Troubleshooting RXi Alarm Codes

Code 133 refers to an error with the tilt transmission and position transducer. Possible causes include a faulty potentiometer, disconnected or incorrect cables, or issues with circuit boards 25S3 and 25S1. Troubleshooting involves checking connections, replacing faulty components, and restoring power if needed.

Uploaded by

rasim yavuz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
676 views67 pages

Troubleshooting RXi Alarm Codes

Code 133 refers to an error with the tilt transmission and position transducer. Possible causes include a faulty potentiometer, disconnected or incorrect cables, or issues with circuit boards 25S3 and 25S1. Troubleshooting involves checking connections, replacing faulty components, and restoring power if needed.

Uploaded by

rasim yavuz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • Alarm 001: Describes the transmission of tilt errors and provides solutions for corresponding potentiometer and cable issues.
  • Alarm 002: Addresses transmission delays and activation issues leading to suspension of equipment movement.
  • Alarm 003: Explains errors during tilt activation due to incorrect motor direction and gives corrective actions.
  • Alarm 011: Details transmission errors during elevation and rotation activation including potentiometer faults.
  • Alarm 012: Covers sporadic transmission issues and potential electrical faults affecting equipment reliability.
  • Alarm 013: Discusses transmission errors related to directional consistency during both activation and rotation phases.
  • Alarm 015: Involves elevation synchronization errors and the subsequent solutions for motor reversibility problems.
  • Alarm 022: Focuses on tube support transmission errors in static and dynamic operation modes.
  • Alarm 023: Addresses elevation transmission errors affecting tube support while maneuvering at various stages.
  • Alarm 024: Explains synchronous movement and elevation transmission errors in equipment control.
  • Alarm 026: Informs about simultaneous dynamic range error issues affecting the synchronized control systems.
  • Alarm 028: Describes transmission errors causing operational adjustments and error control on the equipment's display system.
  • Alarm 031: Lists errors due to improper serial radiographic design transmission impacting performance.
  • Alarm 034: Deals with radiographic design protocols errors and troubleshooting methods during dynamic operations.
  • Alarm 037: Covers design and functional issues with related circuits transmitting synchronization signals.
  • Alarm 041: Elaborates on the synchronization of tube focus during different phases and corrects configuration orders.
  • Alarm 042: Discusses correction for detected errors in the equipment calibration settings and actuator dysfunctions.
  • Alarm 051: Provides solutions to calibration errors due to positional and rotational misalignments during operations.
  • Alarm 061: Highlights transmission failures, focusing on auxiliary control connections and corrective solutions.
  • Alarm 071: Addresses serious transmission errors affecting the iris collimator and operational adjustments.
  • Alarm 081: Emphasizes transmission failures in the adjustment of parallel diaphragms and associated error resolutions.
  • Alarm 091: Details control errors caused by transmission misalignments in cross-diagram functions.
  • Alarm 092: Outlines solutions for design and program error transmission involving synchronization failures.
  • Alarm 096: Describes the prevention of remote control error impacts during transmission adjustments.
  • Alarm 097: Concerns joysticks and remote keypad errors impacting equipment's operational modes.
  • Alarm 101: Involves alarm triggers from operational delays in parallel signal processing.
  • Alarm 111: Describes troubleshooting for potentiometer detection and functional adjustments.
  • Alarm 122: Covers dynamic errors affecting longitudinal transmission and actuator positional accuracy.
  • Alarm 131: Specifies traversed drawer functionality errors and their respective solution implementations.
  • Alarm 143: Describes procedures to address significant serial errors impacting transmitter behavior during normal operations.

Return to RXi Support Enter the Error or Alarm Code 133 GO

GE MEDICAL SYSTEMS in Pthe box


RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.4 Alarm 001


Code 001 refers to the transmission of the tilt and in particular to the position transducer
(potentiometer and related circuits).
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Possible alarm causes Problem solution

Potentiometer 3PT1 fault Replace potentiometer. Reconnect, reacquire


and check control stops following setup
procedure.

Potentiometer 3PT1 exceeds acquisition Bring tilt within defined limits, following
limits setup procedure or manually. Recheck control
stops.

Tie cable disconnected between board 25S3 Reconnect cable.


and 3PT1 CAUTION must be exercised with the screen
earth connection.

Interruption in tie cable between board 25S3 Replace cable.


and 3PT1

Incorrect connections in tie cable between Refer to functional diagrams to restore


board 25S3 and 3PT1 connections.

Tracks interruptions on board 25S3 Restore connections or replace board.

Rosin joints on the connectors of board 25S3 Restore joints or replace board.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

Fault on reading circuit ADC1 of board 25S1 Replace board.


CPU

6
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

+/-15V failure on power supplies of reading Check fuses on board 25S1, the power
circuit ADC1 in board 25S1 supplies and connections from the service
transformer, fuses and power supplies on
transformer.
Replace fuses or board 25S1, restore
connections, and replace fuses or auxiliaries
transformer 22TR2.

Sporadic errors Error caused by external interferences.


To restore activation switch the equipment off
and on.

1.5 Alarm 002


Code 002 refers to the transmission of the tilt and in particular to activation 23S1.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled; the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Activation 23S1 absent or not functional While equipment is switched off insert or
LED OK: OFF replace activation.

Activation powered by an out of range Check board 23S9 and especially fuses, the
voltage value power supplies and connections from the
LED OK: OFF power transformer, the power supplies of the
transformer and line voltage.
Replace fuses or board 23S9, restore
connections, and replace fuses or power
transformer 22TR1.

7
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Inverted motor connection Invert motor connection.


LED O.K.: OFF
LED m.d.: ON

Motor disconnected Refer to functional diagrams to restore


LED O.K.: OFF connections.
LED O.C.: ON

Motor short-circuit Check Motor, the generator/activation tie


LED O.K.: OFF cable, board 23S9 and activation 23S1.
LED O.C.: ON Replace Motor Reducer, tie cable, boards
23S9 and 23S1.

Inverted generator connection Invert generator connection.


LED O.K.: OFF
LED m.d.: ON

Generator disconnected Refer to functional diagrams to restore


LED O.K.: OFF connections.
LED m.d.: ON

Generator short-circuit Check generator, the generator/activation tie


LED O.K.: OFF cable, board 23S9 and activation 23S1.
LED m.d.: ON Replace Motor Reducer, tie cable, boards
23S9 and 23S1.

Activation blocked by thermal protection Use of continuous transmission function.


LED O.K.: OFF To restore operation switch activation off, let
LED S.T.: ON it cool down and switch it back on.

Tracks interruptions on board 23S9 Restore connections or replace board.


Input 25S3-IN21 off
Output 25S3-OUT14 off
Dac VAN3 out of range

8
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Interruption in flat-cable 23S9CFC1- Replace flat-cable.


25S3CFC1
Input 25S3-IN21 off
Output 25S3-OUT14 off
Dac VAN3 out of range

Rosin joints on the connectors of board 23S9 Restore joints or replace boards.
and 25S3
Input 25S3-IN21 off
Output 25S3-OUT14 off
Dac VAN3 out of range

Input 25S3-IN21 not functional Refer to testing manual to check with Test
Output 25S3-OUT14 not functional SW.
Dac VAN3 out of range Replace board I/O 25S3, CPU 25S1 and flat-
cables.

Power supply failure +24Vcc on board 25S3 Check connections, power supplies on boards
for digital input/output 25S3, the power supplies from the service
transformer, fuses and power supplies on
transformer.
Replace board 25S3, connections, fuses or
auxiliaries transformer.

Power supply failure +5Vcc or +/-12Vcc on Check connections, power supplies and fuses
board 25S1 for digital input/output on boards 25S1, the power supplies from the
service transformer, fuses and power supplies
on transformer.
Replace board 25S1, connections, fuses or
auxiliaries transformer.

9
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.6 Alarm 003


Code 003 refers to the transmission of the tilt during movement. Through the position
transducer (potentiometer and related circuits) the software determines the incorrect direction
of the movement.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Inverted motor and generator Refer to functional diagrams to restore


connections.

Inverted dac connections Refer to functional diagrams to restore


connections.

All events that may cause error 001 See error 001.
(problems with potentiometer and related
circuits)

1.7 Alarm 004


Code 004 refers to the transmission of the tilt and in particular to the motor reducer.
Through the position transducer (potentiometer and related circuits) the software determines
the movement without command of the transmission.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Motor reducer reversibility Replace motor reducer.

All events that may cause error 001 See error 001.
(problems with potentiometer and related
circuits)

10
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.8 Alarm 011


Code 011 refers to the transmission of the elevation and in particular to the position
transducer (potentiometer and related circuits).
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Potentiometer 3PT2 not functional Replace potentiometer. Reconnect, reacquire


and check control stops following setup
procedure.

Potentiometer 3PT2 exceeds acquisition Bring transmission within control stops


limits defined limits, following setup procedure or
manually. Recheck control stops.

Tie cable disconnected between board 25S3 Reconnect cable.


and 3PT2 CAUTION must be exercised with the screen
earth connection.

Interruption in tie cable between board 25S3 Replace cable.


and 3PT2

Incorrect connections in tie cable between Refer to functional diagrams to restore


board 25S3 and 3PT2 connections.

Tracks interruptions on board 25S3 Restore connections or replace board.

Rosin joints on the connectors of board 25S3 Restore joints or replace board.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

Fault on reading circuit ADC2 of board 25S1 Replace board.


CPU

11
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Power supply failure +/-15V of reading Check fuses on board 25S1, the power
circuit ADC2 of board 25S1 supplies from the service transformer, the
connections, fuses and power supplies of the
transformer.
Replace fuses or board 25S1, restore
connections, replace fuses or auxiliaries
transformer.

Sporadic errors Error caused by external interferences.


To restore activation switch the equipment off
and on.

1.9 Alarm 012


Code 012 refers to the elevation transmission and in particular to activation 23S2.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Activation 23S2 absent or not functional While equipment is switched off insert or
LED OK: OFF replace activation.

Activation powered by an out of range Check board 23S9 and especially fuses, the
voltage value power supplies and connections from the
LED OK: OFF power transformer, power supplies and line
voltage.
Replace fuses or board 23S9, restore
connections, replace fuses or power
transformer 22TR1.

12
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Inverted motor connection Invert motor connection.


LED O.K.: OFF
LED m.d.: ON

Motor disconnected Refer to functional diagrams to restore


LED O.K.: OFF connections.
LED O.C.: ON

Motor short-circuit Check Motor, the generator/activation tie


LED O.K.: OFF cable, board 23S9 and activation 23S2.
LED O.C.: ON Replace Motor Reducer, tie cable, board
23S9 and 23S2.

Inverted generator connector Invert generator connection.


LED O.K.: OFF
LED m.d.: ON

Generator disconnected Refer to functional diagrams to restore


LED O.K.: OFF connections.
LED m.d.: ON

Generator short-circuit Check generator, the generator/activation tie


LED O.K.: OFF cable, board 23S9 and activation 23S2.
LED m.d.: ON Replace Motor Reducer, tie cable, board
23S9 and 23S2.

Activation blocked by thermal protection Use of continuous transmission function.


LED O.K.: OFF To restore operation switch activation off, let
LED S.T.: ON it cool down and switch it back on.

Tracks interruptions on board 23S9 Restore connections or replace board.


Input 25S3-IN22 off
Output 25S3-OUT20 off
Dac VAN4 out of range

13
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Interruption in flat-cable 23S9CFC1- Replace flat-cable.


25S3CFC1
Input 25S3-IN22 off
Output 25S3-OUT20 off
Dac VAN4 out of range

Rosin joints on the connectors of board 23S9 Restore joints or replace boards.
and 25S3
Input 25S3-IN22 off
Output 25S3-OUT20 off
Dac VAN4 out of range

Input 25S3-IN22 not functional Refer to testing manual to check with Test
Output 25S3-OUT20 not functional SW.
Dac VAN4 out of range Replace board I/O 25S3, CPU 25S1 and flat-
cables.

Power supply failure +24Vcc on board 25S3 Check connections, power supplies on boards
for digital input/output 25S3, the power supplies from the service
transformer, fuses on transformer and power
supplies.
Replace board 25S3, restore connections,
replace fuses or auxiliaries transformer.

Power supply failure +5Vcc or +/-12Vcc on Check connections, power supplies on boards
board 25S1 for digital input/output 25S1, the power supplies from the service
transformer, fuses and power supplies on
transformer.
Replace boards 25S1, restore connections,
replace fuses or auxiliaries transformer

14
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.10 Alarm 013


Code 013 refers to the transmission of the elevation during movement. Through the position
transducer (potentiometer and related circuits) the software determines the incorrect direction
of the movement.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Inverted motor and generator Refer to functional diagrams to restore


connections.

Inverted dac connections Refer to functional diagrams to restore


connections.

All events that may cause error 011 See error 011.
(problems with potentiometer and related
circuits)

1.11 Alarm 014


Code 014 refers to the transmission of the elevation and in particular to the motor reducer.
Through the position transducer (potentiometer and related circuits) the software determines
the movement without command of the transmission.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Motor reducer reversibility Replace motor reducer.

All events that may cause error 011 See error 011.
(problems with potentiometer and related
circuits)

15
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.12 Alarm 015


Code 015 refers to the transmission of the elevation during the synchronised movement with
the tilt.
Through the position transducers (potentiometers and related circuits) the software
determines the incorrect direction of the movements.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Inverted motor and generator due to tilt and Refer to functional diagrams to restore
elevation connections.

Inverted dac connections due to tilt and Refer to functional diagrams to restore
elevation connections.

All events that may cause error 001 and 011 See error 001 and 011.
(problems with potentiometer and related
circuits)

1.13 Alarm 021


Code 021 refers to the transmission of the tube support and in particular to the position
transducer (potentiometer and related circuits).
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Potentiometer 3PT3 not functional Replace potentiometer. Reconnect, reacquire


and check control stops following setup
procedure.

Potentiometer 3PT3 exceeds acquisition Bring transmission within control stops


limits defined limits, following setup procedure or
manually and recheck control stops.

Tie cable disconnected between board 25S3 Reconnect cable.


and 3PT3 CAUTION must be exercised with the screen
earth connection.

16
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Interruption in tie cable between board 25S3 Replace cable.


and 3PT3

Incorrect connections in tie cable between Refer to functional diagrams to restore


board 25S3 and 3PT3 connections.

Tracks interruptions on board 25S3 Restore connections or replace board.

Rosin joints on the connectors of board 25S3 Restore joints or replace board.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

Fault on reading circuit ADC3 of board 25S1 Replace board.


CPU

Power supply failure +/-15V of reading Check fuses on board 25S1, the power
circuit ADC3 of board 25S1 supplies from the service transformer, the
connections, fuses and power supplies of the
transformer.
Replace fuses or board 25S1, restore
connections, replace fuses or auxiliaries
transformer 22TR1.

Sporadic errors Error caused by external interferences.


To restore activation switch the equipment off
and on.

17
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.14 Alarm 022


Code 022 refers to the transmission of the tube support and in particular to activation 23S3.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Activation 23S3 absent or not functional While equipment is switched off insert or
LED OK: OFF replace activation
Activation powered by an out of range Check board 23S9 and especially fuses, the
voltage value power supplies and connections from the
LED OK: OFF power transformer, power supplies and line
voltage.
Replace fuses or board 23S9, restore
connections, replace fuses or power
transformer 22TR1.

Inverted motor connection Invert motor connection.


LED O.K.: OFF
LED m.d.: ON

Motor disconnected Refer to functional diagrams to restore


LED O.K.: OFF connections.
LED O.C.: ON

Motor short-circuit Check Motor, the generator/activation tie


LED O.K.: OFF cable, board 23S9 and activation 23S3.
LED O.C.: ON Replace Motor Reducer, tie cable, boards
23S9 and 23S3.

Inverted generator connection Invert generator connection.


LED O.K.: OFF
LED m.d.: ON

Disconnected generator Refer to functional diagrams to restore


LED O.K.: OFF connections.
LED m.d.: ON

18
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Generator short-circuit Check generator, the generator/activation tie


LED O.K.: OFF cable, board 23S9 and activation 23S3.
LED m.d.: ON Replace Motor Reducer, tie cable, boards
23S9 and 23S3.

Activation blocked by thermal protection Use of continuous transmission function.


LED O.K.: OFF To restore operation switch equipment off, let
LED S.T.: ON it cool down and switch it back on.

Tracks interruptions on board 23S9 Restore connections or replace board.


Input 25S3-IN11 off
Output 25S3-OUT13 off
Dac VAN1 out of range

Interruption in flat-cable 23S9CFC1- Replace flat-cable.


25S3CFC1
Input 25S3-IN11 off
Output 25S3-OUT13 off
Dac VAN1 out of range

Rosin joints on the connectors of board 23S9 Restore joints or replace boards.
and 25S3
Input 25S3-IN11 off
Output 25S3-OUT13 off
Dac VAN1 out of range

Input 25S3-IN11 not functional Refer to testing manual to check with Test
Output 25S3-OUT13 not functional SW.
Dac VAN1 out of range Replace board I/O 25S3, CPU 25S1 and flat-
cable.

19
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Power supply failure +24Vcc for input/output Check connections, power supplies on boards
board 25S3 25S3, the power supplies from the service
transformer, fuses on transformer and power
supplies.
Replace board 25S3, restore connections,
replace fuses or auxiliaries transformer.

Power supply failure +5Vcc or +/-12Vcc for Check connections, power supplies and fuses
input/output board 25S1 on boards 25S1, the power supplies from the
service transformer, fuses and power supplies
on transformer.
Replace board 25S1, restore connections,
replace fuses or auxiliaries transformer

1.15 Alarm 023


Code 023 refers to the transmission of the tube support during movement in dynamic area.
Through the position transducer (potentiometer and related circuits) the software determines
the incorrect direction of movement.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Inverted motor and generator Refer to functional diagrams to restore


connections.

Inverted dac connections Refer to functional diagrams to restore


connections.

All events that may cause error 021 See error 021.
(problems with potentiometer and related
circuits)

20
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.16 Alarm 024


Code 024 refers to the transmission of the tube support during movement in
angling/centering. Through the position transducer (potentiometer and related circuits) the
software defines the incorrect direction of movement.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Inverted motor and generator Refer to functional diagrams to restore


connections.

Inverted dac connections Refer to functional diagrams to restore


connections.

All events that may cause error 021 See error 021.
(problems with potentiometer and related
circuits)

1.17 Alarm 025


Code 025 refers to the transmission of the tube support during movement in tomography.
Through the position transducer (potentiometer and related circuits) the software determines
the incorrect direction of movement.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Inverted motor and generator Refer to functional diagrams to restore


connections.

Inverted dac connections Refer to functional diagrams to restore


connections.

All events that may cause error 021 See error 021.
(problems with potentiometer and related
circuits)

21
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.18 Alarm 026


Code 026 refers to the transmission of the tube support during simultaneous movement of
dynamic area and angling/centering. Through the position transducer (potentiometer and
related circuits) the software determines the incorrect direction of movement.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Inverted motor and generator Refer to functional diagrams to restore


connections.

Inverted dac connections Refer to functional diagrams to restore


connections.

All events that may cause error 021 See error 021.
(problems with potentiometer and related
circuits)

1.19 Alarm 027


Code 027 refers to the transmission of the tube support and in particular to the motor reducer.
Through the position transducer (potentiometer and related circuits) the software determines
the movement without command of the transmission.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Motor reducer reversibility Replace motor reducer.

All events that may cause error 021 See error 021.
(problems with potentiometer and related
circuits)

22
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.20 Alarm 028


Code 028 refers to the transmission of the tube support and in particular it is activated when
there is an angle with the serial radiographic design higher than 42°.
Through the position transducer (potentiometer and related circuits) the software determines
the incorrect direction of movement, to avoid the disengagement of the rod.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the layer display flashes and shows the alarm code while the remaining displays
switch off.

Events that may cause the error Problem solution

Inverted motor and generator tube support or Refer to functional diagrams to restore
serial radiographic design connections.

Inverted dac connections tube support or Refer to functional diagrams to restore


serial radiographic design connections.

All events that may cause errors 021-031 See errors 021-031.
(problems with potentiometers and related
circuits)

23
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.21 Alarm 031


Code 031 refers to the transmission of the serial radiographic design and in particular to the
position transducer (potentiometer and related circuits).
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Potentiometer 3PT4 not functional Replace potentiometer. Reconnect, reacquire


and check control stops following setup
procedure.

Potentiometer 3PT4 exceeds acquisition Bring transmission within defined control


limits stops limits, following setup procedure or
manually and recheck control stops.

Tie cable disconnected between board 25S3 Reconnect cable.


and 3PT4 CAUTION must be exercised with the screen
earth connection.

Interruption in tie cable between board 25S3 Replace cable.


and 3PT4

Incorrect connections in tie cable between Refer to functional diagrams to restore


board 25S3 and 3PT4 connections.
.
Tracks interruptions on board 25S3 Restore connections or replace board.

Rosin joints on the connectors of board 25S3 Restore joints or replace board.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

Fault on reading circuit ADC4 of board 25S1 Replace board.


CPU

24
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Power supply failure +/-15V reading circuit Check fuses on board 25S1, the power
ADC4 of board 25S1 supplies from the service transformer, the
connections, fuses and power supplies of the
transformer.
Replace fuses or board 25S1, restore
connections, replace fuses or auxiliaries
transformer.

Sporadic errors Error caused by external interferences.


To restore activation switch the equipment off
and on.

1.22 Alarm 032


Code 032 refers to the transmission of the serial radiographic design and in particular to
activation 23S4.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Activation 23S4 absent or not functional While equipment is switched off insert or
LED OK: OFF replace activation.

Activation powered by an out of range Check board 23S9, fuses on board 23S9, the
voltage value power supplies from the power transformer,
LED OK: OFF the connections and power supplies of the
transformer, line voltage.
Replace fuses or board 23S9, restore
connections, replace fuses or power
transformer 22TR1.

25
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Inverted motor connection Invert motor connection.


LED O.K.: OFF
LED m.d.: ON

Motor disconnected Refer to functional diagrams to restore


LED O.K.: OFF connections.
LED O.C.: ON

Motor short-circuit Check Motor, the generator/activation tie


LED O.K.: OFF cable, board 23S9 and activation 23S4.
LED O.C.: ON Replace Motor Reducer, tie cable, board
23S9 and 23S4.

Inverted generator connection Invert generator connection.


LED O.K.: OFF
LED m.d.: ON

Generator disconnected Refer to functional diagrams to restore


LED O.K.: OFF connections.
LED m.d.: ON

Generator short-circuit Check generator, the generator/activation tie


LED O.K.: OFF cable, board 23S9 and activation 23S4.
LED m.d.: ON Replace Motor Reducer, tie cable, board
23S9 and 23S4.

Activation blocked by thermal protection Use of continuous transmission function.


LED O.K.: OFF To restore operation switch equipment off, let
LED S.T.: ON activation cool down and switch equipment
back on.

Tracks interruptions on board 23S9 Restore connections or replace board.


Input 25S3-IN12 off
Output 25S3-OUT12 off
Dac VAN2 out of range

26
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Interruption in flat-cable 23S9CFC1- Replace flat-cable.


25S3CFC1
Input 25S3-IN12 off
Output 25S3-OUT12 off
Dac VAN2 out of range

Rosin joints on the connectors of board 23S9 Restore joints or replace boards.
and 25S3
Input 25S3-IN12 off
Output 25S3-OUT12 off
Dac VAN2 out of range

Input 25S3-IN12 not functional Refer to testing manual to check with Test
Output 25S3-OUT12 not functional SW.
Dac VAN2 out of range Replace board I/O 25S3, CPU 25S1 and flat-
cables.

Power supply failure +24Vcc for input/output Check connections, power supplies on boards
board 25S3 25S3, the power supplies from the service
transformer, fuses and power supplies on
transformer.
Replace boards 25S3, restore connections,
replace fuses or auxiliaries transformer
22TR1.

Power supply failure +5Vcc or +/-12Vcc for Check connections, power supplies on boards
input/output board 25S1 25S1, fuses on board 25S1, the power
supplies from the service transformer, fuses
on transformer.
Replace board 25S1, restore connections,
replace fuses or auxiliaries transformer.

27
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.23 Alarm 033


Code 033 refers to the transmission of the serial radiographic design during movement in
dynamic area. Through the position transducer (potentiometer and related circuits) the
software determines the incorrect direction of movement.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Inverted motor and generator Refer to functional diagrams to restore


connections.

Inverted dac connections Refer to functional diagrams to restore


connections.

All events that may cause error 031 See error 031.
(problems with potentiometer and related
circuits)

1.24 Alarm 034


Code 034 refers to the transmission of the serial radiographic design during movement in
angling/centering. Through the position transducer (potentiometer and related circuits) the
software determines the incorrect direction of movement.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Inverted motor and generator Refer to functional diagrams to restore


connections.

Inverted dac connections Refer to functional diagrams to restore


connections.

All events that may cause error 031 See error 031.
(problems with potentiometer and related
circuits)

28
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.25 Alarm 035


Code 035 refers to the transmission of the serial radiographic design during movement in
tomography. Through the position transducer (potentiometer and related circuits) the
software determines the incorrect direction of movement.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Inverted motor and generator or Refer to functional diagrams to restore


connections.

Inverted dac connections Refer to functional diagrams to restore


connections.

All events that may cause error 031 See error 031.
(problems with potentiometer and related
circuits)

1.26 Alarm 036


Code 036 refers to the transmission of the tube support during the simultaneous movement of
dynamic area and angling/centering. Through the position transducer (potentiometer and
related circuits) the software determines the incorrect direction of movement.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Inverted motor and generator Refer to functional diagrams to restore


connections.

Inverted dac connections Refer to functional diagrams to restore


connections.

All events that may cause error 031 See error 031.
(problems with potentiometer and related
circuits)

29
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.27 Alarm 037


Code 037 refers to the transmission of the serial radiographic design in particular to the
motor reducer. Through the position transducer (potentiometer and related circuits) the
software determines the movement without command of the transmission.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Motor reducer reversibility Replace motor reducer.

All events that may cause error 031 See error 031.
(problems with potentiometer and related
circuits)

1.28 Alarm 041


Code 041 refers to the transmission of the focal point and in particular to the position
transducer (reference photocell).
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Microswitch 3FC5 not functional Replace microswitch.

Power amplification board 3S3 not functional Replace power amplification board.

Tie cable disconnected between photocell Reconnect cable.


3FC5 and board 3S3

Interruption in tie cable between photocell Replace cable.


3FC5 and board 3S3

Tie cable disconnected between board 3S3 Reconnect cable.


and 24S9 CAUTION must be exercised with the screen
earth connection.

30
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Interruption in tie cable between board 3S3 Replace cable.


and 24S9

Incorrect connections in cables Refer to functional diagrams to restore


connections.

Tracks interruptions on boards Restore connections or replace boards.

Rosin joints on connectors Restore joints or replace boards.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

1.29 Alarm 042


Code 042 refers to the transmission of the focal point and in particular to activation 24S7.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Activation not powered or powered by an out Check tracks on board 24S9, fuses and
of range voltage value operation of power supply board 24S5, the
LED HV: OFF power supplies from the power transformer,
LED FAU: ON the connections, fuses and power supplies of
the transformer, line voltage.
Replace board 24S9, 24S7, fuses or board
24S5, restore connections, replace fuses or
power transformer 22TR1.

Activation powered by an out of range Check line voltage, the operation of power
voltage value supply board 24S5, the power supplies of the
LED HV: OFF transformer. Replace board 24S5 and power
LED FAU: ON transformer 22TR1.

31
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Activation blocked by thermal protection Ventilators off or not functional, use of


LED TER: ON continuous transmission function.
LED FAU: ON To restore operation switch activation off, let
it cool down and switch the equipment back
on.

Motor short-circuit Check tracks of board 24S9, the tie cable of


LED HV: ON activation/motor and of motor 3MT5.
LED FAU: ON Replace cable and motor.

Incorrect motor connection Refer to functional diagrams to restore


LED HV: ON connections.
LED FAU: ON

Tracks interruptions on board 24S9 Restore connections or replace board.


Input 25S2-IN4 off

Interruption in flat-cable 24S9CFC2- Replace flat-cable.


25S2CN2
Input 25S2-IN4 off

Rosin joints on the connectors of board 24S9 Restore joints or replace boards.
and 25S2
Input 25S2-IN4 off

Input 25S2-IN4 not functional Replace axes board 25S2.

Power supply failure +12Vcc for input/output Check connections, power supplies on board
board 25S2 24S9 and 24S5, fuses on power supply board
24S5, the power supplies from the service
transformer, fuses on transformer and power
supplies.
Replace boards 25S2, 24S9 and 24S5, restore
connections, replace fuses or auxiliaries
transformer.

32
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.30 Alarm 051


Code 051 refers to the transmission of the parallel collimator and in particular to the position
transducer (potentiometer and related circuits).
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Potentiometer 3PT7 not functional Replace potentiometer. Reconnect, reacquire


and check control stops following setup
procedure

Potentiometer 3PT7 exceeds acquisition Bring transmission within control stops


limits defined limits, following setup procedure or
manually. Recheck control stops.

Tie cable disconnected between board 25S3 Reconnect cable.


and 3PT7 CAUTION must be exercised with the screen
earth connection.

Interruption in tie cable between board 25S3 Replace cable.


and 3PT7

Incorrect connections in tie cable between Refer to functional diagrams to restore


board 25S3 and 3PT7 connections.

Tracks interruptions on board 25S3 Restore connections or replace board.

Rosin joints on the connectors of board 25S3 Restore joints or replace board.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

Fault on reading circuit ADC7 of board 25S1 Replace board.


CPU

33
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Power supply failure +/-15V reading circuit Check fuses on board 25S1, the power
ADC7 of board 25S1 supplies from the service transformer, the
connections, fuses and power supplies of the
transformer.
Replace fuses or board 25S1, restore
connections, replace fuses or auxiliaries
transformer 22TR1.

Sporadic errors Error caused by external interferences.


To restore activation switch the equipment off
and on.

1.31 Alarm 052


Code 052 refers to the transmission of the parallel collimator during movement.
Through the position transducer (potentiometer and related circuits) the software determines
the incorrect direction of movement.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Tie cable disconnected between board 23S8 Reconnect cable.


and collimator

Interruption in tie cable between board 23S8 Replace cable.


and collimator

Incorrect connections in tie cable between Refer to functional diagrams to restore


board 23S8 and collimator connections.

Tracks interruptions on board 23S10 Restore connections or replace board.


Input 25S3-IN17 off
Output 25S3-OUT23 off
Dac VAN5 out of range

34
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Fault on board 23S8 Restore and replace board.

Interruption in flat-cable 23S10CFC1- Replace flat-cable.


25S3CFC2
Input 25S3-IN17 off
Output 25S3-OUT23 off
Dac VAN5 out of range

Rosin joints on the connectors of board 23S9 Restore joints or replace boards.
and 25S3
Input 25S3-IN17 off
Output 25S3-OUT23 off
Dac VAN5 out of range

Input 25S3-IN17 not functional Refer to testing manual to check with Test
Output 25S3-OUT23 not functional SW.
Dac VAN5 out of range Replace board I/O 25S3, CPU 25S1 and flat-
cable.

Power supply failure +24Vcc for input/output Check connections, power supplies on boards
board 25S3 25S3, the power supplies from the service
transformer, fuses on transformer and power
supplies.
Replace board 25S3, restore connections,
replace fuses or auxiliaries transformer.

Power supply failure +5Vcc or +/-12Vcc for Check connections, power supplies and fuses
input/output board 25S1 on boards 25S1, the power supplies from the
service transformer, fuses and power supplies
on transformer.
Replace board 25S1, restore connections,
replace fuses or auxiliaries transformer.

35
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.32 Alarm 061


Code 061 refers to the transmission of the perpendicular collimator and in particular to the
position transducer (potentiometer and related circuits).
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Potentiometer 3PT8 not functional Replace potentiometer. Reconnect, reacquire


and check control stops following setup
procedure

Potentiometer 3PT8 exceeds acquisition Bring transmission within control stops


limits defined limits, following setup procedure or
manually. Recheck control stops.

Tie cable disconnected between board 25S3 Reconnect cable.


and 3PT8 CAUTION must be exercised with the screen
earth connection.

Interruption in tie cable between board 25S3 Replace cable.


and 3PT8

Incorrect connections in tie cable between Refer to functional diagrams to restore


board 25S3 and 3PT8 connections.

Tracks interruptions on board 25S3 Restore connections or replace board.

Rosin joints on the connectors of board 25S3 Restore joints or replace board.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

Fault on reading circuit ADC8 of board 25S1 Replace board.


CPU

36
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Power supply failure +/-15V reading circuit Check fuses on board 25S1, the power
ADC8 of board 25S1 supplies from the service transformer, the
connections, fuses and power supplies of the
transformer.
Replace fuses or board 25S1, restore
connections, replace fuses or auxiliaries
transformer 22TR1.

Sporadic errors Error caused by external interferences.


To restore activation switch the equipment off
and on.

1.33 Alarm 062


Code 062 refers to the transmission of the perpendicular collimator during movement.
Through the position transducer (potentiometer and related circuits) the software determines
the incorrect direction of movement.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Tie cable disconnected between board 23S8 Reconnect cable.


and collimator

Interruption in tie cable between board 23S8 Replace cable.


and collimator

Incorrect connections in tie cable between Refer to functional diagrams to restore


board 23S8 and collimator connections.

Tracks interruptions on board 23S10 Restore connections or replace board.


Input 25S3-IN17 off
Output 25S3-OUT23 off
Dac VAN6 out of range

37
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Fault on board 23S8 Restore or replace board.

Interruption in flat-cable 23S10CFC1- Replace flat-cable.


25S3CFC2
Input 25S3-IN17 off
Output 25S3-OUT23 off
Dac VAN6 out of range

Rosin joints on the connectors of board 23S9 Restore joints or replace boards.
and 25S3
Input 25S3-IN17 off
Output 25S3-OUT23 off
Dac VAN6 out of range

Input 25S3-IN17 not functional Refer to testing manual to check with Test
Output 25S3-OUT23 not functional SW.
Dac VAN6 out of range Replace board I/O 25S3, CPU 25S1 and flat-
cable.

Power supply failure +24Vcc for input/output Check connections, power supplies on boards
board 25S3 25S3, the power supplies from the service
transformer, fuses on transformer and power
supplies.
Replace board 25S3, restore connections,
replace fuses or auxiliaries transformer.

Power supply failure +5Vcc or +/-12Vcc for Check connections, power supplies and fuses
input/output board 25S1 on boards 25S1, the power supplies from the
service transformer, fuses and power supplies
on transformer.
Replace board 25S1, restore connections,
replace fuses or auxiliaries transformer.

38
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.34 Alarm 071


Code 071 refers to the transmission of the iris collimator and in particular to the position
transducer (potentiometer and related circuits).
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Potentiometer 3PT9 not functional Replace potentiometer. Reconnect, reacquire


and check control stops following setup
procedure.

Potentiometer 3PT9 exceeds acquisition Bring transmission within control stops


limits defined limits, following setup procedure or
manually and recheck control stops.

Tie cable disconnected between board 25S3 Reconnect cable.


and 3PT9 CAUTION must be exercised with the screen
earth connection.

Interruption in tie cable between board 25S3 Replace cable.


and 3PT9

Incorrect connections in tie cable between Refer to functional diagrams to restore


board 25S3 and 3PT9 connections.

Tracks interruptions on board 25S3 Restore connections or replace board.

Rosin joints on the connectors of board 25S3 Restore joints or replace board.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

Fault on reading circuit ADC9 of board 25S1 Replace board.


CPU

39
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Power supply failure +/-15V reading circuit Check fuses on board 25S1, the power
ADC9 of board 25S1 supplies from the service transformer, the
connections, fuses and power supplies of the
transformer.
Replace fuses or board 25S1, restore
connections, replace fuses or auxiliaries
transformer 22TR2.

Sporadic errors Error caused by external interferences.


To restore activation switch the equipment off
and on.

1.35 Alarm 072


Code 072 refers to the transmission of the iris collimator during movement.
Through the position transducer (potentiometer and related circuits) the software determines
the incorrect direction of movement.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Tie cable disconnected between board 23S8 Reconnect cable.


and collimator

Interruption in tie cable between board 23S8 Replace cable.


and collimator

Incorrect connections in tie cable between Refer to functional diagrams to restore


board 23S8 and collimator connections.

Tracks interruptions on board 23S10 Restore connections or replace board.


Input 25S3-IN17 off
Output 25S3-OUT23 off
Dac VAN7 out of range

Fault on board 23S8 Restore and replace board.

40
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Interruption in flat-cable 23S10CFC1- Replace flat-cable.


25S3CFC2
Input 25S3-IN17 off
Output 25S3-OUT23 off
Dac VAN7 out of range

Rosin joints on the connectors of board 23S9 Restore joints or replace boards.
and 25S3
Input 25S3-IN17 off
Output 25S3-OUT23 off
Dac VAN7 out of range

Input 25S3-IN17 not functional Refer to testing manual to check with Test
Output 25S3-OUT23 not functional SW.
Dac VAN7 out of range Replace board I/O 25S3, CPU 25S1 and flat-
cable.

Power supply failure +24Vcc for input/output Check connections, power supplies on boards
board 25S3 25S3, the power supplies from the service
transformer, fuses and power supplies on
transformer.
Replace boards 25S3, restore connections,
replace fuses or auxiliaries transformer.

Power supply failure +5Vcc or +/-12Vcc for Check connections, power supplies and fuses
input/output board 25S1 on boards 25S1, the power supplies from the
service transformer, the fuses and power
supplies of the transformer.
Replace board 25S1, restore connections,
replace fuses or auxiliaries transformer.

41
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.36 Alarm 081


Code 081 refers to the transmission of the parallel diaphragms and in particular to the
position transducer (reference photocell).
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Photocell 3FC16 not functional Replace photocell.

Power amplification board 3S3 not functional Replace power amplification board.

Tie cable disconnected between photocell Reconnect cable.


3FC16 and board 3S3

Interruption in tie cable between photocell Replace cable.


3FC16 and board 3S3

Tie cable disconnected between board 3S3 Reconnect cable.


and 24S9 CAUTION must be exercised with the screen
earth connection.

Interruption in tie cable between board 3S3 Replace cable.


and 24S9

Incorrect connections in cables Refer to functional diagrams to restore


connections.

Tracks interruptions on boards Restore connections or replace boards.

Rosin joints on connectors Restore joints or replace boards.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

42
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.37 Alarm 082


Code 082 refers to the transmission of the parallel diaphragms and in particular to activation
24S2.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Activation not powered or powered by an out Check tracks on board 24S9, the operation of
of range voltage value power supply board 24S1, fuses on board
LED HV: OFF 24S1, the power supplies from the power
LED FAU: ON transformer, connections to transformer, fuses
on transformer, the power supplies of the
transformer and line voltage.
Replace board 24S9, 24S2, fuses or board
24S1, restore connections, replace fuses or
power transformer 22TR1.

Activation powered by an out of range Check line voltage, the operation of power
voltage value supply board 24S1, the power supplies from
LED HV: OFF the power transformer, the power supplies of
LED FAU: ON the transformer. Replace board 24S1 and
power transformer 22TR1.

Activation blocked by thermal protection Ventilators off or not functional, use of


LED TER: ON continuous transmission function.
LED FAU: ON To restore operation switch activation off, let
it cool down and switch the equipment back
on.

Motor short-circuit Check tracks on board 24S9, the


LED HV: ON activation/motor tie cable and motor 3MT13.
LED FAU: ON Replace cable and motor.

43
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Error in motor connection Refer to functional diagrams to restore


LED HV: ON connections.
LED FAU: ON

Tracks interruptions on board 24S9 Restore connections or replace board.


Input 25S2-IN1 off

Interruption in flat-cable 24S9CFC2- Replace flat-cable.


25S2CN2
Input 25S2-IN1 off

Rosin joints on the connectors of board 24S9 Restore joints or replace boards.
and 25S2
Input 25S2-IN1 off

Input 25S2-IN1 off Replace axes board 25S2.

Power supply failure +12Vcc for input/output Check connections, power supplies on board
board 25S2 24S9 and 24S5, fuses on power supply board
24S5, the power supplies from the service
transformer, fuses on transformer and power
supplies.
Replace board 25S2, 24S9 and 24S5, restore
connections, replace fuses or auxiliaries
transformer.

44
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.38 Alarm 091


Code 091 refers to the transmission of the cross diaphragms and in particular to the position
transducer (reference photocell).
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Photocell 3FC17 not functional Replace photocell.

Power amplification board 3S3 not functional Replace power amplification board.

Tie cable disconnected between photocell Reconnect cable.


3FC17 and board 3S3

Interruption in tie cable between photocell Replace cable.


3FC17 and board 3S3

Tie cable disconnected between board 3S3 Reconnect cable.


and 24S9 CAUTION must be exercised with the screen
earth connection.

Interruption in tie cable between board 3S3 Replace cable.


and 24S9

Incorrect connections in cables Refer to functional diagrams to restore


connections.

Tracks interruptions on boards Restore connections or replace board.

Rosin joints on connectors Restore joints or replace boards.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

45
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.39 Alarm 092


Code 092 refers to the transmission of the cross diaphragms and in particular to activation
24S3.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Activation not powered or powered by an out Check tracks on board 24S9, the operation of
of range voltage value power supply board 24S1, fuses on board
LED HV: OFF 24S1, the power supplies from the power
LED FAU: ON transformer, connections to transformer, fuses
on transformer, the power supplies of the
transformer and line voltage.
Replace board 24S9, 24S3, fuses or board
24S1, restore connections, replace fuses or
power transformer 22TR1.

Activation powered by an out of range Check line voltage, the operation of power
voltage value supply board 24S1, the power supplies from
LED HV: OFF the power transformer, the power supplies of
LED FAU: ON the transformer. Replace board 24S1 and
power transformer 22TR1.

Activation blocked by thermal protection Ventilators off or not functional, use of


LED TER: ON continuous transmission function.
LED FAU: ON To restore operation switch activation off, let
it cool down and switch the equipment back
on.

Motor short-circuit Check tracks on board 24S9, the


LED HV: ON activation/motor tie cable and motor 3MT14.
LED FAU: ON Replace cable and motor.

46
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Error in motor connection Refer to functional diagrams to restore


LED HV: ON connections.
LED FAU: ON

Tracks interruptions on board 24S9 Restore connections or replace board.


Input 25S2-IN2 off

Interruption in flat-cable 24S9CFC2- Replace flat-cable.


25S2CN2
Input 25S2-IN2 off

Rosin joints on the connectors of board 24S9 Restore joints or replace boards.
and 25S2
Input 25S2-IN2 off

Input 25S2-IN2 off Replace axes board 25S2.

Power supply failure +12Vcc for input/output Check connections, power supplies on boards
board 25S2 24S9 and 24S5, fuses on power supply board
24S5, the power supplies from the service
transformer, fuses on transformer and power
supplies.
Replace boards 25S2, 24S9 and 24S5, restore
connections, replace fuses or auxiliaries
transformer.

1.40 Alarm 096


Code 096 refers to the battery of board CPU 25S1. The activation of this alarm interrupts the
ignition of the equipment. All movements are disabled, the angle of tilt display flashes and
shows the code while the remaining displays are switched off. This error must be reset with
keys P57 or P48 to complete the equipment ignition (pulse selection key or 0° tilt). If the
battery is flat the new alarms are not stored and the previous ones are lost.

Events that may cause the error Problem solution

Battery flat Replace battery on board 25S1.

Fault on reading circuit of battery voltage Replace board CPU 25S1.

47
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.41 Alarm 097


Code 097 refers to the keys, joysticks and control levers of console 1S1 and of remote keypad
3S1. The activation of this alarm interrupts the ignition of the equipment. All movements are
disabled, the angle of tilt display flashes and shows the code while the remaining displays are
switched off. This error must be reset with keys P57 or P48 to complete the equipment
ignition (pulse selection key or 0° tilt). While the ignition is on, the movements activated by
controls (pressed at ignition stage) are disabled.

Events that may cause the error Problem solution

Fault on control lever or joystick Replace control lever or joystick.

Fault on connections between control levers Replace or restore connections.


or joysticks and console board 1S1

Fault on console board 1S1 Replace board.

Tie cable fault between console board 1S1 Replace cable.


and board CPU console 1S2.

Fault on CPU Console 1S2 Replace board.

Fault on remote keypad board 3S1 Replace board.

Fault on tie cable between control keypad Replace cable.


board 3S1 and board I/O 25S3.

Fault on board I/O 25S3 Replace board

Tie cable fault between board I/O 25S3 and Replace cable.
board CPU 25S1.

Fault on board CPU 25S1 Replace board

48
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.42 Alarm 098


Code 098 refers to the transmission of data between board CPU 25S1 and console board 1S2.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Fault on board CPU 25S1 Replace board.

Fault on Console board 1S2 Replace board.

Tie cable fault between board CPU 25S1 and Replace cable.
console 1S1 (fiber-optic cable)

Fiber-optic cable disconnected Connect cable.

Connection error on fiber-optic cable Adjust connection.

1.43 Alarm 099


Code 099 refers to the absence of the command of the power transformer connection relay.
All movements are disabled, the angle of tilt display flashes and shows the alarm code while
the remaining displays switch off.

Events that may cause the error Problem solution

Red stop button pressed on console Restore stop button.

Console stop button disconnected from board Restore connections.


1S1

Tracks interruptions or rosin joints on board Restore connections or replace board.


1S1
Tie cable disconnected or incorrect Connect cable or restore connections
connections between board 1S1 and 25S3
Error Code 99
Error Code 99 can be caused by any
switch in the Safety Circuit being open,
this includes:
Two Emergency Off Switches,
II Touchguard Switches
Table Tilt & Elevate Limit Switches
SID Optical Sensor Switch (if fitted)
49
Click on link to see circuit
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Red stop button pressed on remote keypad Restore stop button.

Tie cable disconnected or incorrect Connect cable or restore connections.


connection between IB safety, stop button
and board 25S3

Tilt total safety activated Release tilt safety manually or using setup
procedure. Check software and hardware
control stops.

Tie cable disconnected or incorrect Connect cable or restore connections.


connection between tilt safety and board
25S3

Elevation total safety activated (if present) Release elevation safety manually or
following setup procedure. Check software
and hardware control stops.

Tie cable disconnected or incorrect Connect cable or restore connections.


connection between tilt safety, elevation and
board 25S3
IB safety activated Release IB safety manually or following
setup procedure. Check IB configuration and
safety positioning.

Ceiling safety activated (if present) Release ceiling safety manually or following
setup procedure. Check room configuration
and safety positioning.

Tie cable disconnected or incorrect Connect cable or restore connections.


connection between ceiling safety and board
25S3

Switch 25S3SW1-4 OFF and ceiling safety Turn ON switch 25S3SW1-4.


absent

50
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Watch-dog activated on board CPU 25S1 Check connections of watch-dog contact and
board CPU 25S1.
Adjust connections or replace board.
Incorrect connections between board 25S1 Restore connections.
and 25S3 (watch-dog contact)

Tracks interruptions or rosin joints on board Restore connections or replace board.


25S3

Power supply failure +24Vcc for safety Check connections, power supplies on boards
circuit on board 25S3 25S3, the power supplies from the service
transformer, fuses on transformer and power
supplies.
Replace boards 25S3, restore connections,
replace fuses or auxiliaries transformer.

1.44 Alarm 101


Code 101 refers to the transmission of the parallel jaws and in particular to the position
transducer (potentiometer and related circuits).
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Potentiometer 3PT10 not functional Replace potentiometer. Reconnect, reacquire


and check control stops following setup
procedure.

Potentiometer 3PT10 exceeds acquisition Bring transmission within defined control


limits stops limits following setup procedure or
manually and recheck control stops.

Tie cable disconnected between board 25S3 Reconnect cable.


and 3PT10 CAUTION must be exercised with the screen
earth connection.

51
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Interruption in tie cable between board 25S3 Replace cable.


and 3PT10

Incorrect connections in tie cable between Refer to functional diagrams to restore


board 25S3 and 3PT10 connections.

Tracks interruptions on board 25S3 Restore connections or replace board.

Rosin joints on the connectors of board 25S3 Restore joints or replace board.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

Fault on reading circuit ADC10 of board Replace board.


25S1 CPU

Power supply failure +/-15V of reading Check fuses on board 25S1, the power
circuit ADC10 of board 25S1 supplies from the service transformer, the
connections, fuses and power supplies of the
transformer.
Replace fuses or board 25S1, restore
connections, replace fuses or auxiliaries
transformer 22TR2.

Sporadic errors Error caused by external interferences.


To restore activation switch the equipment off
and on.

52
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.45 Alarm 111


Code 111 refers to the transmission of the perpendicular jaws and in particular to the position
transducer (potentiometer and related circuits).
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Potentiometer 3PT11 not functional Replace potentiometer. Reconnect, reacquire


and check control stops following setup
procedure.

Potentiometer 3PT11 exceeds acquisition Bring transmission within control stops


limits defined limits following setup procedure or
manually and recheck control stops.

Tie cable disconnected between board 25S3 Reconnect cable.


and 3PT11 CAUTION must be exercised with the screen
earth connection.

Interruption in tie cable between board 25S3 Replace cable.


and 3PT11

Incorrect connections in tie cable between Refer to functional diagrams to restore


board 25S3 and 3PT11 connections.

Tracks interruptions on board 25S3 Restore connections or replace board.

Rosin joints on the connectors of board 25S3 Restore joints or replace board.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

Fault on reading circuit ADC11 of board Replace board.


25S1 CPU

53
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Power supply failure +/-15V reading circuit Check fuses on board 25S1, the power
ADC11 of board 25S1 supplies from the service transformer, the
connections, fuses and power supplies of the
transformer.
Replace fuses or board 25S1, restore
connections, replace fuses or auxiliaries
transformer 22TR2.

Sporadic errors Error caused by external interferences.


To restore activation switch the equipment off
and on.

1.46 Alarm 121


Code 121 refers to the transmission of the longitudinal drawer and in particular to the
position transducer (reference photocell).
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Photocell 3FC14 not functional Replace photocell.

Power amplification board 3S3 not functional Replace power amplification board.

Tie cable disconnected between photocell Reconnect cable.


3FC14 and board 3S3

Interruption in tie cable between photocell Replace cable.


3FC14 and board 3S3

Tie cable disconnected between board 3S3 Reconnect cable.


and 24S9 CAUTION must be exercised with the screen
earth connection.

54
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Interruption in tie cable between board 3S3 Replace cable.


and 24S9

Incorrect connections in cables Refer to functional diagrams to restore


connections.

Tracks interruptions on boards Restore connections or replace board.

Rosin joints on connectors Restore joints or replace boards.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cables.

1.47 Alarm 122


Code 122 refers to the transmission of the longitudinal drawer and in particular to activation
24S6.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Activation not powered or powered by an out Check tracks on board 24S9, the operation of
of range voltage value power supply board 24S5, fuses on board
LED HV: OFF 24S5, the power supplies from the power
LED FAU: ON transformer, connections to transformer, fuses
on transformer, the power supplies of the
transformer and line voltage.
Replace board 24S9, 24S6, fuses or board
24S5, restore connections, replace fuses or
power transformer 22TR1.

55
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Activation powered by an out of range Check line voltage, the operation of power
voltage value supply board 24S5, the power supplies from
LED HV: OFF the power transformer, the power supplies of
LED FAU: ON the transformer. Replace board 24S5 and
power transformer 22TR1.

Activation blocked by thermal protection Ventilators off or not functional, use of


LED TER: ON continuous transmission function.
LED FAU: ON To restore operation switch activation off, let
it cool down and switch the equipment back
on.

Motor short-circuit Check tracks on board 24S9, the


LED HV: ON activation/motor tie cable and motor 3MT11.
LED FAU: ON Replace cable and motor.

Error in motor connection Refer to functional diagrams to restore


LED HV: ON connections.
LED FAU: ON

Tracks interruptions on board 24S9 Restore connections or replace board.


Input 25S2-IN3 off

Interruption in flat-cable 24S9CFC2- Replace flat-cable.


25S2CN2
Input 25S2-IN3 off

Rosin joints on the connectors of board 24S9 Restore joints or replace boards.
and 25S2
Input 25S2-IN3 off

56
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Input 25S2-IN3 not functional Replace axes board 25S2.

Power supply failure +12Vcc for input/output Check connections, power supplies on boards
board 25S2 24S9 and 24S5, power supplies on power
supply board 24S5, the power supplies from
the service transformer, fuses on transformer
and power supplies.
Replace boards 25S2, 24S9 and 24S5, restore
connections, replace fuses or auxiliaries
transformer.

1.48 Alarm 131


Code 131 refers to the transmission of the transverse drawer and in particular to the position
transducer (reference photocell).
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Photocell 3FC15 not functional Replace photocell.

Power amplification board 3S3 not functional Replace power amplification board.

Tie cable disconnected between photocell Reconnect cable.


3FC15 and board 3S3

Interruption in tie cable between photocell Replace cable.


3FC15 and board 3S3

Tie cable disconnected between board 3S3 Reconnect cable.


and 24S9 CAUTION must be exercised with the screen
earth connection.

57
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Interruption in tie cable between board 3S3 Replace cable.


and 24S9

Incorrect connections in cables Refer to functional diagrams to restore


connections.

Tracks interruptions on boards Restore connections or replace boards.

Rosin joints on connectors Restore joints or replace boards.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

1.49 Alarm 132


Code 132 refers to the transmission of the transverse drawer and in particular to activation
24S8.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Activation not powered or powered by an out Check tracks on board 24S9, the operation of
of range voltage value power supply board 24S5, fuses on board
LED HV: OFF 24S5, the power supplies from the power
LED FAU: ON transformer, connections to transformer, fuses
on transformer, the power supplies of the
transformer and line voltage.
Replace board 24S9, 24S8, fuses or board
24S5, restore connections, replace fuses or
power transformer 22TR1.

58
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Activation powered by an out of range Check line voltage, the operation of power
voltage value supply board 24S5, the power supplies from
LED HV: OFF the power transformer, the power supplies of
LED FAU: ON the transformer. Replace board 24S5 and
power transformer 22TR1.

Activation blocked by thermal protection Ventilators off or not functional, use of


LED TER: ON continuous transmission function.
LED FAU: ON To restore operation switch activation off, let
it cool down and switch the equipment back
on.

Motor short-circuit Check tracks of board 24S9, the


LED HV: ON activation/motor tie cable and motor 3MT12.
LED FAU: ON Replace cable and motor.

Error in motor connection Refer to functional diagrams to restore


LED HV: ON connections.
LED FAU: ON

Tracks interruptions on board 24S9 Restore connections or replace board.


Input 25S2-IN5 off

Interruption in flat-cable 24S9CFC2- Replace flat-cable.


25S2CN2
Input 25S2-IN5 off

Rosin joints on the connectors of board 24S9 Restore joints or replace boards.
and 25S2
Input 25S2-IN5 off

Input 25S2-IN5 not functional Replace axes board 25S2.

59
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Power supply failure +12Vcc for input/output Check connections, power supplies on boards
board 25S2 24S9, 24S5, fuses on power supply board
24S5, the power supplies from the service
transformer, fuses on transformer and power
supplies.
Replace boards 25S2, 24S9 and 24S5, restore
connections, replace fuses or auxiliaries
transformer.

1.50 Alarm 133


Code 131 refers to the transmission of the transverse drawer and in particular to the
microswitch of the drawer centre.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Microswitch 3FC21 not functional Replace microswitch.

Power amplification board 3S3 not functional Replace power amplification board.

Tie cable disconnected between photocell Reconnect cable.


3FC21 and board 3S3

Interruption in tie cable between photocell Replace cable.


3FC21 and board 3S3

Tie cable disconnected between board 3S3 Reconnect cable.


and 24S9 CAUTION must be exercised with the screen
earth connection.

Interruption in tie cable between board 3S3 Replace cable.


and 24S9

60
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Incorrect connections in cables Refer to functional diagrams to restore


connections.

Tracks interruptions on boards Restore connections or replace boards.

Rosin joints on connectors Restore joints or replace boards.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

1.51 Alarm 141


Code 141 refers to the transmission of the IB and in particular to the position transducer
(reference photocell).
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Microswitch 3FC19 not functional Replace microswitch.

Power amplification board 3S3 not functional Replace power amplification board.

Tie cable disconnected between photocell Reconnect cable.


3FC19 and board 3S3

Interruption in tie cable between photocell Replace cable.


3FC19 and board 3S3

Tie cable disconnected between board 3S3 Reconnect cable.


and 24S9 CAUTION must be exercised with the screen
earth connection.

Interruption in tie cable between board 3S3 Replace cable.


and 24S9

61
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Incorrect connections in cables Refer to functional diagrams to restore


connections.

Tracks interruptions on boards Restore connections or replace boards.

Rosin joints on connectors Restore joints or replace boards.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

1.52 Alarm 142


Code 142 refers to the transmission of the IB and in particular to activation 24S7.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Activation not powered or powered by an out Check tracks on board 24S9, the operation of
of range voltage value power supply board 24S5, fuses on board
LED HV: OFF 24S5, the power supplies from the power
LED FAU: ON transformer, connections to transformer, fuses
on transformer, the power supplies of the
transformer and line voltage.
Replace board 24S9, 24S7, fuses or board
24S5, restore connections, replace fuses or
power transformer 22TR1.

Activation powered by an out of range Check line voltage, the operation of power
voltage value supply board 24S5, the power supplies from
LED HV: OFF the power transformer, the power supplies of
LED FAU: ON the transformer. Replace board 24S5 and
power transformer 22TR1.

62
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Activation blocked by thermal protection Ventilators off or not functional, use of


LED TER: ON continuous transmission function.
LED FAU: ON To restore operation switch activation off, let
it cool down and switch the equipment back
on.

Motor short-circuit Check tracks on board 24S9, the


LED HV: ON activation/motor tie cable and motor 3MT16.
LED FAU: ON Replace cable and motor.

Error in motor connection Refer to functional diagrams to restore


LED HV: ON connections.
LED FAU: ON

Tracks interruptions on board 24S9 Restore connections or replace board.


Input 25S2-IN4 off

Interruption in flat-cable 24S9CFC2- Replace flat-cable.


25S2CN2
Input 25S2-IN4 off

Rosin joints on the connectors of board 24S9 Restore joints or replace boards.
and 25S2
Input 25S2-IN4 off

Input 25S2-IN4 off Replace axes board 25S2.

Power supply failure +12Vcc for input/output Check connections, power supplies on boards
board 25S2 24S9 and 24S5, fuses on power supply board
24S5, the power supplies from the service
transformer, fuses on transformer and power
supplies.
Replace boards 25S2, 24S9 and 24S5, restore
connections, replace fuses or auxiliaries
transformer.

63
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.53 Alarm 143


Code 143 refers to the transmission of the IB of the low IB microswitch.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Microswitch 3FC20 not functional Replace microswitch.

Power amplification board 3S3 not functional Replace power amplification board.

Tie cable disconnected between photocell Reconnect cable.


3FC15 and board 3S3

Interruption in tie cable between photocell Replace cable.


3FC20 and board 3S3

Tie cable disconnected between board 3S3 Reconnect cable.


and 24S9 CAUTION must be exercised with the screen
earth connection.

Interruption in tie cable between board 3S3 Replace cable.


and 24S9

Incorrect connections in cables Refer to functional diagrams to restore


connections.

Tracks interruptions on boards Restore connections or replace boards.

Rosin joints on connectors Restore joints or replace boards.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

64
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.54 Alarm 151


Code 151 refers to the transmission of the grid and in particular to the position transducer
(reference photocell).
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Photocell 3FC18 not functional Replace photocell.

Power amplification board 3S3 not functional Replace power amplification board.

Tie cable disconnected between photocell Reconnect cable.


3FC18 and board 3S3

Interruption in tie cable between photocell Replace cable.


3FC18 and board 3S3

Tie cable disconnected between board 3S3 Reconnect cable.


and 24S9 CAUTION must be exercised with the screen
earth connection.

Interruption in tie cable between board 3S3 Replace cable.


and 24S9

Incorrect connections in cables Refer to functional diagrams to restore


connections.

Tracks interruptions on boards Restore connections or replace boards.

Rosin joints on connectors Restore joints or replace boards.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

65
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.55 Alarm 152


Code 152 refers to the transmission of the grid and in particular to activation 24S4.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the angle of tilt display flashes and shows the
alarm code while the remaining displays switch off.

Events that may cause the error Problem solution

Activation not powered or powered by an out Check tracks on board 24S9, the operation of
of range voltage value power supply board 24S1, fuses on board
LED HV: OFF 24S1, the power supplies from the power
LED FAU: ON transformer, connections to transformer, fuses
on transformer, the power supplies of the
transformer and line voltage.
Replace boards 24S9, 24S4, fuses or board
24S1, restore connections, replace fuses or
power transformer 22TR1.

Activation powered by an out of range Check line voltage, the operation of power
voltage value supply board 24S1, the power supplies from
LED HV: OFF the power transformer, the power supplies of
LED FAU: ON the transformer. Replace board 24S1 and
power transformer 22TR1.

Activation blocked by thermal protection Ventilators off or not functional, use of


LED TER: ON continuous transmission function.
LED FAU: ON To restore operation switch activation off, let
it cool down and switch the equipment back
on.

Motor short-circuit Check tracks on board 24S9, the


LED HV: ON activation/motor tie cable and motor 3MT15.
LED FAU: ON Replace cable and motor.

66
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Error in motor connection Refer to functional diagrams to restore


LED HV: ON connections.
LED FAU: ON

Tracks interruptions on board 24S9 Restore connections or replace board.


Input 25S2-IN6 off

Interruption in flat-cable 24S9CFC2- Replace flat-cable.


25S2CN2
Input 25S2-IN6 off

Rosin joints on the connectors of board 24S9 Restore joints or replace boards.
and 25S2
Input 25S2-IN6 off

Input 25S2-IN6 not functional Replace axes board 25S2.

Power supply failure +12Vcc for input/output Check connections, power supplies on boards
board 25S2 24S9 and 24S5, fuses on power supply board
24S5, the power supplies from the service
transformer, fuses on transformer and power
supplies.
Replace boards 25S2, 24S9 and 24S5, restore
connections, replace fuses or auxiliaries
transformer.

67
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.56 Alarm 161


Code161 refers to the transmission of the longitudinal plan and in particular to the position
transducer (potentiometer and related circuits).
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the layer display flashes and shows the alarm code while the remaining displays
switch off.

Possible alarm causes Problem solution

Potentiometer 3PT17 not functional Replace potentiometer. Reconnect, reacquire


and check control stops following setup
procedure.

Potentiometer 3PT17 exceeds acquisition Bring tilt within defined limits, following
limits setup procedure or manually. Recheck control
stops.

Tie cable disconnected between board 25S3 Reconnect cable.


and 3PT17 CAUTION must be exercised with the screen
earth connection.

Interruption in tie cable between board 25S3 Replace cable.


and 3PT17

Incorrect connections in tie cable between Refer to functional diagrams to restore


board 25S3 and 3PT17 connections.

Tracks interruptions on board 25S3 Restore connections or replace board.

Rosin joints on the connectors of board 25S3 Restore joints or replace board.

Interruption in flat-cable 25S3CN2-25S1CN2 Replace flat-cable.

Fault on reading circuit ADC6 of board 25S1 Replace board.


CPU

68
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

Events that may cause the error Problem solution

Power supply failure +/-15V on the power Check fuses on board 25S1, the power
supplies of reading circuit ADC6 in board supplies and connections from the service
25S1 transformer, fuses and power supplies on
transformer.
Replace fuses or board 25S1, restore
connections, replace fuses or auxiliaries
transformer 22TR2.

Sporadic errors Error caused by external interferences.


To restore activation switch the equipment off
and on.

1.57 Alarm 163


Code 163 refers to the transmission of the longitudinal plan during movement. Through the
position transducer (potentiometer and related circuits) the software determines the incorrect
direction of movement.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the layer display flashes and shows the alarm
code while the remaining displays switch off.

Events that may cause the error Problem solution

Inverted motor and generator Refer to functional diagrams to restore


connections.

Inverted dac connections Refer to functional diagrams to restore


connections.

All events that may cause error 161 See error 161.
(problems with potentiometer and related
circuits)

69
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.58 Alarm 164


Code 164 refers to the transmission of the longitudinal plan and in particular to the motor
reducer.
Through the position transducer (potentiometer and related circuits) the software determines
the movement without command of the transmission.
The activation of this alarm stops the equipment, it disables the power transformer
connection relay. All movements are disabled, the layer display flashes and shows the alarm
code while the remaining displays switch off.

Events that may cause the error Problem solution

Motor reducer reversibility Replace motor reducer.

All events that may cause error 161 See error 161.
(problems with potentiometer and related
circuits)

1.59 Alarm 189÷196


Codes 189÷196 refer to board CPU 25S1.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Board CPU 25S1 not functional Replace board CPU.

1.60 Alarm 197


Code 197 refers to the axes board for stepper motors 25S2.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Axes board 25S2 not functional Replace axes board.

70
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in thePRECISION
box then click
RXI SYSTEM onANDGO
TASKS PROCEDURES
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.61 Alarm 198


Code 198 refers to the transmission of data between board CPU 25S1 and PC in setup mode
in <Telediagnosis>. The activation of this alarm disables the power transformer connection
relay. All movements are disabled, the layer display flashes and shows the alarm code while
the remaining displays switch off.

Events that may cause the error Problem solution

Serial cable or connection by modem Recheck cable. To restore operation switch


interrupted the equipment off and on.

1.62 Alarm 199


Code 199 refers to the transmission of data between board CPU 25S1 and PC in telecontrol
mode in <Telediagnosis>. The activation of this alarm disables the power transformer
connection relay. All movements are disabled, the layer display flashes and shows the alarm
code while the remaining displays switch off.

Events that may cause the error Problem solution

Serial cable or connection by modem Recheck cable. To restore operation switch


interrupted the equipment off and on.

1.63 Alarm 200


Code 200 refers to the fault of Eeprom mounted on board 25S1.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Eeprom not functional Replace Eeprom. Reinsert default data on


Eeprom in setup mode. Acquire configuration
data, control stops and calibration following
the service manual.

Eeprom absent Insert Eeprom.

71
Return to RXi Support Enter the Error or Alarm Code 133 GO
GE MEDICAL SYSTEMS in Pthe box
RECISION RXIthen
SYSTEM click onPROCEDURES
TASKS AND GO
DIRECTION 5121726-100, REVISION 1 BOOK 1 – TABLE TROUBLESHOOTING

1.64 Alarm 201


Code 201 refers to the content of Eeprom mounted on board 25S1.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

Events that may cause the error Problem solution

Eeprom new (during testing) Reinsert default data on Eeprom in setup


mode. Acquire configuration data, control
stops and calibration following the service
manual.

Replace board CPU 25S1 Remove Eeprom from the replaced board.

Eeprom content modified due to change in Follow instructions enclosed with software
software version version.

Eeprom dirty Reinsert default data on Eeprom in setup


mode. Acquire configuration data, control
stops and calibration following the service
manual.

1.65 Alarm 202


Code 202 identifies the activation of a hypothetical alarm that has been generated but not
dealt with by the application software. There are no plausible events that may activate this
alarm.
The activation of this alarm disables the power transformer connection relay. All movements
are disabled, the angle of tilt display flashes and shows the alarm code while the remaining
displays switch off.

72