DX Section
DX Section
3 HP to 3500 HP
Standard Features:
* PRECISE CONTROL OF MOTOR SPEED AND TORQUE * BI-DIRECTIONAL FLYCATCHER (CATCH SPINNING MOTOR)
* EASY TO USE, SIMPLE SETUP * POWER DIP RIDE THROUGH
* ENGLISH LANGUAGE DISPLAY - 2 LINE, 32 CHARACTER * KW / KWH METERING
* 50C AMBIENT TEMPERATURE RATING * S CURVE ACCEL / DECEL CONTROL
* SHORT CIRCUIT AND GROUND FAULT PROTECTION * PROGRAMMABLE THRESHOLD DETECTORS
* TOLERATES HIGH INPUT AC LINE VOLTAGES * MULTI FUNCTION I/O
* BUILT IN LINE VOLTAGE SURGE PROTECTION * CUSTOM V/HZ PROGRAMMING
* MOTOR OVERLOAD PROTECTION, MEETS NEC 430 * AUTOLOGGING FAULT HISTORY
* BUILT IN RFI NOISE FILTER * FIXED OR VARIABLE CARRIER FREQUENCY
* HIGH PERFORMANCE PID CONTROL * AUTO RESTART
* 8 PRESET SPEEDS WITH ACCEL / DECEL CONTROL * MUCH, MUCH, MORE
OUTSTANDING FEATURES
High Voltage Ratings Line voltages in the United Smart Power Start We have developed a unique
States are now averaging as high as 500VAC, in Canada starting feature in the Phoenix, which produces a
that figure is 600VAC. Designing a product that doesn’t higher starting torque in the motor, then that achieved
take this fact into consideration will result in a product by line starting. By independently finding the right
that will have power bridge failures or at best, nuisance voltage and frequency to apply to the motor, the
overvoltage tripping. The Phoenix is rated to handle Phoenix creates more starting torque than most Vector
these new voltage averages with ± 10% to spare! controlled drives! This is essential with loads that
require high starting torque and high inertia loads.
Built In Radio Frequency Filter The RFI filter, that
is standard in the Phoenix, reduces noise in the radio 50°C Ambient Temperature We know there are
frequency band which may be generated by the drive. many places in North America where the ambient
The R.F.I. filter has a secondary benefit of protecting temperature can be very high during the summer
the drive from high voltage transients which occur when months. Many products coming frm overseas,
attached to motors with long leads. Many drive however, have lowered their cost by providing a
manufacturers ignore these potential problems that can product that can only handle an ambient temperature
cause radio communications problems in a facility and of 104°F(40°C) in an enclosure. The Phoenix has been
weaken the integrity of the drive. designed to handle the heat with a rating of
122°F(50°C) in a Nema type 1 enclosure.
Input Line Suppression Metal oxide varistors are
included on each unit to absorb line voltage transients, Power Factor Correction DC Reactor If you need
not only phase to phase, but also phase to ground. a drive that is impervious to power line disturbances
Without these suppression devices the drive’s power and doesn’t create noise on the AC power line, then a
semiconductors are exposed to high potential voltages. built in 3% bus reactor is a must. A 3% bus reactor
helps to create close to unity displacement power
Short Circuit Protection If any of the output phases factor. It also lowers harmonic distortion to the power
are shorted together (motor stator failure) or if an line and limits inrush currents to the drive. This results
output phase shorts to ground, the Phoenix will safely in a product that inherently has lower failures and
shut down protecting itself until the short is cleared. eliminates problems with sensitive external equipment.
These types of conditions often occur during installation (Included on all drives 25HP and larger)
when a power lead is nicked and shorts to conduit.
DX2
PHOENIX DX
ENGINEERING DATA
ELECTRICAL ENVIRONMENTAL
Rated Input Voltage: 200-250VAC, 380-500VAC, 500-600VAC. - Ambient Temperature: -10°C to 50°C (14°F to 122°F) without
10% of minimum, + 10% of maximum. derating.
Rated Input Frequency: 45-65 Hz Storage Temperature: -40°C to 70°C (-40°F to 158°F)
Number of Phases: 3 Altitude: Sea level to 3300 Feet [1000m] without
Displacement Power derating.
Factor: .95 or greater. Humidity: 95% relative humidity non-condensing.
Efficiency: 97% or greater at rated current. Vibration: 9.8m/sec2 (1.0G) peak.
Surge Protection: Line Transients to 6000V IEEE C62.41-1991
CONTROL Category B.
Noise Immunity: Showering Arc - 2000V Peak EN50082 - 1, 2.
Control Method: Sine coded PWM with programmable Input R.F.I. Filter: Standard on all models.
carrier. Space Vector control.
Output Voltage: 0 to input voltage. PHYSICAL ATTRIBUTES
Output Frequency Range: 0 to 600 Hz.
Frequency Accuracy: Analog reference: 0.1% of max frequency. Mounting: Wall Mount: Thru-Hole or Panel Mount.
Digital reference: 0.01% of max frequency Nema Rating: Type 1 (IP20) as Standard.
Frequency Resolution: Analog reference: 0.06 Hz at 60 Hz. Type 12 (IP54) Optional.
Digital reference: 0.0005 Hz at 60 Hz. Type 4 (IP65) Optional.
Accel / Decel: Adjustable 0.1 to 3276 sec. Construction: Steel Enclosure (Reduces E.M.I.)
Drive Overload: High Overload Capacity Drives:
-150% of drive rated output for one (1)
AUTOLOGGING FAULT HISTORY
minute.
Ten last faults recorded in order of occurrence.
Normal Overload Capacity Drives:
-120% of drive rated output for one (1)
minute.
INDICATORS
Inverse Time Overload: Programmable for class 10, 20, and 30
L.E.D.’s: Drive Fault, Motor Direction, Drive In Current
protection to comply with N.E.C. Article
Limit, Drive Running, Microprocessor Active.
430
Liquid Crystal Display: Power On, All Parameters, All Fault
Current Limit: Proactive current limit programmable in %
Conditions.
of motor rated current.
Braking Torque: 5 to 20% without modification. Braking
modules available for added braking to
PROTECTIVE FEATURES
150%.
Control Power Ride-Thru: Two (2) seconds (typical) depending on Critical Speed Rejection: Three Points with Bandwidth.
load. Start into a Spinning
Motor: Bi-directional (No Inertia Limits).
CONTROL INPUTS Motor Overload
Protection: Complies with NEC Article 430
Short Circuit Protection
Logic (8): 7-Programmable: Start, Stop, Jog,
Ground Fault Protection
Forward/Reverse, Preset Speeds, Digital
Heatsink Over-
MOP, Hand/Off/Auto, Local/Remote, etc.
Temperature Protection
1-Dedicated: Stop (Enabled)
Programmable Stall
Analog: -10 to +10VDC (10Bit) or 4-20ma (10Bit)
Protection
Programmable.
Over / Under Voltage
Speed Potentiometer: 5K Ohm, 2 Watts (Onboard supply
Protection
available).
DX3
PHOENIX DX
Special Modifications
= No Modifications
RG = Regenerative Drive
CP = Clean Power Drive
Enclosure Type
Motor HP N1 = Nema 1
Voltage Class N12= Nema 12
D2 = 200 to 250VAC ± 10% N4 = Nema 4
D4 = 380 to 500VAC ± 10%
D5 = 500 to 600VAC ± 10%
SIZE 0 D2-0005-N1 3 5 10 16 4 7 12 19 5 8 35
D2-0007-N1 5 7.5 16 22 7 9 19 25 8 10 40
D2-0010-N1 7.5 10 22 28 9 12 25 33 10 14 50
D2-0015-N1 10 15 28 42 12 17 25 36 10 15 60
D2-0020-N1 15 20 42 54 17 22 36 50 15 21 70
D2-0020CT-N1 20 - 54 - 22 - 50 - 21 - 70
SIZE 1 D2-0025-N1 20 25 54 68 22 28 50 61 21 25 90
D2-0030-N1 25 30 68 85 28 35 61 79 25 33 100
D2-0030CT-N1 30 - 80 - 33 - 74 - 31 - 100
SIZE 2 D2-0040-N1 30 40 80 104 33 43 74 96 31 40 150
D2-0050-N1 40 50 104 130 43 54 96 120 40 50 200
D2-0060-N1 50 60 130 163 54 68 120 155 50 64 250
D2-0075-N1 60 75 154 192 60 80 140 186 58 77 300
D2-0100-N1 75 100 192 248 80 103 186 230 77 96 300
D2-0100CT-N1 100 - 248 - 103 - 230 - 96 - 300
6
SIZE 3 D2-0125VT-N1 - 125 - 312 - 130 - 290 - 121
6
D2-0125CT-N1 125 - 312 - 130 - 290 - 121 -
6
D2-0150VT-N1 - 150 - 360 - 150 - 335 - 139
6
D2-0150CT-N1 150 - 360 - 150 - 335 - 139 -
6
D2-0200VT-N1 - 200 - 480 - 200 - 446 - 186
6
D2-0200CT-N1 200 - 480 - 200 - 446 - 186 -
6
D2-250VT-N1 - 250 - 602 - 250 - 560 - 233
6
D2-0250CT-N1 250 - 602 - 250 - 560 - 233 -
1
Horsepower rating based on 230 VAC Motors.
2
High Overload Capacity Drives (CT) produce 150% of Rated Drive Output Current for 1 minute.
3
Normal Overload Capacity Drive (VT) produce 120% of Rated Drive Output Current for 1 minute.
4
Output and Input KVA at nominal 240 VAC.
5
UL Class T, J, and Semiconductor Fuses (preferred): Ferraz Shawmut A50Q, Bussmann FWH.
6
Included as standard.
DX4
PHOENIX DX
DX5
PHOENIX DX
DX6
PHOENIX DX
DX7
PHOENIX DX
Figure 5
Figure 4
Figure 6
DX8
PHOENIX DX
Motor HP
High Normal Approximate
Approximate
Input Voltage Overload Overload Dimensions Figure Mounting
Weight
Capacity Capacity (HxWxD)
(CT) (VT)
3 - 7.5 5 - 10 20.74" x 9.0" x 10.9" 7 Wall 50 Lbs.
10 - 20 15 - 20 20.74" x 9.0" x 10.9" 7 Wall 50 Lbs.
200 - 250 VAC 25 - 30 25 - 30 25" x 11.6" x 11.1" 8 Wall 90 Lbs.
(208/230/240) 40 - 100 40 - 100 32.5" x 20.1" x 13.5" 9 Wall 190 Lbs.
125 - 250 125 - 250 72" x 36" x 23.5" 10 Floor 900 Lbs.
Above 250 Above 250 Consult Factory - - -
5 - 15 7.5 - 20 20.74" x 9.0" x 10.9" 7 Wall 50 Lbs.
20 - 40 25 - 40 20.74" x 9.0" x 10.9" 7 Wall 50 Lbs.
50 - 60 50 - 60 25" x 11.6" x 11.1" 8 Wall 90 Lbs.
380 - 500 VAC
75 - 200 75 - 200 32.5" x 20.1" x 13.5" 9 Wall 190 Lbs.
(380/400/415/480)
250 - 500 250 - 500 72" x 36" x 23.5" 10 Floor 900 Lbs.
600 - 1000 600 - 1000 90" x 72" x 25.5" 12 Floor 1950 Lbs.
Above 1000 Above 1000 Consult Factory - - -
5 - 15 7.5 - 20 20.74" x 9.0" x 10.9" 7 Wall 50 Lbs.
20 - 40 25 - 40 20.74" x 9.0" x 10.9" 7 Wall 50 Lbs.
50 - 75 50 - 75 25" x 11.6" x 11.1" 8 Wall 90 Lbs.
525 - 600 VAC
(525/575/600) 100 - 200 100 - 200 32.5" x 20.1" x 13.5" 9 Wall 190 Lbs.
250 - 600 250 - 600 72" x 36" x 23.5" 10 Floor 900 Lbs.
700 - 1200 700 - 1200 90" x 72" x 25.5" 12 Floor 1950 Lbs.
Above 1200 Above 1200 Consult Factory - - -
DX9
PHOENIX DX
DX10
PHOENIX DX
DX11
PHOENIX DX
Figure 16
Figure 17
DX12