Retrofitting STP at Robinsons Valencia

This document is a table of contents for an as-built plan of a sewage treatment plant retrofitting project. The table of contents lists 7 sections covering sanitary works, electrical works, and mechanical works. Section S covers vicinity maps, process diagrams, and layouts of the sewage treatment plant. Sections E and M cover electrical and equipment layouts and diagrams.

Uploaded by

Jysar Reubal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
321 views5 pages

Retrofitting STP at Robinsons Valencia

This document is a table of contents for an as-built plan of a sewage treatment plant retrofitting project. The table of contents lists 7 sections covering sanitary works, electrical works, and mechanical works. Section S covers vicinity maps, process diagrams, and layouts of the sewage treatment plant. Sections E and M cover electrical and equipment layouts and diagrams.

Uploaded by

Jysar Reubal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

TABLE OF CONTENTS

ROBINSONS PLACE 4 5
SANITARY

VALENCIA S-1 VICINITY MAP, STP PROCESS FLOW


DIAGRAM, STP TOP LAYOUT, & LEGENDS

VALENCIA, BUKIDNON S-2 STP ACCESS ROOM, STP BOTTOM LAYOUT,


2"ø SS PIPES STP SECTION THRU A, & STP SECTION THRU B
3"ø SS PIPES
4"ø SS PIPES

AS BUILT PLAN 6"ø SS PIPES


5"ø GI PIPES
S-3 STP SECTION THRU C, STP SECTION THRU D,
STP SECTION THRU E, STP SECTION THRU F,
STP SECTION THRU G, & BARSCREEN DETAILS

RETROFITTING OF SEWAGE OPEN ELECTRICAL


TREATMENT PLANT - 421CMD A
MH

E-1 STP TOP ELECTRICAL LAYOUT, STP BOTTOM


OPEN ELECTRICAL LAYOUT, STP LOAD SCHEDULE
& STP SINGLE LINE DIAGRAM

6"Ø PVC AIR MH


N BREATHER

MECHANICAL
MH
M-1 STP TOP EQUIPMENT LAYOUT, STP BOTTOM
EQUIPMENT LAYOUT, STP EQUIPMENT
EQUIPMENT
B SCHEDULE, & STP TERTIARY LAYOUT

MCC2
MHROOM
MH

OPEN
MH

ACF ACF

C
VICINITY MAP
STP TOP LAYOUT
BLOWER 2

CHLORINATOR

SAMPLING
BLOWER 1 PORT FLOWMETER
LEGEND: INFLUENT
SEWER LINE
MULTI- ACTIVATED LEGENDS
SLUDGE LINE MEDIA CARBON STP SEWAGE TREATMENT PLANT MCC MOTOR CONTROL CENTER
AIRL LINE SLUDGE FILTER FILTER SAMPLING PORT/
ANOXIC MIXING BACK BACK TO DRAINANGE
SBR SEQUENTIAL BATCH REACTOR CHL CHLORINATOR
CHLORINE LINE DIGESTER FINAL FINAL
SBR-1 SBR-2 WASH WASH CBD COARSE BUBBLE DIFFUSER FBD FINE BUBBLE DIFFUSER
FLOWMETER DECANTER DECANTER TANK TANK1 TANK2 FT1 FINAL TANK 1 TWL TOP WATER LEVEL
BUTTERFLY VAVLE AGITATOR ANOXIC AIR TRANSFER RETURN PUMP RETURN PUMP TERTIARY EFFLUENT
AIR AIR AIR FT2 FINAL TANK 2 MH MANHOLE
MIXER PUMP PUMP PUMP PUMP
CHECK VALVE
BALL VALVE
AIRLIFT ACF ACTIVATED CARBON FILTER MMF MULTI-MEDIA FILTER

STP PROCESS FLOW DIAGRAM

MILESTONE ENVIRONMENT RETROFITTING OF STP AT ROBINSONS VICINITY MAP


MNCP JUNE / 2022 S-1
STP PROCESS FLOW DIAGRAM
& INDUSTRIAL MANAGEMENT PLACE VALENCIA (421CMD) IN ROBINSONS LAND CORPORATION STP TOP LAYOUT
C O R P O R A T I O N COMPLIANCE TO DAO2016-08 RPM JUNE / 2022
Block 1 Lot 35&36 Grand Riverstone Village, National Highway, Dita, Sta Rosa City, Laguna 4026,
P h i l i p p i n e s T e l . N o . : ( 0 2 ) 8 2 4 5 - 8 2 6 8 / ( 0 2 ) 8 2 4 5 6 2 7 3 ALFREDO M. SANTOS VALENCIA, BUKIDNON 11th FLR CYBERSCAPE ALPHA, GARNETT AND SAPPHIRE ROADS,
Email ad: ams@[Link] Website: [Link] ORTIGAS CENTER, PASIG CITY
SANITARY ENGINEER
4 5 4 5

2"ø SS PIPES 2"ø SS PIPES


3"ø SS PIPES 3"ø SS PIPES
4"ø SS PIPES 4"ø SS PIPES
6"ø SS PIPES 6"ø SS PIPES
5"ø GI PIPES 5"ø GI PIPES

A A ANOXIC SBR1
RETURN
PUMP
AGITATOR
MIXER

MIXING
BOREHOLE
PUMPS
B B RETURN
PUMP

FT1 SBR2
FT2
SDT

C C

STP ACCESS ROOM STP BOTTOM LAYOUT

4 5 4 5

2"ø SS PIPES
3"ø SS PIPES 2"ø SS PIPES
4"ø SS PIPES 3"ø SS PIPES
6"ø SS PIPES 4"ø SS PIPES
6"ø SS PIPES
5"ø GI PIPES
5"ø GI PIPES

STP AREA STP AREA

ACF ACF
MCC2

TWL TWL

TO DRAINAGE TO TERTIARY TO ANOXIC


TWL TWL TWL TWL

FINAL FINAL FINAL


SDT SBR2 SBR2
TANK2 TANK 2 TANK 1 RETURN
PUMP

BOREHOLE
PUMPS

STP SECTION THRU A STP SECTION THRU B

MILESTONE ENVIRONMENT RETROFITTING OF STP AT ROBINSONS STP ACCESS ROOM


MNCP JUNE / 2022 S-2
STP BOTTOM LAYOUT
& INDUSTRIAL MANAGEMENT PLACE VALENCIA (421CMD) IN ROBINSONS LAND CORPORATION STP SECTION THRU A
STP SECTION THRU B
C O R P O R A T I O N COMPLIANCE TO DAO2016-08 RPM JUNE / 2022
Block 1 Lot 35&36 Grand Riverstone Village, National Highway, Dita, Sta Rosa City, Laguna 4026,
P h i l i p p i n e s T e l . N o . : ( 0 2 ) 8 2 4 5 - 8 2 6 8 / ( 0 2 ) 8 2 4 5 6 2 7 3 ALFREDO M. SANTOS VALENCIA, BUKIDNON 11th FLR CYBERSCAPE ALPHA, GARNETT AND SAPPHIRE ROADS,
Email ad: ams@[Link] Website: [Link] ORTIGAS CENTER, PASIG CITY
SANITARY ENGINEER
4 5 C B A C B A

ACCESS 2"ø SS PIPES


ROOM 3"ø SS PIPES
4"ø SS PIPES 2"ø SS PIPES ACCESS 2"ø SS PIPES ACCESS
6"ø SS PIPES 3"ø SS PIPES 3"ø SS PIPES
ROOM ROOM
4"ø SS PIPES 4"ø SS PIPES
5"ø GI PIPES
6"ø SS PIPES 6"ø SS PIPES
5"ø GI PIPES 5"ø GI PIPES

STP AREA MCC2

ACF

BSC

TWL

TO SBR TANKS TO ANOXIC TWL TWL TWL TWL TWL TWL TWL
TWL
FINAL MIXING ANOXIC ANOXIC
MIXING SDT FINAL MIXING
TANK2 TANK TANK TANK
TANK SBR1 TANK1 TANK
RETURN
TO DRAINAGE TO TERTIARY TO SBR TANKS TO MIXING
PUMP

AGITATOR
BOREHOLE MIXER
PUMP

STP SECTION THRU C STP SECTION THRU E STP SECTION THRU G

5 4 A B C

ACCESS
2"ø SS PIPES
3"ø SS PIPES
ROOM
4"ø SS PIPES 2"ø SS PIPES
6"ø SS PIPES 3"ø SS PIPES
4"ø SS PIPES
BS3 BS2
5"ø GI PIPES 6"ø SS PIPES
5"ø GI PIPES

STP AREA STP AREA


BS1

BSC
BSC

TWL TWL TWL


TO ANOXIC TO MIXING TO ANOXIC

TWL

ANOXIC
SBR1 RETURN RETURN
RETURN TANK PUMP PUMP
PUMP SBR2 SBR1

AGITATOR
MIXER

STP SECTION THRU D STP SECTION THRU F BARSCREEN DETAILS

MILESTONE ENVIRONMENT RETROFITTING OF STP AT ROBINSONS STP SECTION THRU C


MNCP JUNE / 2022 S-3
STP SECTION THRU D
& INDUSTRIAL MANAGEMENT PLACE VALENCIA (421CMD) IN ROBINSONS LAND CORPORATION STP SECTION THRU E
STP SECTION THRU F
C O R P O R A T I O N COMPLIANCE TO DAO2016-08 STP SECTION THRU G RPM JUNE / 2022
Block 1 Lot 35&36 Grand Riverstone Village, National Highway, Dita, Sta Rosa City, Laguna 4026, BARSCREEN DETAILS
P h i l i p p i n e s T e l . N o . : ( 0 2 ) 8 2 4 5 - 8 2 6 8 / ( 0 2 ) 8 2 4 5 6 2 7 3 ALFREDO M. SANTOS VALENCIA, BUKIDNON 11th FLR CYBERSCAPE ALPHA, GARNETT AND SAPPHIRE ROADS,
Email ad: ams@[Link] Website: [Link] ORTIGAS CENTER, PASIG CITY
SANITARY ENGINEER
4 5

2"ø SS PIPES
3"ø SS PIPES
4"ø SS PIPES
6"ø SS PIPES
TO MCC 5"ø GI PIPES
6

OPEN TO MCC
1 2 MH
A TO MCC
5
OPEN

PVC AIR MH
BREATHER

MH

TO MCC 13
B
MCC2

14 MH
MH

OPEN
MH
TO MCC 3 15
ACF ACF
4 TO MCC

STP TOP ELECTRICAL PLAN STP LOAD SCHEDULE

4 5
3 - 60 mm² THHN LINE
1 - 14 mm² THHN GND
1 - 60 mm² THHN NEUT
IN 2 1/2"Ø PVC CONDUIT

FUJI MCCB 3P
380/400V
175AT, 225AF
2"ø SS PIPES
3"ø SS PIPES N
4"ø SS PIPES L3
6"ø SS PIPES L2
L1
5"ø GI PIPES

FUJI MCCB 3P FUJI MCCB 3P FUJI ITCB 3P FUJI ITCB 3P FUJI ITCB 3P FUJI ITCB 3P FUJI ITCB 3P FUJI ITCB 3P FUJI ITCB 3P FUJI ITCB 3P FUJI MCB 1P FUJI MCB 1P FUJI MCB 1P
380/400V 380/400V 380/400V 380/400V 380/400V 380/400V 380/400V 380/400V 380/400V 380/400V 220/240V 220/240V 220/240V
50AT, 50AF 50AT, 50AF 30AT, 50AF 30AT, 50AF 30AT, 50AF 30AT, 50AF 30AT, 50AF 30AT, 50AF 20AT, 50AF 20AT, 50AF 10AT, 16AF 10AT, 16AF 10AT, 16AF

TO MCC 11 FUJI SC-N1


32A MAIN
FUJI SC-N1
32A MAIN
FUJI SC-0
13A MAIN
FUJI SC-0
13A MAIN
FUJI SC-0
13A MAIN
FUJI SC-0
13A MAIN
FUJI SC-0
13A MAIN
FUJI SC-0
13A MAIN
FUJI SC-0
13A MAIN
FUJI SC-0
13A MAIN
FUJI SC-0
13A MAIN
FUJI SC-0
13A MAIN
FUJI SC-0
13A MAIN

12 CONTACTOR CONTACTOR CONTACTOR CONTACTOR CONTACTOR CONTACTOR CONTACTOR CONTACTOR CONTACTOR CONTACTOR CONTACTOR CONTACTOR CONTACTOR

A
FUJI TR-N2/3 FUJI TR-N2/3 FUJI TR-0N/3 FUJI TR-0N/3 FUJI TR-0N/3 FUJI TR-0N/3 FUJI TR-0N/3 FUJI TR-0N/3 FUJI TR-0N/3 FUJI TR-0N/3 FUJI TR-0N/3 FUJI TR-0N/3 FUJI TR-0N/3
18-26A 18-26A 9-13A 9-13A 9-13A 9-13A 9-13A 9-13A 6-9A 6-9A 0.8-1.2A 0.8-1.2A 0.8-1.2A

ANOXIC 3' TO MCC SBR1 U V W


OVERLOAD
RELAY

MOTOR
U V W
OVERLOAD
RELAY

MOTOR
U V W
OVERLOAD
RELAY

MOTOR
U V W
OVERLOAD
RELAY

MOTOR
U V W
OVERLOAD
RELAY

MOTOR
U V W
OVERLOAD
RELAY

MOTOR
U V W
OVERLOAD
RELAY

MOTOR
U V W
OVERLOAD
RELAY

MOTOR
U V W
OVERLOAD
RELAY

MOTOR
U V W
OVERLOAD
RELAY

MOTOR
U1 U2
OVERLOAD
RELAY

MOTOR
U1 U2
OVERLOAD
RELAY

MOTOR
U1 U2
OVERLOAD
RELAY

MOTOR
TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL

TO MCC 5' RETURN 3PHASE


60HZ
10HP
BOOSTER
PUMP 1
3PHASE
60HZ
10HP
BOOSTER
PUMP 2
3PHASE
60HZ
5HP
EXHAUST
AIR BLOWER
3PHASE
60HZ
5HP
FRESH
AIR BLOWER
3PHASE
60HZ
5HP
EFFLUENT
PUMP 1
3PHASE
60HZ
5HP
EFFLUENT
PUMP 2
3PHASE
60HZ
5HP
TRANSFER
PUMP 1
3PHASE
60HZ
5HP
TRANSFER
PUMP 2
3PHASE
60HZ
3HP
ANOXIC
PUMP 1
3PHASE
60HZ
3HP
ANOXIC
PUMP 2
1PHASE
60HZ
180W
DECANTER 1
1PHASE
60HZ
180W
DECANTER 2
1PHASE
60HZ
20W
CHLORINATOR

PUMP
AGITATOR
MIXER
TO MCC 3 - 8.0 mm² THHN LINE
1 - 5.5 mm² THHN GND
1 - 8.0 mm² THHN NEUT
FUJI MCCB 3P FUJI MCCB 3P

9 10 380/400V
100AT, 100AF
380/400V
100AT, 100AF
IN 1"Ø PVC CONDUIT

ABB MCCB 3P
380/400V
50AT, 50AF

TO MCC MIXING N

BOREHOLE L3

7 8 PUMPS
FUJI SC-N1
32A MAIN
FUJI SC-N1
32A DELTA
FUJI SC-5-1
22A STAR
FUJI SC-N1
32A MAIN
FUJI SC-N1
32A DELTA
FUJI SC-5-1
22A STAR L2

B
CONTACTOR CONTACTOR CONTACTOR CONTACTOR CONTACTOR CONTACTOR L1
RETURN
PUMP FUJI TR-N2/3 FUJI TR-N2/3
24-36A 24-36A
ABB MCCB 3P ABB MCCB 3P ABB MCCB 3P ABB MCCB 3P ABB MCCB 3P
OVERLOAD OVERLOAD

1' FT1
380/400V, 380/400V, 380/400V, 380/400V, 380/400V,

4' TO MCC SBR2


RELAY RELAY
40AT, 50AF 40AT, 50AF 20AT, 50AF 20AT, 50AF 20AT, 50AF

TO MCC 2' W1
V1
3PHASE
W2

INDUCTION V2
W1
V1
3PHASE
W2

INDUCTION V2
ABB AX-12
CONTACTOR
ABB AX-12
CONTACTOR
ABB AX-12
CONTACTOR
ABB AX-12
CONTACTOR
ABB AX-12
CONTACTOR

FT2
U1 MOTOR U2 U1 MOTOR U2

25HP AERATION BLOWER 1 25HP AERATION BLOWER 2

SDT
ABB TA25 ABB TA25 ABB TA25 ABB TA25 ABB TA25
16-24A 16-24A 4.5-6.5A 4.5-6.5A 4.5-6.5A
OVERLOAD RELAY OVERLOAD RELAY OVERLOAD RELAY OVERLOAD RELAY OVERLOAD RELAY

U V W MOTOR U V W MOTOR U V W MOTOR U V W MOTOR U V W MOTOR


TERMINAL TERMINAL TERMINAL TERMINAL TERMINAL

7.5HP 7.5HP 2HP 2HP 2HP


3PHASE 3PHASE 3PHASE 3PHASE 3PHASE
60HZ
TERTIARY 60HZ
TERTIARY 60HZ
AGITATOR 60HZ
RETURN 60HZ
RETURN
PUMP 1 PUMP 2 MIXER PUMP 1 PUMP 2

STP BOTTOM ELECTRICAL PLAN STP SINGLE LINE DIAGRAM

MILESTONE ENVIRONMENT RETROFITTING OF STP AT ROBINSONS STP TOP ELECTRICAL PLAN


MNCP JUNE / 2022 E-1
STP BOTTOM ELECTRICAL PLAN
& INDUSTRIAL MANAGEMENT PLACE VALENCIA (421CMD) IN ROBINSONS LAND CORPORATION STP LOAD SCHEDULE
STP SINGLE LINE DIAGRAM
C O R P O R A T I O N COMPLIANCE TO DAO2016-08 RPM JUNE / 2022
Block 1 Lot 35&36 Grand Riverstone Village, National Highway, Dita, Sta Rosa City, Laguna 4026,
P h i l i p p i n e s T e l . N o . : ( 0 2 ) 8 2 4 5 - 8 2 6 8 / ( 0 2 ) 8 2 4 5 6 2 7 3 ALFREDO M. SANTOS VALENCIA, BUKIDNON 11th FLR CYBERSCAPE ALPHA, GARNETT AND SAPPHIRE ROADS,
Email ad: ams@[Link] Website: [Link] ORTIGAS CENTER, PASIG CITY
PROF. ELECTRICAL ENGINEER
4 5
FLOW RATE/ MOTOR SPECIFICATIONS
EQUIPMENT SERVICE
QTY. LOCATION BRAND / ORIGIN MODEL TYPE CAPACITY REMARKS
# NAME POWER SOURCE SPEED
APPROXIMATE OTHERS
KW(HP) PH/V/freq (RPM)
EQUIPMENT ROOM TSURUMI / JAPAN POSITIVE DISPLACEMENT (25) 3/400/60Hz 5000 mmAq
AB1 1 AERATION BLOWER 1 RSR - 125LK 10.83 cum Air/min 1800
ROTARY (3) LOBE
TSURUMI / JAPAN POSITIVE DISPLACEMENT (25) 5000 mmAq
AB2 1 AERATION BLOWER 2 EQUIPMENT ROOM RSR - 125LK 10.83 cum Air/min 3/400/60Hz 1800
ROTARY (3) LOBE
2"ø SS PIPES
VERTICAL IN-LINE
3"ø SS PIPES BP1 1 BOOSTER PUMP 1 EQUIPMENT ROOM EBARA / JAPAN EVMSG10 4N6/3.0 65.00 gpm (10) 3/400/60Hz 3500 30m TDH
4"ø SS PIPES
CENTRIFUGAL PUMP
6"ø SS PIPES VERTICAL IN-LINE
BP2 1 BOOSTER PUMP 1 EQUIPMENT ROOM EBARA / JAPAN EVMSG10 4N6/3.0 65.00 gpm (10) 3/400/60Hz 3500 30m TDH
CENTRIFUGAL PUMP
5"ø GI PIPES
FAB TR1 1 TERTIARY PUMP 1 FINAL TANK1 EBARA / JAPAN B650S-2 BOREHOLE PUMP 264.00 gpm (7.5) 3/400/60Hz 3450 21m TDH

TR2 1 TERTIARY PUMP 2 FINAL TANK1 EBARA / JAPAN B650S-2 BOREHOLE PUMP 264.00 gpm (7.5) 3/400/60Hz 3450 21m TDH
CENTRIFUGAL
EAB 1 EXHAUST AIR BLOWER EQUIPMENT ROOM FILGEN / USA (VERIFY) 4800 cfm (5) 3/400/60Hz 3600 3" S.P.
SNAIL TYPE
OPEN AB1 AB2 FAB 1 FRESH AIR BLOWER EQUIPMENT ROOM FILGEN / USA (VERIFY)
CENTRIFUGAL
SNAIL TYPE
4800 cfm (5) 3/400/60Hz 3600 3" S.P.
MH SUBMERSIBLE
A EP1 1 EFFLUENT PUMP 1 FINAL TANK 2 EBARA / JAPAN 100DML63.7
NON-CLOG
SUBMERSIBLE
1.2 cum/min (5) 3/400/60Hz 1750 6m TDH

EAB EP2 1 EFFLUENT PUMP 2 FINAL TANK 2 EBARA / JAPAN 100DML63.7 1.2 cum/min (5) 3/400/60Hz 1750 6m TDH
OPEN MIXING TANK
NON-CLOG
SUBMERSIBLE
(5)
TP1 1 TRANSFER PUMP 1 EBARA / JAPAN 100DML63.7 1.2 cum/min 3/400/60Hz 1750 6m TDH
NON-CLOG
SUBMERSIBLE
TP2 1 TRANSFER PUMP 2 MIXING TANK EBARA / JAPAN 100DML63.7 1.2 cum/min (5) 3/400/60Hz 1750 6m TDH
NON-CLOG
PVC AIR MH SUBMERSIBLE
AP1 1 ANOXIC PUMP 1 ANOXIC TANK EBARA / JAPAN 80DML62.2 0.9 cum/min (3) 3/400/60Hz 1750 6m TDH
BREATHER NON-CLOG
SUBMERSIBLE
AP2 1 ANOXIC PUMP 2 ANOXIC TANK EBARA / JAPAN 80DML62.2 0.9 cum/min (3) 3/400/60Hz 1750 6m TDH
NON-CLOG
SUBMERSIBLE
RP1 1 RETURN PUMP 1 SBR TANK 1 EBARA / JAPAN 50DVS61.5 0.5 cum/min (2) 3/400/60Hz 3600 8m TDH
NON-CLOG
MH SUBMERSIBLE
RP2 1 RETURN PUMP 2 SBR TANK 2 EBARA / JAPAN 50DVS61.5 0.5 cum/min (2) 3/400/60Hz 3600 8m TDH
NON-CLOG
SUBMERSIBLE
ANOXIC TANK 3600 2.5m/s TDH
DV1 MIX 1 AGITATOR MIXER EVERGUSH / TAIWAN EFM 20-T 270 cum/hr (2) 3/400/60Hz
B MIXER
MCC2

MOTORIZED
MH DV1 1 DECANTER VALVE 1 ABOVE FINAL TANK 1 BELIMO/ SWITZERLAND D6150N / PRCA-S2-T
ACTUATOR VALVE
1.0 cum/min 180W 1/230/60Hz N/A IP67
MH DV2 MOTORIZED
DV2 1 DECANTER VALVE 2 ABOVE FINAL TANK 1 BELIMO/ SWITZERLAND D6150N / PRCA-S2-T 1.0 cum/min 180W 1/230/60Hz N/A IP67
ACTUATOR VALVE
CFP 1 CHEMICAL FEED PUMP ABOVE FINAL TANK 2 SEKO TEKNA EVO/ ITALY AKL603NHH000 DIAPHRAGM PUMP 0-30 gpd 20W 1/230/60Hz N/A 110L PE TANK
OPEN FM 1 FLOMWETER ABOVE FINAL TANK 2 FLOWTECH / TAIWAN KP7100 ELECTROMAGNETIC N/A N/A 1/230/60Hz N/A 4" DIA.
MH PLC 1 PROGRAMMABLE MAIN CONTROL
SIEMENS / GERMANY LOGO 230 RCE
LOGIC MODULE N/A 6W 1/230/60Hz N/A N/A
BP1 LOGIC CIRCUIT CENTER 8 INPUT/ 4 OUTPUT
CHL FBD 118 FINE BUBBLE DIFFUSER SBR TANKS 1&2 AQUAFLEX / TURKEY ADD 230-9 MEMBRANE TYPE 1-8 Ncum/hr N/A N/A N/A 9" DIA.
ACF ACF
BP2 MMF 2 MULTIMEDIA FILTER EQUIPMENT ROOM PENTAIR/ USA 36" x 72"
FIBER REINFORCED N/A N/A N/A N/A N/A
PLASTIC (FRP)
FIBER REINFORCED N/A N/A N/A N/A
ACF 2 ACTIVATED CARBON FILTER EQUIPMENT ROOM PENTAIR/ USA 36" x 72" N/A
PLASTIC (FRP)

STP TOP MECHANICAL PLAN STP EQUIPMENT SCHEDULE

4 5

2"ø SS PIPES
3"ø SS PIPES
4"ø SS PIPES
6"ø SS PIPES
5"ø GI PIPES
MMF ACF ACF MMF

AP1

PVC PIPE 3"

PVC PIPE 3"

PVC PIPE 3"

PVC PIPE 3"


AP2
A ANOXIC RP1 SBR1 BALL VALVE BALL VALVE BALL VALVE BALL VALVE
MIX PRESSURE GAUGE
SAMPLING SAMPLING
PRESSURE GAUGE
RETURN FAUCET FAUCET
PRESSURE GAUGE PRESSURE GAUGE
PUMP FROM FT 1 BALL VALVE
AGITATOR
MIXER
PVC PIPE 3" BALL VALVE PVC PIPE 3" PVC PIPE 3" BALL VALVE PVC PIPE 3"
AP2 AP1

BACK WASH

BACK WASH

BACK WASH

BACK WASH
TO FT 2

BY PASS TO FT 2
MIXING

PVC PIPE 3"

PVC PIPE 3"

PVC PIPE 3"

PVC PIPE 3"

PVC PIPE 3"

PVC PIPE 3"

PVC PIPE 3"

PVC PIPE 3"


EP1
EP2 BOREHOLE
PUMPS
B RETURN
PUMP

FT1 RP2 SBR2


TR1 TR2
FT2 BACKWASH BACKWASH
TO FT 2
SDT BACKWASH TO ANOXIC BACKWASH TO ANOXIC

STP BOTTOM MECHANICAL PLAN STP TERTIARY LAYOUT

MILESTONE ENVIRONMENT RETROFITTING OF STP AT ROBINSONS STP TOP MECHANICAL PLAN


MNCP JUNE / 2022 M-1
STP BOTTOM MECHANICAL PLAN
& INDUSTRIAL MANAGEMENT PLACE VALENCIA (421CMD) IN ROBINSONS LAND CORPORATION STP EQUIPMENT SCHEDULE
STP TERTIARY LAYOUT
C O R P O R A T I O N COMPLIANCE TO DAO2016-08 RPM JUNE / 2022
Block 1 Lot 35&36 Grand Riverstone Village, National Highway, Dita, Sta Rosa City, Laguna 4026,
P h i l i p p i n e s T e l . N o . : ( 0 2 ) 8 2 4 5 - 8 2 6 8 / ( 0 2 ) 8 2 4 5 6 2 7 3 ALFREDO M. SANTOS VALENCIA, BUKIDNON 11th FLR CYBERSCAPE ALPHA, GARNETT AND SAPPHIRE ROADS,
Email ad: ams@[Link] Website: [Link] ORTIGAS CENTER, PASIG CITY
PROF. MECHANICAL ENGINEER