(PLUMBING #3)
GENERAL NOTES:
1. ALL PLUMBING WORKS INCLUDED HEREIN SHALL BE EXECUTED ACCORDING TO THE
PROVISIONS OF THE NATIONAL PLUMBING CODE OF THE PHILIPPINES NATIONAL
BUILDING CODE AND THE RULES AND REGULATION OF THE MUNICIPALITY.
2. COORDINATE THE DRAWINGS WITH OTHER RELATED DRAWINGS THE ENGINEER
SHALL BE NOTIFIED IMMEDIATELY OF ANY DISCREPANCY FOUND THEREIN.
3. ALL PIPES SHALL BE INSTALLED AS INDICATED ON PLANS ANY RELOCATION
REQUIRED FOR PROPER EXCAVATION OF OTHER TRADES SHALL BE WITH THE
PRIOR APPROVAL BY ARCHITECT OR ENGINEER.
4. PROPOSED SANITARY UTILITIES SHALL CONFORM TO THE ACTUAL LOCATION
DEPTHS AND INVERT ELEVATION OF ALL EXISTING PIPES AND STRUCTURES AS
VERIFIED BY THE CONSTRUCTOR.
5. ALL SLOPES FOR HORIZONTAL SEWER LINES SHALL MAINTAIN 2% MINIMUM UNLESS
OTHERWISE SPECIFIED.
6. SIZE OF WATER SUPPLY PIPES TO FIXTURES SHALL BE IN ACCORDANCE WITH THE
MANUFACTURES INSTRUCTION.
7. THE CONSTRUCTOR SHALL VERIFY ALL EXISTING UTILITIES AT THE SITE AND
COORDINATE THE WORKS WITH SEWER LINE EFFLUENT DISPOSAL POINT AND WATER
LINE SERVICE CONNECTING POINT.
8. ALL SLOPES ARE IN MILLIMETERS NORMAL INSIDE DIAMETER AND ALL DIMENSIONS
ARE IN METER UNLESS OTHERWISE SPECIFIED.
9. ALL FIXTURES FOR CWL SHALL BE PROVIDED WITH AIR CHAMBER AND MUST BE
INDIVIDUALLY VENTED UNLESS SPECIFIED OTHERWISE.
10. ALL SEWER PIPES EMBEDDED ON GROUND AND BELOW CONCRETE SLAB SHALL
BE PROVIDED WITH SAND BEDDING MATERIAL.
(STRUCTURAL 1)
A. GENERAL NOTES:
1. IN THAT INTERPRETATION OF THESE DRAWINGS INDICATED DIMENSIONS SHALL
GOVERN DISTANCE OR SIZE SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES.
2. IN CASE OF CONFLICT OF DETAILS OR DIMENSIONS BETWEEN THE ARCHITECTURAL
AND ENGINEERING DRAWINGS REFER TO THE ARCHITECT FOR FINAL DECISION
3. IN CASE OF CONFLICTS BETWEEN THESE DRAWINGS AND SPECIFICATIONS, THE
WORKING DRAWING SHALL GOVERN.
4. ALL STRUCTURAL DETAILS UNLESS OTHERWISE SHOWN IN DRAWINGS SHALL FOLLOW
CONSTRUCTION NOTES DETAIL.
5. ALL CONCRETE WORK SHALL BE DONE IN ACCORDANCE WITH THE ACI 318 2001
CODE SO FAR AS THEY DO NOT CONFLICT WITH LOCAL BUILDING CODE REQUIREMENTS.
6. CONTRACTOR SHALL COORDINATE WITH THE ARCHITECT, MECHANICAL,
ELECTRICAL AND STRUCTURAL ENGINEER PLANS AS TO EXACT SIZE AND LOCATION OF
OPENING THRU GRADE ON SLAB, BEAMS AND WALLS.
7. SOIL BEARING CAPACITY ASSUMPTION IS Q: 350Kpa. ANY FINDINGS REGARDING
THE SOIL STATUS ON JOBSITE OR SOIL BORING TEST SHALL REPOST IN WRITING TO THE
ENGINEER FOR RE-DICISION PROCEDURE.
B. CONCRETE:
MINIMUM CONCRETE STRENGTH AT 28 DAYS COMPRESSIVE STRESS SHALL BE AS
FOLLOW:
1. FOOTINGS AND ROOF BEAMS.............................fc= 21.60MPA (3000psi)
2. COLUMN AND BEAMS.........................................fc= 21.60MPA (3000psi)
3. SLAB ON GRADE................................................fc= 21.60MPA (3000psi)
4. OTHERS NOT SPECIFIED....................................fc= 21.60MPA (3000psi)
CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION RE-
HANDLING OR FLOWING PLACING SHALL BE DONE PREFERABLY WITH BUGGIES BUCKETS
OR WHEELBARROWS, NO CHUTES WILL BE ALLOWED EXCEPT TO TRANSFER CONCRETE
FROM HOPPERS TO BUGGIES, WHEELBARROWS AND BUCKETS IN WHICH CASE THEY SHALL
NOT EXCEED SIX (6.00) METERS IN AGGREGATE LENGTH.
NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE SUE OF VIBRATORS
UNLESS AUTHORIZED IN WRITING BY THE DESIGNER AND ONLY FOR UNUSUAL CONDITIONS
WHERE VIBRATION IS EXTREMELY DIFFICULT TO ACCOMPLISH WITHOUT PRELIMINARY TEST
DATA, THE WATER CEMENT RATIO FOR A GIVEN STRENGTH OF CONCRETE SHOULD NOT
EXCEED THE VALUES SHOWN IN THE ACT CODE WHEN STRENGTH IN EXERCISE OF 2110
kg/cm ARE REQUIRED, STRENGTH TEST SHOULD BE MADE.
C. CONCRETE PROTECTION FOR REINFORCING BARS
THE FOLLOWING SHALL BE THE CLEAR COVER CONCRETE PROTECTION.
1. FOUNDATION....................................................0.08 meters
2. SLAB ON SURFACE.............................................0.04 meters
3. SURFACE EXPOSE TO WEATHER.........................0.05 meters
4. BEAMS AND GIRDERS.........................................0.04 meters
5. WALLS...............................................................0.02 meters
D. SIZE OF AGGREGATES TO BE USED
REINFORCES CONCRETE WALLS
BEAMS AND COLUMNS.....................................1/2 TO 3/4
REINFORCED SLAB ON GRADE..........................3/4 TO 1
F. STRUCTURAL STEEL
1. ALL STRUCTURAL STEEL BOTH ANGLES AND STEEL PLATES SHALL CONFORM TO
ASTM A36......fy=227.58 Mpa (33,000 PSI)
2. WELDING ELECTROCODES SHALL BE E60 XX SERIES
3. MACHINE AND ANCHOR BOLTS SHALL CONFORM TO ASTM A-325
(STRUCTURAL 2)
CONSTRUCTION NOTES:
GENERAL
1. THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE
SPECIFICATION THE ARCHITECTURAL, MECHANICAL, ELECTRICAL CIVIL DRAWINGS.
2. THE CONTRACTOR SMALL VERIFY ALL DIMENSIONS AND CONDITION AT THE SITE
WHICH SHALL INCLINE THE LOCATIONS AND DIMENSIONS OF THE OPENINGS,
GROOVES, RIGGERS PIPE SLEEVES, CONDUITS, EMBEDDED OR ATTACHED ITEMS
TO CONCRETE ETC.
3. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT NEW
AND EXISTING CONSTRUCTION THIS SHALL INCLUDE BUT NOT LIMITED TO BRACING
AND SNORTING FOR LOADS IMPOSED DURING CONSTRUCTION.
4. ALL DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALE SHOWN ON PLANS
SECTION AND DETAILS
5. GENERAL NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS
OTHERWISE NOTED
6. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE NOTED
7. ALL BAR DIAMETERS AND SPACING ARE IN MILLIMETERS UNLESS OTHERWISE NOTED
8. ALL FOUNDATIONS SHALL REST ON 50 THK. LEAN CONCRETE UNLESS OTHERWISE
SHOWN OR NOTED
CONCRETE & REINFORCING STEEL
1. CONCRETE COVER TO ALL REINFORCING BARS SHALL BE AS FOLLOWS:
A. CONCRETE CAST AGAINST AND PERMANENTLY
EXPOSED TO EARTH 75mm
B. FORMED SURFACES EXPOSED TO EARTH OR WEATHER
16 BARS OR SMALLER 40mm
OTHER BARS 50mm
C. FORMED SURFACES NOT EXPOSED DIRECTLY TO WEATHER OR EARTH
SLAB AND WALLS 20mm
BEAMS AND COLUMNS 40mm
2. REINFORCING BARS SHALL BE FREE OF RUST, GREASE OR OTHER MATERIALS LIKELY
TO IMPAIR BOND
3. ALL REINFORCING BARS SHALL BE SECURELY PLACED BEFORE POURING CONCRETE
OR APPLYING MORTAR OR GROUT
4. BAR SPACES SHALL BE SECURELY WIRED TOGETHER SPLICES IN REINFORCED
DETAILS, FOR NON-STRUCTURAL WALLS, MASONRY WALLS AND SLAB SPICES SHALL A LAP
A MINIMUM OF 40 BAR DIAMETERS AND SHALL BE STAGGERED WHENEVER POSSIBLE
5. SPICES REQUIRED IN THE REINFORCEMENT OF BEAMS, GIRDERS FRAMING INTO
COLUMNS SHALL NOT BE LOCATED WITHIN THE COLUMNS NOR WITHIN A DISTANCE OF TWICE
THE BEAM/GIRDER FRAMING DEPTH ROOM FROM THE FACE OF THE COLUMN AT LEAST
TWO CLOSED STIR UP TIES SHALL BE PROVIDED AT ALL SPLICES (SEE DETAILS ON SHEET
S.002)
6. LAP SPLICES SHALL BE MADE WITHIN THE CENTER HALF OF COLUMN HEIGHT AND THE
LENGTH SHALL NOT BE LESS THAN 1.3 TIMES THE DEVELOPMENT LENGTH d.
7. SPECIAL TIES / TRANSVERSE HOOP REINFORCEMENTS SHALL BE PROVIDED WITHIN
THE BEAM - COLUMN JOINT
8. FABRICATION / PLACING DRAWINGS
CONTRACTOR SHALL NOT BE SLOWED TO START PLACEMENT / INSTALLATIONS OF
REINFORCING BARS FOR FOOTINGS, BEAMS, WALLS, COLUMNS SLABS, AND OTHER RC
STRUCTURAL ELEMENTS WITHOUT SUBMITTAL AND APPROVAL OF PLACING DRAWINGS.
ONLY THE STRUCTURAL ENGINEER OF RECORD AND/OR THE CHURCH ARE ENGINEER ARE
AUTHORIZED TO APPROVED PLACING DRAWINGS WHICH SHOULD BE SUBMITTED AND
RECEIVED BY EITHER CHURCH ARCHITECTURAL AND ENGINEER OF RECORD AT LEAST
TWO (2) WEEKS PRIOR TO START OF STRUCTURAL CONCRETE WORKS. PLACING DRAWINGS
MUST FOLLOW THE SAME DRAWING AS USED IN THE WORKING DRAWINGS OF THIS PROJECT
AND ONLY CERTIFIED BY THE CONTRACTORS REGISTERED CIVIL OR STRUCTURAL
ENGINEER DEFINITION OF PLACING DRAWINGS. PLACING REINFORCING STEEL THESE
DRAWINGS FOR FABRICATION AND PLACING OF REINFORCING STEEL THESE DRAWING
MUST COMPRISE THE FOLLOWING BAR LISTS, SCHEDULES, BENDING DETAILS, PLACING
DETAILS, PLACING PLANS AND ELEVATIONS, GRADE SIZE SPACING, LENGTH OF EACH
BARS SPLICES AND THEIR LOCATIONS AND ANY NECESSARY ADDITIONAL INFORMATION
THAT MUST BE SUPPLIED BY THE CONTRACTOR CONCERNING FIELD CONDITIONS,
FIELD MEASUREMENTS, CONSTRUCTION JOINTS, AND SEQUENCE OF PLACING
CONCRETES.
STRUCTURAL
1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM WITH THE NINTH EDITION OF
THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) UNLESS OTHERWISE SHOWN
OR NOTED.
2. CONTRACTOR SHALL FURNISH ALL PLATES CUP ANGLES, CONNECTORS, ETC.
REQUIRED FOR THE COMPLETION OF THE STRUCTURE EVEN IN EVERY SUCH ITEMS
IS NOT SHOWN ON THE CONTRACT DRAWINGS.
3. WELDING SHALL BE IN ACCORDANCE WITH THE AMERICAN WELDING SOCIETY CODE
AWS D 1.1 UNLESS INDICATED OTHERWISE WELDING ELECTRODES SHALL BE E70 XX.
4. ALL BOLTS AND THREADED FASTENERS SHALL BE ASTM A 307 UNLESS OTHERWISE
NOTED.
5. ALL ANCHOR BOLTS SHALL BE ASTM A325 UNLESS OTHERWISE NOTED.
MASONRY
1. ALL CONCRETE MANSORY WALLS SHALL BE LAID IN RUNNING BOND (INTERLOCKING
COURSE) WITH FULL MORTAR BEDDING, STACK BONDS SHALL BE USED ONLY WHEN
SPECIFIED
2. ALL CELLS SHALL BE SUPLY FILLED WITH A CONCRETE GROUT
FOUNDATION
1. THE STRUCTURAL ENGINEER OF RECORD UPON NOTIFICATION SHALL CONDUCT A
THOROUGH INSPECTION OF THE FOUNDATION WORKS AFTER ELEVATION FOR
FOOTINGS ARE COMPLETELY AND ANY REQUIRED REINFORCING STEEL IS IN PLACE,
FORM WORKS SHALL BE IN PLACE PRIOR TO INSPECTION. CONCRETE POURING OF
THE FOUNDATION SYSTEM SHALL NOT BE ALLOWED WITHOUT FIRST OBTAINING
WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER OF RECORD.
2. ALL BACKFILL MATERIALS ARE COMPACTED IN LIFTS NOT EXCEEDING 150mm THICK
FILL FOR BACK FILLING SHALL BE COMPOSED OF GRANULAR MATERIALS (LESS
THAN 7% FINES) COMPACTED TO MINIMUM 95% MDD BASED ON ASTM - D - 698
WITH THE QUALITY OF COMPACTION STRICTLY MONITORED BY FIELD DENSITY TEST
(ASTM D - 1556).
3. REFERENCE INVESTIGATION REPORT PREPARED BY BIP STEADFAST GROUND INC
ON MAY 2019.
4. ALL FOOTINGS WERE DESIGNED BASED ON AN ALLOWABLE SOIL BEARING
CAPACITY OF 165 KPA (3450 PSF) AT 240 M BELOW EXISTING GROUND LINE.
THE GEO-TECHNICAL ENGINEER SHOULD VERIFY THAT THE ASSUMED SOIL-BEARING
PRESSURE IS ACTUALLY VALID FOR THE SPECIFIC SITE. THE GEO-TECHNICAL
ENGINEER SHOULD VERIFY ALL SOIL PROFILES TYPES FOR THE EARTHQUAKE LOADS
SUPERIMPOSED ON THE STRUCTURE.
STRAIGHT BARS
DEVELOPMENT IN LENGTH (mm.)
BARS IN DIAMETER f'c = 28.0 MPa fy= 275 MPa
(mm) CASE 1 CASE 2
TOP BARS OTHERS TOP BARS OTHERS
10 370 290 565 435
12 450 350 450 520
16 600 470 200 700
20 750 580 1130 870
25 1160 890 1790 1375
28 1300 1000 2000 1540
32 1480 1140 2290 1760
36 1665 1280 2580 1980
STANDARD HOOKS FOR
STIRRUPS, TIES & HOOPS
BARS IN DEVELOPMENT STRAIGHT STRAIGHT MINIMUM INSIDE
DIAMETER IN LENGTH EXTENSION EXTENSION BEND
(mm.) FOR 90° FOR 90° DIAMETER
(mm)
f'c = 28.0 HOOK cost HOOK cost (mm)
MPa fy= 275 (mm) (mm)
MPa
1O 75 75 65 40
12 75 75 72 48
16 96 96 96 64
2O 24O 72O 72O 72O
25 3OO 75O 75O 75O
HOOKED BARS
BARS IN DEVELOPMENT STRAIGHT STRAIGHT MINIMUM INSIDE
DIAMETER IN LENGTH EXTENSION EXTENSION BEND
(mm.) FOR 90° FOR 180° DIAMETER
(mm)
f'c = 28.0 HOOK cost HOOK cost (mm)
MPa fy= 275 (mm) (mm)
MPa
1O 15O 12O 65 6O
12 15O 144 65 72
16 235 192 65 96
2O 2OO 24O 8O 12O
25 365 3OO 1OO 15O
28 47O 336 112 224
32 465 384 128 256
36 525 432 144 228
LAP SPLICES
f'c = 28.0 MPa fy= 275 MPa
LAP SPLICES LENGTHS (mm)
BARS IN
DIAMETER CASE 1 CASE 2
(mm) TOP BARS OTHERS TOP BARS OTHERS
1O 48O 38O 735 565
12 585 455 885 675
16 78O 675 117O 97O
2O 875 755 147O 113O
25 151O 176O 233O 179O
28 169O 13OO 26OO 2OOO
32 1925 1665 298O 229O