Electrical Design Report
ELECTRICAL DESIGN
REPORT
Project: G+7 MIXED USE BUILDING
Owner:- W/RO WUBIT GOSAYE
July. 2023
1
Electrical Design Report
Content PAGE NO
1. BOARDS 3
2. ILLUMINATION LEVEL 10
3. INTRODUCTION 13
4. Power calculation 14
5. Grounding System 16
6. Telephone system 17
7. BREAKER, CABEL SIZE AND CONDUTE 22
8. LIGHT FITTING AND LAMPS 23
2
Electrical Design Report
Panel Name: CMDB Number of lights/ sockets in the circuit P = Power in KW of units in the circuit
Circuit No Type of fittings power (K.W) Type of sockets and auxiliary Units Power Current (A) Cable Cross
(KW) P=∑,p1xN1( KW) ( Standard) Section (mm2)
1 2 3 Sockets Water Bell Stove [Link] Reserve
heater
p1 P2 P3 P4 P5 P6 P7 P8 P9 P10
1 N1 MDB GF 3.69 10 2 x 2.5
2 N2 MDB BANK A/GF 2.46 10 2 x 2.5
3 N3 MDB BANK B/GF 2.12 10 2 x 2.5
4 N4 MDB 1F 10.69 25 5x6
5 N5 MDB 2F 10.69 25 5x6
6 N6 MDB 3F 8.05 25 5x6
7 N7 MDB 4F 8.05 25 5x6
8 N8 MDB 5F 8.05 25 5x6
9 N9 MDB 6F 8.05 25 5x6
10 N10 MDB 7F 8.05 25 5x6
-11 N11 Reserve
Total Power ( KW) with 10 % spare 101.54
Total Power with diversity factor of 0.9( KW) 88.27 250 3x95/50+1x50
Panel
3 Name: MDB GF Number of lights/ sockets in the circuit P = Power in KW of units in the circuit
Electrical Design Report
Circuit No Type of fittings power (K.W) Type of sockets and auxiliary Units Power Current (A) Cable Cross
(KW) P=∑,p1xN1( KW) ( Standard) Section (mm2)
1 2 3 Sockets Water Bell Stove [Link] Reserve
heater
p1 P2 P3 P4 P5 P6 P7 P8 P9 P10
0.060 0.072 0.036 0.20 1.5 0.05 2.5 3 .080 0.40
1 N1 8 0.58 10 2 x 2.5
2 N2 8 0.54 10 2 x 2.5
3 N3 7 8 0.50 10 2 x 2.5
4 N4 4 0.29 10 2 x 2.5
5 N5 8 0.48 10 2 x 2.5
6 N6 5 0.30 10 2 x 2.5
7 N7 5 1.00 16 2 x 2.5
-10 N8 Reserve
Total Power ( KW) with 10 % spare 4.05
Total Power with diversity factor of 0.9( KW) 3.24 20 3x6
Panel Name: MDB BANK A/GF Number of lights/ sockets in the circuit P = Power in KW of units in the circuit
4
Electrical Design Report
Circuit No Type of fittings power (K.W) Type of sockets and auxiliary Units Power Current (A) Cable Cross
(KW) P=∑,p1xN1( KW) ( Standard) Section (mm2)
1 2 3 Sockets Water Bell Stove [Link] Reserve
heater
p1 P2 P3 P4 P5 P6 P7 P8 P9 P10
0.060 0.072 0.036 0.20 1.5 0.05 2.5 3 .080 0.40
1 N1 6 0.43 10 2 x 2.5
2 N2 4 0.43 10 2 x 2.5
3 N3 6 0.80 16 2 x 2.5
4 N4 6 0.80 16 2 x 2.5
5 N5 Reserve
Total Power ( KW) with 10 % spare 2.71
Total Power with diversity factor of 0.9( KW) 2.16 20 3x6
5
Electrical Design Report
Panel Name: MDB BANK B/GF Number of lights/ sockets in the circuit P = Power in KW of units in the circuit
Circuit No Type of fittings power (K.W) Type of sockets and auxiliary Units Power Current (A) Cable Cross
(KW) P=∑,p1xN1( KW) ( Standard) Section (mm2)
1 2 3 Sockets Water Bell Stove [Link] Reserve
heater
p1 P2 P3 P4 P5 P6 P7 P8 P9 P10
0.060 0.072 0.036 0.20 1.5 0.05 2.5 3 .080 0.40
1 N1 6 3 0.43 10 2 x 2.5
2 N2 4 0.29 10 2 x 2.5
3 N3 6 0.60 16 2 x 2.5
4 N4 6 0.80 16 2 x 2.5
5 N9 Reserve
Total Power ( KW) with 10 % spare 2.33
Total Power with diversity factor of 0.9( KW) 1.86 20 3x6
6
Electrical Design Report
Panel Name: MDB 1F Number of lights/ sockets in the circuit P = Power in KW of units in the circuit
Circuit No Type of fittings power (K.W) Type of sockets and auxiliary Units Power Current (A) Cable Cross
(KW) P=∑,p1xN1( KW) ( Standard) Section (mm2)
1 2 3 Sockets Water Bell Stove [Link] Reserve
heater
p1 P2 P3 P4 P5 P6 P7 P8 P9 P10
0.060 0.072 0.036 0.20 1.5 0.05 2.5 3 .080 0.40
1 N1 6 0.43 10 2 x 2.5
2 N2 4 0.29 10 2 x 2.5
3 N3 4 0.29 10 2 x 2.5
4 N4 6 0.43 10 2 x 2.5
5 N5 6 0.43 10 2 x 2.5
6 N6 4 0.29 10 2 x 2.5
7 N7 4 0.29 10 2 x 2.5
8 N8 7 0.42 10 2 x 2.5
9 N9 8 0.29 10 2 x 2.5
10 N10 9 0.48 10 2 x 2.5
11 N11 6 1.20 16 2 x 2.5
12 N12 6 1.20 16 2 x 2.5
13 N13 6 0.80 16 2 x 2.5
14 N14 4 0.80 16 2 x 2.5
15 N15 4 0.80 16 2 x 2.5
16 N16 4 0.80 16 2 x 2.5
17 N17 4 0.80 16 2 x 2.5
-10 N18 Reserve
Total Power ( KW) with 10 % spare 10.69
Total Power with diversity factor of 0.9( KW) 8.55 25 5x6
Panel
7 Name: MDB 2F Number of lights/ sockets in the circuit P = Power in KW of units in the circuit
Electrical Design Report
Circuit No Type of fittings power (K.W) Type of sockets and auxiliary Units Power Current (A) Cable Cross
(KW) P=∑,p1xN1( KW) ( Standard) Section (mm2)
1 2 3 Sockets Water Bell Stove [Link] Reserve
heater
p1 P2 P3 P4 P5 P6 P7 P8 P9 P10
0.060 0.072 0.036 0.20 1.5 0.05 2.5 3 .080 0.40
1 N1 6 0.43 10 2 x 2.5
2 N2 4 0.29 10 2 x 2.5
3 N3 4 0.29 10 2 x 2.5
4 N4 6 0.43 10 2 x 2.5
5 N5 6 0.43 10 2 x 2.5
6 N6 4 0.29 10 2 x 2.5
7 N7 4 0.29 10 2 x 2.5
8 N8 7 0.42 10 2 x 2.5
9 N9 8 0.29 10 2 x 2.5
10 N10 9 0.48 10 2 x 2.5
11 N11 6 1.20 16 2 x 2.5
12 N12 6 1.20 16 2 x 2.5
13 N13 6 0.80 16 2 x 2.5
14 N14 4 0.80 16 2 x 2.5
15 N15 4 0.80 16 2 x 2.5
16 N16 4 0.80 16 2 x 2.5
17 N17 4 0.80 16 2 x 2.5
-10 N18 Reserve
Total Power ( KW) with 10 % spare 10.69
Total Power with diversity factor of 0.9( KW) 8.55 25 5x6
Panel Name: MDB 3F=MDB 3F=MDB 3F= Number of lights/ sockets in the circuit P = Power in KW of units in the circuit
MDB 6F=MDB 7F
8
Electrical Design Report
Circuit No Type of fittings power (K.W) Type of sockets and auxiliary Units Power Current (A) Cable Cross
(KW) P=∑,p1xN1( KW) ( Standard) Section (mm2)
1 2 3 Sockets Water Bell Stove [Link] Reserve
heater
p1 P2 P3 P4 P5 P6 P7 P8 P9 P10
0.060 0.072 0.036 0.20 1.5 0.05 2.5 3 .080 0.40
1 N1 8 0.58 10 2 x 2.5
2 N1 11 0.66 10 2 x 2.5
3 N1 8 0.48 10 2 x 2.5
4 N1 6 0.43 10 2 x 2.5
5 N1 6 0.43 10 2 x 2.5
6 N1 4 0.29 10 2 x 2.5
7 N1 4 0.29 10 2 x 2.5
8 N1 6 0.36 10 2 x 2.5
9 N5 5 1.00 16 2 x 2.5
10 N5 6 1.20 16 2 x 2.5
11 N6 4 0.80 16 2 x 2.5
12 N6 4 0.80 16 2 x 2.5
-13 N9 Reserve
Total Power ( KW) with 10 % spare 8.05
Total Power with diversity factor of 0.9( KW) 6.44 25 5x6
9
Electrical Design Report
Illumination Level Calculation
lllumination Lamp Type Used Fitting Arangment
Calculated
Room Utilization Utilization Factor level
Maintenance Wattage No of No of
S/N Room Description area M2 Factor (UF) x Maintenance (Lumen) Lumen output Ceiling Wall
Factor (MF) Lamp Type of Lamp lamps per fittings=
(A) (UF) Factor (MF) Standards of Lamp Mounted Mounted
(watt) fitting ExA/Ufx ø
(EBCS-10)(E)
1 Ground Floor
1.1 Super market 42.2 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 8 8 0
1.1 SHOP 10 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
1.1 BANK 95 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 12 12 0
1.1 GRAND LOBBY 117 0.59 0.8 0.59 x 0.8 = 0.47 100 CFL 14 1 790 16 16 0
1.1 Verendah 37 0.55 0.8 0.55 x 0.8 = 0.44 100 CFL 14 1 790 5 5 0
1.1 TOILET 30.5 0.59 0.8 0.59 x 0.8 = 0.47 100 CFL 14 1 790 7 7 0
1.1 JANITOR 5.6 0.59 0.8 0.59 x 0.8 = 0.47 100 CFL 14 1 790 1 1 0
1.1 BANK 81.5 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 10 10 0
2 FIRST Floor
2.2 SHOP 18 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 16.2 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 15 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 10 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 10 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 25 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 20 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 20 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 SHOP 25 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
2.2 TOILET 30.5 0.59 0.8 0.59 x 0.8 = 0.47 100 CFL 14 1 790 7 7 0
2.2 LOBBY 98.7 0.59 0.8 0.59 x 0.8 = 0.47 100 CFL 14 1 790 15 15 0
2.2 JANITOR 5.6 0.59 0.8 0.59 x 0.8 = 0.47 100 CFL 14 1 790 1 1 0
10
Electrical Design Report
Illumination Level Calculation
lllumination Lamp Type Used Fitting Arangment
Calculated
Room Utilization Utilization Factor level
Maintenance Wattage No of No of
S/N Room Description area M2 Factor (UF) x Maintenance (Lumen) Lumen output Ceiling Wall
Factor (MF) Lamp Type of Lamp lamps per fittings=
(A) (UF) Factor (MF) Standards of Lamp Mounted Mounted
(watt) fitting ExA/Ufx ø
(EBCS-10)(E)
3 Second Floor
3.3 SHOP 18 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 16.2 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 15 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 10 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 10 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 11 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 25 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 20 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 20 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 SHOP 25 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 2 2 0
3.3 LOBBY 98.7 0.59 0.8 0.59 x 0.8 = 0.47 100 CFL 14 1 790 15 15 0
3.3 TOILET 30.5 0.59 0.8 0.59 x 0.8 = 0.47 100 CFL 14 1 790 7 7 0
3.3 JANITOR 5.6 0.59 0.8 0.59 x 0.8 = 0.47 100 CFL 14 1 790 1 1 0
4 3rd-7th Floor
4.4 pental house 51 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 8 8 0
4.4 TOILET 30.5 0.59 0.8 0.59 x 0.8 = 0.47 100 CFL 14 1 790 7 7 0
4.4 JANITOR 5.6 0.59 0.8 0.59 x 0.8 = 0.47 100 CFL 14 1 790 1 1 0
4.4 rental office 49 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 6 6 0
4.4 rental office 40 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 6 6 0
4.4 LOBBY 110.5 0.59 0.8 0.59 x 0.8 = 0.47 100 CFL 14 1 790 17 17 0
4.4 rental office 46 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 4 4 0
4.4 rental office 44 0.69 0.8 0.69 x 0.8 = 0.55 100 CFL 14 1 790 4 4 0
11
Electrical Design Report
[Link] Installation
1.1 Introduction
This report elaborates on the envisaged electrical system design for G+7 MIXED USE
BUILDING building proposed to be constructed at SIDAMO HAWASSA. sub city.
Mains electric power will be supplied from the nearest source of the Ethiopian electric Power
Corporation (EEPCO). It is assumed that EEPCO’s Supply shall be realized through over head
distribution transformers capable of delivering estimated peak demand. Electric power within the
premise of the project will be delivered in the form of a three phase 380 volts 50 Hz systems by
means undergroundNYY feeder cable.
1.2 Scope of design work
The electrical design work as shown on the accompanying drawings is worked out according to
appropriate standards and norms like EBCS-10. DIN. VDE and IEE wiring regulation and the
prevailing norms of Ethiopian Electric Power Corporation (EEPCo).
1.3 Lighting system
All lighting system is designed with the use of compact Florescent or energy saving lamps with
illumination level for each room set as per the EbCS-10. The Calculation for the number of light
fixture for each room and the illumination level is accordance with the relevant clause of EBCS-
10. Light fixtures are selected to fit the function.
The following formulas are applied while calculating the number of fixtures for each room.
N= E x A
Uf * Mf * ø
Where:
E= Illumination level required ( lux)
A= Room area ( sq.m)
Ø = Lumen output of lamp ( in lux)
12
Electrical Design Report
1.4 Service power and socket out lets
Each area in each building is provided with appropriate number and reliable power socket outlets
to various appliances that the customer might require, with due attention also given to the power
distribution to sub sections through normal utility power.
1.5 Distribution boards
1.5.1 Sub circuit design
The circuits for lighting and socket out lets are designed in order to accommodate equal
distribution of power to each sub circuit with the lighting load determined as follows.
P=Ni X Wi
Where:N number of lamps in the sub circuit
W the power of each lamp in KW
i Type of fitting in each sub circuit
Similarly the loads for the of each socket sub circuit is determined by
P = NX200 w
Where:N number of socket in the sub circuit
1.5.2. Main Distribution Board (MDB)
The Central main distribution board is located in ground floor which is suitable for riser area
near to the stairs area and shall be flush mounted type made of metal enclosure frames fixed to
the floor comprising all insulated modular units (MCB) and miniature automatic circuit breakers
rating and quantity shown on the relevant drawing. The bus bar system for CMDB is selected
one step higher from the main circuit breakers. And shall be made of copper. The panel shall be
complete with all the necessary gland plates. Cable entries, Fixing brackets and supports suitable
for the cable specified.
The following formula has been used to determine the current ratings of miniature circuit
breakers where S Total KVA and p is total KW.
13
Electrical Design Report
L1-ph=Sx10 3
V
Or
L1-ph = PX103
V*0.8
1.5.3. Sub Distribution Board ( MDB’)
The Sub distribution boards are located within each floor location and in line with the main
distribution boards each panels are assigned to feed lighting and service socket circuits. In
similar manner as MDB the SDBS comprise of miniature circuit breakers. The bus-bars for the
panels have been selected on step higher from the main circuit breaker ratings to carry a current
of 20 to 50 percent of the rated current. The panel shall be complete with all the necessary gland
plates. Cable entries, Fixing brackets and supports suitable for the cable specified an addition of
25% reserve spaces has been left for the future similar formulas’ as per the main board has been
used to determine the ratings of each breakers.
1.6 Power cables
All power distribution system is done with multi-core PVC Sheathed cable of copper conductor
of appropriate size with due consideration to voltage drop and current carrying capacity. Cable
design and current carrying capacity are in accordance with B56004 or VDE 0271. VDE 0298
and the relevant clause of EBCS-10.
Power cables run under ground in PVC [Link] color identification of cable cores shall
comply with the relevant clause of EBCS- 10. Power cables from MDB to SDB’s are provided
with due consideration to amp city and voltage drop.
The following formulae are used for calculating 1-phase and 3- phase current respectively:
Single phase current (I) in amperes for a given apparent power Sin KVA:
14
Electrical Design Report
L1 –ph=Sx103
Vcos
Where: V= phase voltage in volts
Three phase current (I) in amperes for a given apparent Power Sin KVA:
L3-ph =SX103
√3 XV cos
Where : V = Line Voltage in volts
Power cables are Selectedin such a way so as not to exceed a voltage drop of 4%
Voltage drops in percent Vd % for a give power p in KW:
Vd% = Lx1.732x I x0.8 X 100
YXA V
Vd= Lx 1.732 X I X0.8
YxA
Where: L= Wiring distance in m
I=Current in Amp.
A= Cross- Sectional area in mm2
V= line voltage in volts ( 380V)
Y= Conductivity in mm2 /ᾯ x m . Copper = 56
1.7 Grounding system
The main distribution boards shall be grounded with bare copper conductor of appropriate cross-
section and shall be connected to the earthingsystem. Earthing shall be done with properly buried
galvanized steel earth electrode, Coupling and all necessary accessories. All other systems shall
be 5 wires for three phases and 3 wire for single phase.
15
Electrical Design Report
1.8 Telephone system
Each area in building is provided with appropriate number of telephone out lets depending on the
service of the area with main telephone entry located in ground floor with riser junction boxes at
each floor.
1.8.1 TELEPHONE SOCKET: LEGRAND MOSAIC/DÉCOR/SUNO TYPE
ARE
RECOMENDEDE the owner has full right to choose what he/she wants.
RJ-11 telephone outlet CAT-5E
1.8.2 TELEPHONE TERMINAL BOX: TYPEMINIMUM OF TWO
KNOCKOUTS ON LONGER BOX SIDES SIZE 300X200X100MM, MINIMUM
1.9 MAIN ANTENNA TELEVISION OUTLET SYSTEM
1.9.1 SOCKET OUTLET:
LEGRAND MOSAIC/DÉCOR/SUNO TYPE ARE RECOMENDEDE
The owner has full right to chose what he/she wants.
1. TV + FM + SAT SOCKETS
2. TV PASSAGE
3. TV SINGLE WITH MALE
1.9.2 TV TERMINAL BOXES:
PULL THROUGH JUNCTION BOXES
TYPE DECOR
MINIMUM OF TWO KNOCK OUTS ON LONGER BOX SIDES
SIZE: 200X200X100 MM, MINIMUM
16
Electrical Design Report
Appendix
I. Minimum size of copper earth continuity conductors
And copper earthing leads
Largest current
carrying conductor Earth continuity Earthing
(mm)2 conductor (mm)2 Lead (mm)2
2.5 2.5 4
4 4 4
6 6 6
10 10 6
16 16 6
25 16 10
35 16 10
50 25 35
70 35 35
95 50 50
120 70 70
150 70 70
185 95 70
240 120 70
300 150 70
400 185 70
17
Electrical Design Report
[Link] Wire or Cable sizes, Current carrying capacity and
Voltage drops for every 50 mts.
Cross- Enclosed in conduit Enclosed/Clipped direct to surface
section(mm)2 2-Wire 3or4 Wire 2-Wire 3or4 Wire
I I I I
(A) drop(V) (A) drop(V) (A) drop(V) (A) drop(V)
1.5 16 19 13 12.6 19 22.9 17 16.1
2.5 21 15 17 10 25 18.2 22 12.6
4 27 12 23 8.3 35 14.5 29 10.1
6 35 10.5 29 7 42 12.5 37 8.8
10 48 8.6 40 5.7 57 10 51 7.2
16 65 7.3 55 4.8 78 8.7 70 6.1
25 88 6.3 74 4.2 105 7.6 95 5.7
35 110 5.6 93 3.7 132 6.8 119 4.7
50 140 5 119 3.3 168 6 151 4.2
70 175 4.5 149 3 210 5.4 189 3.8
95 210 4 185 2.7 252 4.7 226 3.3
120 250 3.7 212 2.5 300 4.5 270 3.1
150 275 3.3 236 2.2 330 3.9 300 2.8
185 305 2.9 260 2 366 3.5 330 2.5
240 360 2.7 306 1.8 432 3.2 385 2.2
300 415 2.5 352 1.6 497 3 448 2.1
18
Electrical Design Report
[Link] Circuit Breakers (CB)
Single Phase: -6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A.
Three Phase: -10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A,
160A, 320A, 400A, 500A, 630A, 800A, 1000A, 1250A, 1500A, 2000A……..
[Link] Conduit Sizes
- Lighting system……………...……………….16mm²
- Bell system…………………………..……….13mm²
- Tell system…………………………..……….13mm²
- TV system…………………...……..……..….13mm²
- Socket system………………..……………….16mm²
- Electric Mitad……………….….…………….25mm²
- Stove…………..………….…….…………….25mm²
- Water Heater.……………..…….…………….25mm²
- Power Riser………………….………………..32mm²
- EEPCO Feeder………………….…….……….50mm²
19
Electrical Design Report
V. STANDARDS AND REGULATIONS:
(1) IEC STANDARD
(2) PHILIPS ISL ILLUMINATION DESIGN DETAILS
(3) ETHIOPIAN BUILDING DESIGN AUTHORITY, EBCA,
(4) ELECTRICAL HANDBOOK
(5) ETHIOPIAN ELECTRIC POWER CORPORATION: RULES AND
REGULATIONS
20
Electrical Design Report
VI . BREAKER, CABEL SIZE AND CONDUTE
1. 2A/1P 3x2.5
2. 6A /1P 3x2.5
3. 10A/P 3x2.5
4. 16A/P 3x2.5
5. 16A/3P 5x2.5 Ø20mm
6. 20A/1P 3x4 Ø32mm
7. 20A/3P 5x4 ”
8. 25A/1P 3x6 ”
9. 25A/3P 5x6 ”
10. 32A/3P 5x10 Ø50mm
11. 40A/3P 5x10 ”
12. 50A/3P 5x10 ”
13. 63A/3P 5x16 ”
14. 80A/3P 3x25/16+1x16 Ø75mm
15. 100A/3P 3x35/16+1x16 ”
16. 125A/3P 3x35/16+1x16 Ø110mm
17. 160A/3P 3x50/25+1x25 ”
18. 200A/3P 3x70/35+1x35 ”
19. 250A/3P 3x95/50+1x50 ”
20. 320A/3P 3x120/70+1x70 ”
21. 400A/3P 3x150/70+1x70 ”
22. 500A/3P 2(3x120/70+1x70) ”
23. 630A/3P 2(3x150/70+1x70) ”
24. 800A/3P 3(3x150/70+1x70) ”
25. 1000A/3P 4(3x150/70+1x70) ”
26. 1250A/3P 4(3x150/70+1x70) ”
27. 1600A/3P 6(3x 150/70+1X70) ”
21
Electrical Design Report
VII. LIGHT FITTING AND LAMPS
1. MASSIVE 73863/05/01 with 5xE14 40W lamps.
2. MASSIVE 73863/03/01 with 3xE14 40W lamps.
3. MASSIVE 81863/01/01 with E14 40W lamp.
4. RZB 31651.002 with 2xA60 60W lamps.
5. RZB 31650.002 with A60 75W lamp.
6. RZB 10321.002 with A60 60W lamp.
7. RZB 22141.003 with A60 60W lamp.
8. MASSIVE 34021/11/10 with 2xE14 40W lamps.
9. RZB 221010.923 with TC-D 13W lamp.
[Link] Dubrovnik 15031/45/10 with E27 100W lamp.
[Link] TMS 022/136 IC with TL-D 36W/840 lamp.
[Link] TMW 065/136 IC with TL-D 36W/840 lamp.
[Link] 221023.002.1 with A60 75W lamp.
[Link] TCS 198/236 IC M1 with 2xTL-D 36W/840 lamps.
[Link] Dubrovnik 15036/45/10 with E27 60W lamp.
[Link] 211138.002 with A60 60W lamp.
22