Sample Plumbing Layouts

This document contains a diagram of a plumbing system layout. It shows the connections between various plumbing fixtures like sinks, toilets, and showers to the main drainage and septic systems through pipes of varying diameters. The diagram provides the locations and distances between plumbing components.

Uploaded by

Jennalyn Castelo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (4 votes)
15K views3 pages

Sample Plumbing Layouts

This document contains a diagram of a plumbing system layout. It shows the connections between various plumbing fixtures like sinks, toilets, and showers to the main drainage and septic systems through pipes of varying diameters. The diagram provides the locations and distances between plumbing components.

Uploaded by

Jennalyn Castelo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

8.

00m TO EXISTING DRAINAGE

1/2"Ø PC BLUE
1.00m 3.50m 1.50m 3.00m CATCH BASIN SEPTIC TANK
6"Ø STORM
DRAIN PIPE
VSTR

4"Ø PVC MAIN PIPE LINE


6"Ø STORM
SP HB
DRAIN PIPE
CO

CB CB CB
FD 2"Ø PVC PIPE

FA
CO
WC
WC

3.00m
LV
LAV 1/2"Ø PVC BLUE
4.50m

CO
CO

CB
HB
CB CB

3.00m

10.00m
10.00m

FA

KS

CB HB
KS
F 6"Ø STORM
WP
5.50m

DRAIN PIPE

3/4"Ø PVC MAIN

4.00m
WP

CB
CB CB

2.00m
HB
2"Ø PVC PIPE
1.00m

CB CB
HB HB
1.00m 4.00m

4.00m 4.00m 5.00m

9.00m
ISOMETRIC WC
LEGEND AND SYMBOLS
WATER CLOSET CB CATCH BASIN
NOT TO SCALE CO CLEAN OUT WP WATER PUMP
FD FLOOR DRAIN 4"Ø PVC PIPE
LAV LAVATORY 2"Ø PVC PIPE

PLUMBING LAYOUT PLAN


KS KITCHEN SINK 3/4"Ø OR 1/2"Ø PVC
CONC. MANHOLE VSTR VENT STACK 6"Ø PVC STORM
HB HOSE BIBB DS DOWNSPOUT(3"Ø)
SCALE 1:150MTS 4"Ø PVC TEE FA FAUCET ST SEPTIC TANK
2.70m
4" CONC. SLAB WITH
4"Ø PVC TEE 10mmØ RSB @ 0.15 BW

0.10m
3"Ø PVC DOWN SPOUT 6"Ø PVC PIPE

0.30m
AIR SPACE
WATER LEVEL
10mmØ RSB PLUMBING SPECIFICATIONS

1.50m
0.50m

1.25m
3"Ø DOWN SPOUT 1. ALL WORKS INCLUDED HERE IN SHAKK BE EXCUTED ACCORDING TO THE
0.10m

0.10m

1.70m
DIGESTIVE PROVISIONS OF THE PHILIPPINE PLUMBIBG CODE THE NATIONAL BUILDING

1.10m
LEACHING CHAMBER CODE AND RULES REGULATIONS.
4" THICK CHB WALL 2. COORDINATE THE DRAWING WITH OTHER RELATED DRAWINGS AND
0.50m CHAMBER
0.60m

0.40m

0.60m

0.40m

SPECIFICATION. HE ENGINEERING SHALL BE NOTIFIED IMMEDIATELY FOR ANY


6"Ø DOWN SPOUT DISCREPANCYFOUND THEREIN.
3. ALL PIPES SHALL BE INSTALLED AS INDICATED ANY RELOCATION RREQUIRED

0.20m
FOR PROPER EXECUTION OF OTHER TRADES SHALL BE WITH PRIOR APPROVAL
0.10m

0.10m

4" CONC.
0.70m 1.60m SLAB WITH 0.35m 2-10mmØ CONT. 0.35m
OF ARCHITECT OR ENGINEER.
0.10m 0.40m 0.10m 10mmØ BARS WITH 10mmØ 4. PROPOSED SANITARY SHALL CONFIRM TO THE ACTUAL LOACTION DEPTH AND
5" THICL CHB WALL INVERT ELEVATION OF ALL EXISTING PIPES AND STUCTURE AS VERIFIED BY
0.60m
RSB @ 0.15 0.35m TIES SP. 0.40 O.C
BW THE CONTRACTOR.
PLAN SECTION 5. ALL SLOPES FOR THE HORIZONTAL DRAINAGE SHALL MAINTAIN 2% MINIMUM
PLAN SECTION UNLESS OTHERWISE SPECIFIED.
6. SIZE OF WATER SUPPLY PIPES TO FIXTURES SHALL BE ACCORDING WITH
MANUFACTURER INSTRUCTION.

CATCH BASIN DETAIL DETAIL OF SEPTIC TANK 7. THE CONTRACTOR SHALL VERIFY ALL EXISTING UTIITIES AT SITE AND COORDIN
THE WORK WITH THE SEWER LINE EFFLUENT DISPOSAL POINT AND WATER LINE
SERVICE COONECTING POINT.
SCALE 1:30MTS SCALE 1:50MTS 8. ALL WORKS TO BE DONE SHALL BE THE DIRECTION SUPERVISION OF A
MASTER PLUMBER.
PVC DS PVC DS

PVC DS/FD PVC DS/FD


CO

ST
up up LEGEND AND SYMBOLS PLUMBING SPECIFICATIONS:
PVC DS PVC DS PVC DS PVC DS PVC DS PVC DS PVC DS WP
PVC DS PVC DS WC WATER CLOSET CB CATCH BASIN 1. ALL WORKS INCLUDED HERE IN SHAKK BE EXCUTED ACCORDING TO THE
PVC DS PVC DS PROVISIONS OF THE PHILIPPINE PLUMBIBG CODE THE NATIONAL BUILDING
CO CLEAN OUT WP WATER PUMP CODE AND RULES REGULATIONS.
2. COORDINATE THE DRAWING WITH OTHER RELATED DRAWINGS AND
FD FLOOR DRAIN 4"Ø PVC PIPE
SPECIFICATION. HE ENGINEERING SHALL BE NOTIFIED IMMEDIATELY FOR ANY
KS VSTR LAV LAVATORY 2"Ø PVC PIPE DISCREPANCYFOUND THEREIN.
RISER UP RISER UP
3. ALL PIPES SHALL BE INSTALLED AS INDICATED ANY RELOCATION RREQUIRED
FA
KS KITCHEN SINK 3/4"Ø OR 1/2"Ø PVC FOR PROPER EXECUTION OF OTHER TRADES SHALL BE WITH PRIOR APPROVAL
OF ARCHITECT OR ENGINEER.
PVC DS VSTR VENT STACK 6"Ø PVC STORM 4. PROPOSED SANITARY SHALL CONFIRM TO THE ACTUAL LOACTION DEPTH AND
RISER UP PVC DS VSTR
PVC DS PVC DS PVC DS
INVERT ELEVATION OF ALL EXISTING PIPES AND STUCTURE AS VERIFIED BY
FD HB HOSE BIBB DS DOWNSPOUT(3"Ø) THE CONTRACTOR.
RISER UP CO PVC DS
PVC DS PVC DS
SHO LAV
PVC DS/FD 5. ALL SLOPES FOR THE HORIZONTAL DRAINAGE SHALL MAINTAIN 2% MINIMUM
FA FAUCET ST SEPTIC TANK
DOWN UNLESS OTHERWISE SPECIFIED.
BTD
DOWN WC 6. SIZE OF WATER SUPPLY PIPES TO FIXTURES SHALL BE ACCORDING WITH
CO
MANUFACTURER INSTRUCTION.
LAV CO
WC CO 7. THE CONTRACTOR SHALL VERIFY ALL EXISTING UTIITIES AT SITE AND COORDIN
THE WORK WITH THE SEWER LINE EFFLUENT DISPOSAL POINT AND WATER LINE
PVC DS DOWN
FD WC LAV SHO PVC DS SERVICE COONECTING POINT.
DOWN FD
PVC DS SHO
PVC DS
8. ALL WORKS TO BE DONE SHALL BE THE DIRECTION SUPERVISION OF A
PVC DS
PVC DS
MASTER PLUMBER.
PVC DS PVC DS PVC DS/FD

LAV

WC
FD PVC DS
CO SHO PVC DS PVC DS PVC DS PVC DS/FD
PVC DS PVC DS/FD
PVC DS PVC DS PVC DS
PVC DS PVC DS
PVC DS

PVC DS
PVC DS/FD
PVC DS/FD PVC DS/FD
PVC DS
PVC DS PVC DS
PVC DS PVC DS

PVC DS

PVC DS PVC DS
PVC DS

HB HB

SECOND FLOOR PLAN ROOF DECK


GROUND FLOOR PLAN

PLUMBING LAYOUT
SCALE 1:150MTS
2.70m

4"Ø PVC TEE

6" PVC PIPE


3"Ø PVC DOWN SPOUT
1.50m

1.25m

0.50m

0.10m

0.50m
0.60m

0.40m

4" CONC. SLAB WITH 10mmØ RSB @ 0.15 BW


0.70m 1.60m
5" THICK CHB WALL

PLAN
0.10m

CONC. MANHOLE 0.10m 0.40m 0.10m

4"Ø PVC TEE 0.60m

4" CONC. SLAB WITH 10mmØ RSB @ 0.15 BW


0.10m

PLAN
AIR SPACE 6"Ø DOWN SPOUT
0.30m

4" THICK CHB WALL


WATER LEVEL 10mmØ RSB
3"Ø DOWN SPOUT
0.10m

DIGESTIVE
1.70m

LEACHING
CHAMBER CHAMBER
1.10m

0.60m

0.40m
0.20m

0.10m

0.35m 0.35m 0.35m

2-10mmØ CONT. BARS WITH 10mmØ TIES SP. 0.40 O.C


SECTION
SECTION ISOMETRIC LAYOUT
DETAILS OF SEPTIC TANK CATCH BASIN DETAILS NOT T TO SCALE

SCALE 1:50MTS SCALE 1:20MTS