminal 34
7.1. Connection of the ring circuits in the low-voltage cabinet 34
7.2. Placing external cables in the switchgear panel 34
VDRB05981-02 3
Contents
PIX-36
8. Commissioning 35
8.1. Final steps 35
8.2. Checking switching functions and interlocks 36
8.3. Power frequency test of busbar (optional) 36
9. Operation 38
9.1. Operating Interface of the panel 38
9.2. Operating interface of trucks 38
9.2.1. Vacuum circuit breaker HVX-O 38
9.2.2. Isolating truck UTX-O 39
9.2.3. Metering truck MTX-O 39
9.3. Operation accessories 40
9.4. Interlocks 41
9.4.1. Mechanical interlocks 41
9.4.2. Interlocks (cable Earthing Switch) 42
9.4.3. Interlocks (bus Earthing Switch) 42
9.4.4. Electromagnetic interlocks (Optional) 43
9.4.5. Interlocks with padlock 43
9.5. Operating Specifications 43
9.6. Operating the circuit-breaker 44
9.6.1. Operator interface 44
9.6.2. Charging the circuit-breaker’s energy storing device 44
9.6.3. Switching the circuit-breaker manually 45
9.6.4. Switching the circuit-breaker electrically 46
9.6.5. Position indicators on circuit-breaker and possible operating
sequences 46
9.7. Move truck into operating/disconnected position 47
9.7.1. Racking-in the truck from disconnected into service position 47
9.7.2. Racking-out the truck from service into disconnected position 47
9.8. Operating the earthing switch manually 48
9.8.1. Switching the earthing switch ON 48
9.8.2. Switching the earthing switch OFF 48
9.8.3. Switching the earthing switch ON in case of solenoid interlock 48
9.9. Standard switching operations 49
9.9.1. Operating the outgoing feeder cable 49
9.9.2. Earthing the outgoing feeder cable 49
9.9.3. Coupling busbar section using the bus section coupler 49
9.10. Earthing the busbar with busbar earthing switch 50
10. Maintenance 51
10.1. Safety provision 51
10.2. Maintenance and servicing specifications 51
10.3. Cleaning 52
10.4. Avoiding condensation 52
10.5. Corrosion protection 52
10.6. Replacement of components and panels 52
10.7. Lubrication instructions 53
10.8. Replace fuses for voltage transformers 54
11. Annex 55
11.1. Auxiliary products 55
11.2. How to treat the contact surfaces 55
11.3. Specifications for screw connections 56
11.4. Required tools (not included in the scope of supplies) 57
11.5. List of assembly drawings 57
4 VDRB05981-02
PIX-36
This Technical Manual is an integral part of the product and must be stored
such that it is at all times readily accessible for and can be used by persons
who are to work on the switchgear. If the switchgear is relocated to another
site, this Technical Manual must be passed on to the new operators along
with the unit.
This Technical Manual does not include information regarding the safety of
buildings in case of internal faults (pressure load of the switchgear room and
necessary pressure relief ports). Pressure calculations for switchgear room
incl. recommendations regarding pressure relief ports can be provided on
request against a fee. For further details, please contact the manufacturer.
Reference documents
The following additional documents must be complied with:
Purchase agreement containing the stipulations on the specific
equipment
of the switchgear and the legal details
the switchgear-specific circuit diagrams / documentation
the operating manuals of the low-voltage devices installed in the
switchgear (e.g. voltage presence indicating systems, devices in low
voltage cabinet)
the assembly drawings supplied with the switchgear
the Operating Instructions of the trucks used:
Circuit-breaker HVX-O
Metering truck MTX-O
Isolating truck UTX-O
Earthing truck ETX-O
the Assembly Instructions of the manufacturer of the cable connection
systems to be connected to the switchgear
VDRB05981-02 5
PIX-36 Remarks on this manual
Terms and symbols used
This manual uses certain terms and symbols. They warn about dangers or
provide important information which must be complied with in order to avoid
danger to persons and damage to equipment:
“Danger!”
This danger symbol warns about dangerous electrical
voltage. Contact with voltage may result in fatal injury!
“Warning!”
This danger symbol warns about the risk of injury.
Please comply with all the provisions identified by this
symbol in order to avoid death or serious injury.
“Warning!”
This danger symbol warns about the risk of falling.
“Important”
This instruction symbol is used for information which is
important to avoid material damage
Abbreviations used
“PIX-36”: Switchgear PIX-36 for rated voltage Ur = 36kV
6 VDRB05981-02
PIX-36
1 Safety provisions
The work described in this manual may only be performed by specialist
electricians who have proved their experience with the PIX series and the
applicable safety provisions.
Please read the whole manual carefully before working on the switchgear.
Before performing work on the panel, it is essential that you comply with the
following instructions:
Danger!
Risk of fatalities due to high voltage. Isolation from high
voltage and earthing must always be ensured before
performing assembly or maintenance work.
Warning!
After the removal of covers from a switchgear unit,
operator safety regarding internal arcs may be reduced
unless the switchgear is isolated from the power
supply. Optimum operator safety is only ensured if
the switchgear is completely isolated from the power
supply and earthed during assembly or maintenance
work.
Warning!
Risk of injury due to movable parts in mechanical
drives.
For the case of an internal fault, the PIX-36 switchgear features pressure
relief ports which prevent the panels and the switchgear unit from bursting.
In case of fire or of internal faults, toxic and caustic decomposition products
may be produced. Comply with the locally applicable accident and safety
provisions.
In case of personal injury, take first-aid measures or cause them to be taken.
VDRB05981-02 7
PIX-36 2 Design & description
Fig. 1
Pix-36 panel with HVX-O circuit breaker
8 VDRB05981-02
PIX-36
Single Line
Single Line
Single Line
VDRB05981-02 9
PIX-36
Single Line
Single Line
10 VDRB05981-02
PIX-36
Fig. 2
Dimensions of PIX-36 panels
a. Panel width = 1000 mm
b. Panel height = 2375 mm
c. Panel depth = 2640 / 3100 / 3560 mm
Fig. 3
Dimension of panel with deflector Dimensions & weights
a. Panel height = 2825 mm Item Unit Data
Width mm 1000
Height mm 2375
Depth Mm 2640 3100 3560
1
Weight kg < 1600 1900 1 2300 1
1
Including moving part & average extent of Low-voltage cabinet equipments.
Fig. 4
Dimensions of panel with tunnel
a. Total height = 2875 mm
VDRB05981-02 11
PIX-36
12 VDRB05981-02
PIX-36
1
The short-circuit capability of the current transformers must be considered
separately.
The technical data of the switching device (HVX-O, UTX-O, ETX-O) are
indicated on the nameplate and in the operating manual of the device
concerned.
2.7 Nameplate.
The type designation of the switchgear panels on the nameplate Fig. 5
specifies essential technical data. When submitting enquiries to the
manufacturer or ordering spare parts, the following information is required:
Fig. 5
Name plate on front panel
1. Serial number
2. Type designation
3. Technical data
VDRB05981-02 13
PIX-36
Trucks
14 VDRB05981-02
PIX-36
Disclaimer of liability
The manufacturer shall not be held responsible for damage which occurs if
instructions in this Technical Manual are not complied with;
the switchgear is not operated according to its intended use (see
above);
the switchgear is assembled, connected or operated improperly;
accessories or spare parts are used which have not been approved by
the manufacturer;
the switchgear is converted without the manufacturer’s approval, or if
inadmissible parts are added.
No liability is accepted for parts provided by customers, e.g. current
transformers.
VDRB05981-02 15
PIX-36
3 Packaging, transportation, storage
Important:
The weight of the entire transport unit is indicated on the
packaging.
Packaging
Fig. 6 Fig. 7
Packed in PE protective Packed in PE protective film suitable
Film on a pallet for seaworthy transport
16 VDRB05981-02
PIX-36
3.2 Transport
Warning!
Danger due to load tipping over.
Transport units must be secured sufficiently
during transport to prevent slipping and
tipping over.
The panel may only be transported on a pallet. The entire length of the forks
must be placed under the transport unit (Fig. 8).
Fig. 8
Transport units must not be allowed to tip over
Delivery
Fig. 9
Transportation using Forklift truck
3.3 Warehousing
Warning!
Risk of accidents. Sufficient stability and
evenness of the supporting area (floor) must
be ensured.
If the panels are not installed immediately after delivery, they can be stored
under the following conditions:
Fig. 10 Panels must be stored in vertical position, and must not be stacked.
Schematic diagram of storage conditions for Storage only admissible indoors.
PIX-36 panels Switchgear panels and accessories must be sealed with desiccant in
aluminium foil and be packed in a wooden crate (storage for max. two
years after the date of packaging).
VDRB05981-02 17
PIX-36
4 Access to main circuit compartment
Important:
The panels may be equipped with additional interlocks
to lock the cable compartment cover and the front door.
In this context, refer also to Chapter 9.4 “Interlocks”.
Danger!
Risk of fatalities due to high voltage. The front
door may only be opened if the truck is in
disconnected position (see Chapter 9.7.2).
Fig. 12
Handle in open condition
18 VDRB05981-02
PIX-36
Important:
The low-voltage connector can only be removed or
inserted while the truck is in disconnected position.
Fig. 13
1. Unlock low-voltage connector
2. Remove low-voltage connector
Fig. 14
Place low-voltage connector in tray above the
truck
VDRB05981-02 19
PIX-36
Fig. 15
Moving the truck outside the panel
Fig. 16
Unlocking the truck in the panel
20 VDRB05981-02
PIX-36
Important:
Optionally, trucks and panels can be given matching
coding. This is to prevent a truck from being racked
completely into a panel if the ratings do not match.
Fig. 17
Moving the truck to the front of the panel.
Fig. 18
Locking the truck in the panel
VDRB05981-02 21
PIX-36
Danger!
Risk of fatalities due to high voltage. Ensure
cable chamber is de-energized & earthed
before opening the cable compartment cover
Fig. 19
Removing the cable compartment cover
22 VDRB05981-02
PIX-36
Open the front door and remove the truck from the panel (see chapter
4.2.3 )
Un-mount the busbar access cover from the CB compartment (Fig. 20 &
21). The busbar compartment is now accessible
Fig. 20 Fig. 21
Remove truck (1) & partition plate (2) Posture of worker during main
busbar mounting & panel fastening
After completion of assembly work, re-insert the partition plate and fasten it
by means of the bolts.
VDRB05981-02 23
PIX-36
5 Assembly
5.1 Safety provisions
The switchgear panels may only be installed and assembled by the
manufacturer’s staff or by persons who have been certified for this work.
PIX-36 panels are delivered with the earthing switch OFF.
The circuit breakers are always shipped in open state (”OFF”) with the
energy storing device released.
Warning!
Risk of injury due to movable parts in
mechanical drives. The circuit-breakers
energy storing device and the earthing switch
must not be tensioned during assembly.
Warning!
Risk of accidents! Watch out for floor
openings in the switchgear room
Warning!
The top sides of the panels are not meant to
be walked on. Persons may fall through them,
get injured or may damage the panel. When
work has to be performed on the panel top -
e.g. assembly of deflectors or pressure relief
ducts – temporarily position a solid base plate
to step on.
Warning!
Risk of injury in case of non-compliance with
the safety instructions in Chapter 1.
24 VDRB05981-02
PIX-36
Important:
- Observe switchgear-specific space assignment plan.
Fig. 22
Dimensions in the switchgear room example)
1. PIX-36 panels
2. Switchgear room
3. 450 mm incase of deflector & 500 mm in case of tunnel
VDRB05981-02 25
PIX-36
Fig. 23
Ground plan of PIX-36 panel
Fig. 24
Ground plan of PIX-36 panel
26 VDRB05981-02
PIX-36
Warning!
On lowering the panels and the trucks, make
sure that the supporting platform is
sufficiently stable and even.
Warning!
Risk of accidents! Watch out for floor
openings in the switchgear room
Important:
The position of the first panel is decisive for
placement of the subsequent panels, thus it is
essential that measuring is effected with the utmost
precision.
VDRB05981-02 27
PIX-36
Installation of Panels:
Important:
The position of the first panel is decisive for the placement of the subsequent
panels, thus it is essential that measuring is effected with the utmost
precision.
Fig. 27
Fastening of panels on concrete foundation.
28 VDRB05981-02
PIX-36
Position the next panel next to the previous one in accordance with the
assignment plan and align it.
Fig. 28
Panel coupling details.
VDRB05981-02 29
PIX-36
1
≤ 1250 A
Number of outgoing
feeder bars per phase
2
2000 A -
Important:
Comply with the specifications on treatment of contact surfaces and the
tightening torques for busbar screw fastening in the Annex.
Comply with the position and direction of screws and nuts as shown in
the diagram.
Put shrouds on Bus joints after assembly.
30 VDRB05981-02
PIX-36
Important:
Comply with the specifications on treatment of
contact surfaces and the tightening torque for screw
fastening in the Annex.
Important:
Observe the specific standards referring to earthing
Fig. 29 systems which apply in your country
Mounting the earth bar
1. Connecting bar
2. Cutout in panel supporting structure
3. Earthing bars in the panels Clean all contact areas of the connecting bar and the appropriate earth
4. Adjacent panel
bar in the switchgear panels and coat them with Synthetic lubricant (see
5. Screw fastening of connecting bar to
earthing bars Chapter 11.1).
Slip the connecting bar (Fig. 29 , item 1) into the adjacent panel (4)
through the cutout in the panel-supporting structure (2).
Screw-fasten (5) connecting bar on both sides to the earth bar (3) in
question.
Connect earth bus (Fig. 30) to the earthing system of the switchgear
building (connecting lines and screw accessories are not included in the
scope of supplies)
Fig. 30
Connecting point of switchgear earth bus to
building earth
5.9 Mounting of deflectors
The pressure relief duct on the upper side of the panel ensures operator
safety in accordance with IEC 62271-200 in the case of internal faults
VDRB05981-02 31
PIX-36 6 High–voltage connection
6.1 Overview of cable connection variants
In panel [A] Panel width [mm] Cables per phase
800 1000 1/2
1250 1000 1/2/3/4
2000 1000 4/5
Fig. 31
Connecting brackets available for cable connection.
Max. 500 mm2 cable
32 VDRB05981-02
PIX-36
Important:
- Unless otherwise specified by the cable manufacturer:
Comply with the specified tightening torques and
pre-coat contact areas (see Chapter 11.2).
- Observe the phase grouping of the switchgear panel.
Fig. 33
High-voltage connection
1. Cable connection on the panel
2. Clamping assembly for the cables
3. Base plates
4. Connection of the ground wires to the panel
Fig. 34
Clamping assembly for cables with a diameter of ≥ 40 mm
Fig. 35
Clamping assembly for cables with a diameter of ≤ 40 mm
VDRB05981-02 33
PIX-36 7 Low voltage terminal
7.1 Connection of the ring circuits in the
low-voltage cabinet
Route the ring circuits for the inter-panel wiring through the lateral
openings of the low-voltage cabinet (Fig. 36, item 2).
Connect ring circuits to the appropriate terminal strips in the low-voltage
cabinet according to the circuit diagram.
Fig. 36
Connection of low-voltage cable
1) Terminal strip
2) Openings for ring circuits in the low-voltage
cabinet
Remove the metal cable duct covers on the left & right side of the panel
depending on the need (2).
Remove the LV gland plate (4) and drill as per cable requirement.
Route external cables (6) from the cable basement through the cutout in
the panel floor (3) and route them in the cable duct to the low-voltage
cabinet. Fasten cables to the panel using cable clamps (5).
Connect external cables to the terminal strip in the low-voltage cabinet
according to the circuit diagram (1).
Reposition cable compartment covers.
Open the gland plate (7) provided on the top of low-voltage cabinet.
Drill as per cable requirement
Route the cables to the low-voltage cabinet.
Connect external cables to the terminal strip in the low-voltage cabinet
according to the circuit diagram (1).
Fig. 37 Reposition gland plate on the cabinet.
Placing external cables in the switchgear panel
1) Connection to terminal strip in the low-voltage
cabinet
2) Cable duct covers
3) Cutout in the panel floor
4) Low-voltage gland plate Important:
5) Cable clamp If the cables are to be routed into the low-voltage
6) Low-voltage cables
7) Gland plate in case the cables has to be routed
cabinet from above, the cable fastening and protection
from above the low-voltage cabinet equipment must be provided by the customer
34 VDRB05981-02
PIX-36
8 Commissioning
8.1 Final steps
Danger!
The high voltage supply must not be
connected. All active parts must be earthed,
Important:
Whenever you detect anomalies, faults or malfunctions,
do not commission the switchgear, but inform the
manufacturer.
Damaged paint
The panels are powder-coated. Minor damage to the paint can be repaired
using commercially available paint (standard colour RAL 7032 or
corresponding colour).
Inspection
Check the switchgear for damage which might be due to transport or
assembly work.
Compare data on nameplate to the required ratings.
Check the connected cables for phase coincidence
VDRB05981-02 35
PIX-36
Important:
- For switching operations, comply with Chapter 9
“Operation”.
- In case supply voltage is not available,
• blocking coils (optional; lock circuit-breaker
button and/ or truck in disconnected position)
are in locked position, thus blocking manual
switching operations;
• There is a dropped-out under voltage release in
the circuit breaker (optional).
- The energy-storing device of the circuit-breaker
drive is charged autonomously as soon as the
supply voltage is applied.
A test unit and a test adapter (not included in scope of supplies) are required
for the power frequency test.
Preparation
All panels must be isolated from the power supply and earthed (see
Chapter 9.9,).
Busbar: Disconnect voltage transformers (MTX) and surge arrester.
36 VDRB05981-02
PIX-36
Perform the power frequency test of the busbar on the feeder panel:
Connect test unit to the test cable.
Switch the earthing switch OFF.
Move circuit-breaker truck HVX service position and switch circuit
breaker ON.
Perform the power frequency test successively for all three phases (L1,
L2, and L3) in accordance with the specifications of the test unit
manufacturer.
Important:
Observe admissible test values for the switchgear and
the admissible test values for power-frequency tests
after installation of the switchgear in accordance with
IEC 62271-200.
Fig. 38
Switch position during the power frequency test (example: five panels)
1) Branch-circuit panels
2) Incoming feeder panel for test voltage
3) Busbar
4) Test unit (e g. high-voltage source, test transformers)
5) Test cable
VDRB05981-02 37
PIX-36 9 Operation
9.1 Operating interface of the panel
1. Feeder Nameplate
2. Rating plate
3. Handle for pulling door
4. Operating handle for door locking & unlocking
5. Switching circuit-breaker ON
6. Inspection glass
7. Opening for manual charging of the circuit-breakers energy storing
device
8. Option for defeating the close door interlock (to be operated only by
authorized person)
9. Insertion opening for racking the truck in/out manually
10. Slide for opening the insertion opening (9) for racking the truck in and
out
11. Window for checking Test / Service indication
12. Low-voltage cabinet with control unit
13. Handle for pulling door
14. Locking for low-voltage cabinet door.
15. Switching circuit-breaker OFF
Fig. 39
Operating interface of a PIX-36 Panel
Fig. 40
Vacuum circuit-breaker HVX-O
38 VDRB05981-02
PIX-36
Fig. 41
Isolating truck UTX-O
Fig. 42
Metering truck MTX-O
VDRB05981-02 39
PIX-36
Important:
These accessories are supplied with the panel. The
panel may only be operated by means of these
accessories.
Fig. 43
Standard double-bit key to lock/unlock the door of the
low-voltage cabinet
Item no. SEM 101137-01
Fig. 44
Crank to charge the circuit-breaker’s energy-storing
device
Item no. MVIA00207-01
Fig. 45
Operating rod to switch the circuit breaker ON and
OFF
Item no. MVIB00775-01
Fig. 46
Rack-IN/ OUT handle for Truck
Item no. VDRG00157-02
Fig. 47
Operating lever for the earthing switch
Item no. VDRB05405-01
40 VDRB05981-02
PIX-36
9.4 Interlocks
Important:
Complete switchgear interlocking can only be ensured with complete locking devices.
panels have mechanical basic interlocks which help avoid operating errors. You must be familiar with these
Interlocks before operating panels.
VDRB05981-02 41
PIX-36
Incomer Cubicle(Electrical) The insertion of the earthing switch Supply to the solenoid is possible when
operating handle is blocked using there is no presence of voltage in
solenoid if cable is energized. incoming side.
Outgoing Cubicle(Electrical) The insertion of the earthing switch Supply to the solenoid is possible when
Optional operating handle is blocked using there is no presence of voltage in
solenoid if cable is energized. incoming side.
42 VDRB05981-02
PIX-36
Important:
- In case of failure of the supply voltage, all electrical
interlocks are in their locked position.
Action: Re-establish power supply.
Fig. 48
Manual rack IN of truck locked by padlock
Danger!
To rule out faulty switching operations, the
operating sequences described below must
be complied with. Each switching operation
must be completed.
Fig. 49
Manual switching ON of circuit breaker locked by Check whether the supply voltage is ON.
padlock
Important:
While the power supply is not available, blocking
coils (locking the interrogation slides and circuit-
breaker push-buttons, depending on design), are in
“locked” position. An under voltage release
(optional) has dropped out. Measure: Re-establish
the supply voltage.
After each switching operation for which you have
used a crank or a lever, remove this tool and store it
in the tool board.
Fig. 50
Manual switching OFF of circuit breaker locked by
padlock
VDRB05981-02 43
PIX-36
Fig. 51
Operator interface of HVX circuit-breaker
Initial situation:
- Circuit-breaker OFF
- Energy-storing device released
Charging by hand
Move the slider to the left and hold it (Fig. 53, item 1) and insert the
crank (Fig. 52 and Fig. 53, 2).
Fig. 52 Turn the crank in clockwise direction until the charge drive mechanism
Charging the circuit-breaker’s energy storing device is uncoupled (sound). The energy storing device indicates the “charged”
condition through the inspection glass.
Remove crank.
Fig. 53
Charging the circuit-breaker’s energy storing device
44 VDRB05981-02
PIX-36
Insert the operating rod (Fig. 54 and Fig. 55) into the guide provided on the
door and press it to perform the circuit breaker “ON” operation.
Confirm the circuit breaker “ON” status provided on the Circuit breaker by
viewing window on the door.
Fig. 54
Switching the circuit-breaker via the operating rod
Insert the operating rod (Fig. 54 and Fig. 56) into the guide provided on the
door and press it to perform the circuit breaker “OFF” operation.
Confirm the circuit breaker “OFF” status provided on the Circuit breaker by
viewing window on the door.
Fig. 55
Switching the circuit-breaker ON via the operating rod
Fig. 56
Switching the circuit-breaker OFF via the operating rod
VDRB05981-02 45
PIX-36
Switching ON (Closing)
Actuate the opening release via the bay computer or the remote control
Under voltage release or
Secondary release
3 released ON O
4 charged ON O–C-O
C = Closing (ON)
O = Opening (OFF)
46 VDRB05981-02
PIX-36
Initial situation:
- Circuit-breaker OFF
- Earthing switch OFF
Fig. 57
Moving the truck from disconnected into service
position
9.7.1 Racking-in the truck from disconnected into service position
Move the slider (Fig. 57, item 1) to the left and hold it. Insert handle
through the opening in the door onto the drive shaft of the truck (2).
Turn crank clockwise until the truck has been racked in (Fig. 58).
Remove crank.
Check position of truck (Fig. 58) through the inspection glass (Fig. 57,
item 3).
Fig. 58
Truck racked-in in service position
Press the slide (Fig. 59, item 1) to the left and hold it. Insert handle
through the opening in the door onto the drive shaft of the truck (2).
Turn crank counter-clockwise until the truck has been racked out (Fig.
60). Remove crank.
Check position of truck (Fig. 60) through the inspection glass (Fig. 59,
item 3).
Fig. 59
Moving the truck from service into disconnected
position
Fig. 60
Truck racked-out in disconnected position
VDRB05981-02 47
PIX-36
Initial situation:
- Circuit-breaker OFF
- Earthing switch OFF
- Truck In disconnected position
Initial situation:
- Circuit-breaker OFF
- Earthing switch ON
- Truck In disconnected position
Initial situation:
- Circuit-breaker OFF
Fig. 61
Operation of Earthing switch. - Earthing switch OFF
- Truck In disconnected position
Dont’s
48 VDRB05981-02
PIX-36
Initial situation:
- Circuit-breaker OFF
- Truck HVX in disconnected position
- Earthing switch OFF
- Circuit-breaker OFF
- Truck HVX in disconnected position
- Earthing switch OFF
De-earthing
Initial situation:
- Circuit-breaker OFF
- Truck HVX in disconnected position
VDRB05981-02 49
PIX-36
Initial situation:
De-earthing
Switch the earthing switch OFF
50 VDRB05981-02
PIX-36
10 Maintenance
10.1 Safety provisions
Maintenance and repair work may only be performed by specialist
electricians who have proved their experience with the PIX-36 series and the
applicable safety provisions.
Warning!
Comply also with the safety provisions in
chapter 1.
Important:
In case of frequent condensation or air pollution (dust,
smoke or corrosive gases), the maintenance intervals
must be adapted to the actual conditions.
Qualification /
Maintenance interval Work to be carried out
Work performed by
Clean and grease
drives and movable
main current
Staff who have
contacts (see
Every 4 years been certified for
Chapter 10.7 )
this work
Check releases and
blocking coils for
proper function
After 1,000 actuations Staff who have
Revision of the switching
of the truck or the been certified for
device in question
earthing switch this work
Truck
Refer to the applicable
Circuit-breaker HVX-O Service Center of
instruction manual for the
Metering truck MTX-O the manufacturer
truck concerned
Isolating truck UTX-O
VDRB05981-02 51
PIX-36
10.3 Cleaning
Warning!
Risk of injury: the drives must not be
disassembled for service and maintenance
work.
When cleaning, make sure that the lubrication in the drive mechanisms is
not removed. If the drive mechanisms are no longer sufficiently lubricated,
new lubrication must be applied.
Clean using a dry, lint-free cloth. Depending on the degree of soiling, replace
cloth as often as necessary.
Cleaning agent (see Chapter 10.1). The use of other cleaning agents is not
admissible.
Wear protective gloves
Use cleaning agent according to manufacturer’s instructions
Soak the cloth thoroughly and wipe the insulating components. Keep
duration of exposure as short as possible.
Expose the cleaned surface to the air for at least two hours.
52 VDRB05981-02
PIX-36
Lubrication
Lubrication
Lubricants
points Lubrication procedure
(refer to Annex)
(see also Fig.66)
Sliding contact Apply a thin and uniform film of
Synthetic lubricant
surfaces lubricant.
All accessible Clean lubrication points with
friction points lint-free cotton cloth; apply a
Synthetic lubricant
and sliding thin film of lubricant (using e.g.
surfaces a paintbrush).
Pour drops of liquid lubricant (oil
can, drip feed lubricator) into
the bearing gap. Liquid lubricant
Bearings and gets between the bearing
Liquid lubricant
joints surfaces due to the capillary
effect. In case of inaccessible
lubrication points, use an
extension tube or spray.
VDRB05981-02 53
PIX-36
Fig. 66
Points of lubrication/maintenance
1. Fixed contacts on the cubicle
2. Earthing switch drive
3. Earthing switch contacts
4. Shutter mechanism
5. Guide for the truck
6. Truck (lubricate in accordance with lubricating instructions in the appropriate operating
manual HVX-O / UTX-O / MTX-O)
Isolate outgoing feeder cable from the power supply and earth it.
Remove cable compartment cover (see Chapter 4.3.1).
Insert PT ramp on the rear end of panel.
Push the trolley handles inwards & pull the PT trolley outside of the
panel.
Remove the PT contact & pull fuse carefully out of the PT.
Coat all contact areas (see Chapter 11 ”Annex”) and insert new fuses &
assemble the PT contact.
Re insert the PT trolley in to the cable chamber.
Ensure the trolley is locked by pushing the handles outwards.
Mount cable compartment cover again.
54 VDRB05981-02
PIX-36
11 Annex
11.1 Auxiliary products
The auxiliary products are available from the manufacturer. The use of
alternative auxiliary products is not permissible.
Warning!
Risk of injury: the drives must not be
disassembled for service and maintenance
work.
Important:
- Caution when handling bars insulated by heat
shrinkable sleeves: The heat-shrinkable sleeve must
not get into contact with lubricant (swelling).
- Contact areas coated with synthetic lubricant should
not be touched, if possible.
Material of contact
Pre-treatment
surfaces
1
Silver-plated Clean
4
Nickel-plated Remove passivation layer
1 2
Copper or copper alloy Clean , expose metallic surface
1 2
Aluminium Clean , expose metallic surface
1 2
Steel Clean , expose metallic surface
1
Zinc-plated steel Clean , passivation need not be removed
1
Hot-galvanized sheet-metal Clean , passivation need not be removed
1
Clean by means of lint-free cloth; use cleaning agent in case of serious
contamination
2
Expose metallic surface
by treating the entire surface with emery cloth or a rotating grinding
tool (grain size 100 or 80) or
using a wire brush which is clearly marked for use exclusively for
aluminium or exclusively for copper
3
using a brass brush, steel brush
4
rub slightly by hand using Scotch brite abrasive agent (Ni layer must not
be reduced)
VDRB05981-02 55
PIX-36
Tightening
Thread Ø
torques [Nm]
M 2.5 (M 2.6) 0.5
M3 0.7
M 3.5 1.0
M4 1.5
M5 2.5
56 VDRB05981-02
PIX-36
Nail puller
Cutting pliers
VDRB05981-02 57
PIX-36 Annexure A
A.1 Busbar assembly for
Cubicle rating : ≤1250A &
Busbar rating : ≤1250A
58 VDRB05981-02
PIX-36
VDRB05981-02 59
PIX-36
60 VDRB05981-02
PIX-36
Annexure B
Before performing work on the panel, it is essential to comply with the following instructions:
Danger!
Risk of fatalities due to high voltage. Isolation from high voltage and earthing must
always be ensured before performing assembly or maintenance work.
Warning!
After the removal of covers from a switchgear unit, operator safety regarding internal
arcs may be reduced unless the switchgear is isolated from the power supply.
Optimum operator safety is only ensured if the switchgear is completely isolated
from the power supply and earthed during assembly or maintenance work.
Warning!
Risk of injury due to movable parts in mechanical drives. For maintenance work,
isolate from supply voltage
release the circuit breakers energy storing device by switching it OFF-ON-OFF
Close via the earthing switch.
Warning!
The top sides of the panels are not meant to be walked on. Persons may fall through
them, get injured or may damage the panel.
When work has to be performed on the panel top - e.g. assembly of deflectors –
temporarily position a solid base plate to step on.
VDRB05981-02 61
PIX-36
Step 1: Start from one end of the switch board, first assemble the front deflector (Part No.1) on top of
the end panel.
62 VDRB05981-02
PIX-36
Step 2: Assemble the side deflectors (Part No.2 & 3) on top of the end panel.
VDRB05981-02 63
PIX-36
Step 3: Assemble the rear deflector (Part No.1) on top of the end panel.
64 VDRB05981-02
PIX-36
VDRB05981-02 65
PIX-36
Step 4: Assemble the front supports (Part No.6) followed by the front and rear deflectors (Part No.1) for the
adjacent panel.
66 VDRB05981-02
PIX-36
Repeat Step 4 for all the panels in the switchboard starting from one end.
VDRB05981-02 67
PIX-36
Step 5: Assemble the side deflectors (Part No.2 & 3) on top of the end panel.
68 VDRB05981-02
PIX-36
Step 6: Assemble the side supports (Part No.4 & 5) as given in detail in Step 3.
VDRB05981-02 69
PIX-36
The complete assembly will be as shown below. (Incase of all standard / all extended panels)
70 VDRB05981-02
PIX-36
The complete assembly will be as shown below. (Incase of combination of different depth panels)
VDRB05981-02 71
PIX-36
The below steps are additional for Top Cable Entry Panel only.
Step 7: If the top cable entry panel is the end panel, in addition to the side deflectors (Part No.2 & 3)
assemble side deflector (Part No. 6) on top of the end panel.
72 VDRB05981-02
PIX-36
Step 8: Then assemble the rear deflector (Part No.1) as given in Step No.3 behind the gland plate for top
cable entry, followed by the side support (Part No. 4 or 5) as given in Step No.4 depending on whether it is
the left or right end panel.
Then assemble the side deflector (Part No.6) if the adjacent panel is a standard depth panel, else follow Step
no.4
VDRB05981-02 73
PIX-36
Step 9: Depending on the adjacent panel follow Step 8 – if adjacent panel is of different length or Step 4 – if
adjacent panel is of same length.
74 VDRB05981-02
PIX-36
VDRB05981-02 75
PIX-36 Annexure C
Before performing work on the panel, it is essential to comply with the following instructions:
Danger!
Risk of fatalities due to high voltage. Isolation from high voltage and earthing must
always be ensured before performing assembly or maintenance work.
Warning!
After the removal of covers from a switchgear unit, operator safety regarding internal
arcs may be reduced unless the switchgear is isolated from the power supply.
Optimum operator safety is only ensured if the switchgear is completely isolated
from the power supply and earthed during assembly or maintenance work.
Warning!
Risk of injury due to movable parts in mechanical drives. For maintenance work,
isolate from supply voltage
release the circuit breakers energy storing device by switching it OFF-ON-OFF
Close via the earthing switch.
Warning!
The top sides of the panels are not meant to be walked on. Persons may fall through
them, get injured or may damage the panel.
When work has to be performed on the panel top - e.g. assembly of deflectors –
temporarily position a solid base plate to step on.
76 VDRB05981-02
PIX-36
VDRB05981-02 77
PIX-36
Step 2: Start from one end of the switch board, assemble the rear support (Part No. 4) on the panel. Then
mount the assembled top duct on top of the panel as shown.
78 VDRB05981-02
PIX-36
Step 3: Assemble the coupling joints (Part No.5 & 6) under the top duct towards the side of the adjacent
panel as shown.
VDRB05981-02 79
PIX-36
Next repeat Step1 & 2 for the adjacent panel. Then couple together the top ducts of the two adjacent panels.
80 VDRB05981-02
PIX-36
Step 4: Determine on which side – left or right – the tunnel would exit. The tunnel end cover would be on the
opposite side.
Assemble the tunnel end cover (Part No.7) with the top duct on the side as shown.
VDRB05981-02 81
PIX-36
Step 5: Towards the tunnel exit, first assemble the extension cutout for duct (Part No.8) with the top duct and
then assemble to it the duct of 1m length (Part No.9) as shown.
82 VDRB05981-02
PIX-36
VDRB05981-02 83
PIX-36
Step 6: Next assemble the Duct to Duct Joint (Part No.10) under the duct before assembling another duct of
1meter length (Part No.9) as shown.
84 VDRB05981-02
PIX-36
Step 7: Next assemble the angular duct with flap (Part No.11) at the end of the duct as shown.
VDRB05981-02 85
PIX-36
86 VDRB05981-02
PIX-36
The below steps are additional for Top Cable Entry Panel only.
Step 8: Assemble the vertical side deflector (Part No.12) and rear end vertical deflector (Part No.13) behind
the gland plate for top cable entry as shown.
VDRB05981-02 87
PIX-36
Step 9: If the adjacent panel is a Top Cable Entry panel then first assemble the rear support (Part No.14) and
then assemble the rear end vertical deflector (Part No.13) and finally the vertical side deflector (Part No.12).
88 VDRB05981-02
PIX-36
If the adjacent panel is not a Top Cable Entry Panel then assemble another vertical side deflector (Part No.12)
only.
VDRB05981-02 89
Appendices 12 Notes
PIX-36
90 VDRB05981-02
Appendices 12 Notes
PIX-36
VDRB05981-02 91
Appendices 12 Notes
PIX-36
92 VDRB05981-02
© 2021 Schneider Electric. All rights reserved.
Schneider Electric Infrastructure Limited As standards, specifications and designs change from time to time, please ask for
Milestone 87, Vadodara – Halol highway confirmation of the information given in this publication.
Village: Kotambi, Post: Jarod
Vadodara – 391510, Gujarat, India This document has been printed
on ecological paper
www.se.com
The process for switching the circuit-breaker manually involves charging the energy storing device using a handle and then actuating the operating mechanism . Electrically, the process involves actuating the closing release via the bay computer or remote control, with the energy storing device being charged automatically if voltage is applied to the motor. Switching off is similarly handled via an opening release, under voltage release, or a secondary release . Position indicators on the circuit-breaker guide the operator on whether the device is charged or released, and provide possible operating sequences .
Assembly involves determining start and end panel configurations — standard or extended depth — initially positioning front, side, and rear deflectors sequentially . Variants needing adjustments include top cable entry panels where additional side deflectors conform to pipe configurations . Mechanical flexibility in switchboard configurations necessitates adaptive assembly steps differing by panel depth, critical for ensuring structural integrity and airflow management .
Racking-in involves moving the slider to the left, inserting a handle into the drive shaft of the truck, and turning it clockwise until fully positioned in service; its position is verified through an inspection glass . Racking-out follows similar steps, but with counter-clockwise movement, returning the truck to disconnected positions . Important warnings include not performing these operations unless the busbar and outgoing feeder cable are de-energized .
Packaging must protect against mechanical impacts and environmental conditions . During transport, ensuring prevention against shocks and maintaining an upright position is crucial for preserving internal alignments . For storage, conditions need to control humidity and temperature, safeguarding against corrosion and deterioration before installation .
To couple busbar sections, move the truck into service position while ensuring initial conditions such as the circuit-breaker being OFF and the truck in a disconnected state . Engage the circuit-breaker once in the service position to establish the connection . Important precautions include adhering to switching provisions and interlocking conditions to prevent unexpected energizing during coupling .
The energy storing device should be released during maintenance to ensure safety . This involves isolating from supply voltage, and cycling the circuit breaker through OFF-ON-OFF to discharge stored energy . Utilizing the earthing switch to establish a low-voltage state ensures further safety during maintenance .
Assembly begins with positioning a solid base plate for safety on the panel top, as the panels themselves are not safe to stand on. Secure the front deflector on the top of the end panel, followed by side deflectors, and rear deflectors, in that order . Additional steps include fitting supports and repeating this sequence through the switchboard . Safety warnings stress preventing falls and ensuring stability during the installation .
Switchgear operations involve various interlocks such as mechanical, electromagnetic, and those utilizing padlocks. These are designed to prevent improper sequences such as operation without de-energizing switches or engaging incorrectly positioned components . For instance, mechanical interlocks prevent operation of circuit-breakers when the earthing switch is engaged, while padlocks secure switches in place to deter unauthorized access, contributing significantly to operational safety by enforcing correct operating sequences and access control .
Maintenance should incorporate cleaning routines to prevent airborne contaminants from contributing to condensation . Corrosion can be mitigated through regular checks on seals and using dehumidifiers or heaters to manage internal climate . These practices ensure electrical reliability and longevity of components by maintaining a stable, moisture-free environment .
To operate the earthing switch, ensure the initial condition where the circuit-breaker is OFF and the earthing switch is also OFF. The truck should be in a disconnected position. Rotate the flap anticlockwise to access the operating shaft, insert the operating handle, and rotate it 90 degrees anticlockwise to close the earthing switch. Verify the switch is ON by checking from the rear cover, then remove the handle . Safety precautions include not engaging the earthing switch if the circuit breaker is in the SERVICE position and ensuring the setup is isolated and de-energized .