Construction of Water Cooled Central AC plant of capacity 3200 TR ( 4nos.
centrifugal Chillers each of capacity 800 TR) in IIT Kanpur
BMS I/O SUMMARY
Qty AI AO DI DO
[Link]. DESCRIPTION Field Devices
A Water Cooled Screw Chillers 4
1 Chillers - Status
2 Chiller Enable/Disable
3 Chiller - Lockout/fault
4 Chiller /Condensor water flow status
5 Leaving Chilled Water Temperature
6 Entering Chilled Water Temperature
7 Leaving Condensor Water Temperature The bidder shall provide the Software
8 Entering Condensor Water Temperature Integration with Chiller Plant Manager (CPM)
9 Compressor Percent RLA along with providing a daily report of minimum
10 Evaporator Refrigerant Pressure of these paramaters to show the operating
11 Condensor Refrigerant Pressure condition of each chiller.
12 Compressor Discharge Refrigerant Temperature
13 Evaporator Refrigerant Temperature
14 Condensor Refrigerant Temperature
15 Chilled Water Setpoint
16 Current Limit Setpoint
8 4 Motorised Butterfly Valve & Actuator to be supplied &
17 Chiller Out Butterfly Valve Control & Status Installed by the lowest bidder as per tender BOQ
8 4 Motorised Butterfly Valve & Actuator to be supplied &
18 Condensor Out Butterfly ValveControl & Status Installed by the lowest bidder as per tender BOQ
Immersion Temperature sensor-SITC of socket shall be
1
19 Common CHW header Supply Temp in the lowest bidder scope
Immersion Temperature sensor-SITC of socket shall be
1
20 Condensor water header Supply temp. in the lowest bidder scope
Immersion Temperature sensor-SITC of socket shall be
1
21 Common CHW header Return Temp in the lowest bidder scope
Immersion Temperature sensor-SITC of socket shall be
1
22 Condensor water header Return temp. in the lowest bidder scope
23 Ambient Temperature/RH 2 Outside temp + Rh Sensor
24 Chilled Water Header Flow Monitoring (350mm) 1 Inline type ElectroMagnetic Flow Meter (4-20mA/0-10V)
B Chilled Water Primary Pumps 5
1 Pump Start/Stop 5 Relay Output from DDC to the Panel
2 Pump Run Status 5 Currrent Relay (4-20mA)
3 Pump Auto Manual switch Status 5 Potential Free Contact from DDC to the Panel
C Secondary Variable Pumps (VFD) 5
1 Condensor Pump Start/Stop 5 Relay Output from DDC to the Panel
2 Condensor Pump Run Status
Soft Integration through Modbus
3 Condensor Pump Auto Manual switch Status
4 Pump Logic Controller
D Condenser Pumps 5
1 Condensor Pump Start/Stop 5 Relay Output from DDC to the Panel
2 Condensor Pump Run Status 5 Currrent Relay (4-20mA)
3 Condensor Pump Auto Manual switch Status 5 Potential Free Contact from DDC to the Panel
E Tertiary Variable Pumps (VFD) (6 sets) Each set 18
pump will consists of 3 pumps.
1 Condensor Pump Start/Stop 18 Relay Output from DDC to the Panel
2 Condensor Pump Run Status
Soft Integration through Modbus
3 Condensor Pump Auto Manual switch Status
F Cooling Tower (1 Fan each) 8
Construction of Water Cooled Central AC plant of capacity 3200 TR ( 4nos. centrifugal Chillers each of capacity 800 TR) in IIT Kanpur
Qty AI AO DI DO
[Link]. DESCRIPTION Field Devices
1 Cooling Tower On/Off 8 Relay Output from DDC to the Panel
2 Cooling Tower Fan Status 8 Current Relay
3 Cooling Tower Manual Operation Status 8 Potential Free Contact from DDC to the Panel
4 Cooling Tower Sump Low Water Level 8 Single Level switch
Cooling Tower "In & Out" Valves ON/Off Command & Motorised Butterfly Valve& Actuator to be supplied &
16 8
5 Status Installed by the lowest bidder
6 Cooling Tower return Header Temp 1 Immersion Temperature sensor
G Expansion Tanks 1
Motorised Butterfly Valve& Actuator to be supplied &
1 Tank "In & Out" Valves ON/Off Command & Status 4 2
Installed by the lowest bidder
2 Tank return Header Temp 1 Immersion Temperature sensor
H Dirt Seperator 1
1 Dirt Seperator O/ Off Command 1 Relay Output from DDC to the Panel
2 Dirt Seperator Run Status 1 Current Relay
3 Dirt Seperator Manual Operation Status 1 Potential Free Contact from DDC to the Panel
I Water softening & Filteration plant 1
1 Water softener O/ Off Command 1 Relay Output from DDC to the Panel
2 Make water Pump On/Off command 1 1 Current Relay
3 Make water Pump Run Status 1
4 Make up water level status 1 Potential Free Contact from DDC to the Panel
J HT PANEL 1
HT Main panel breaker Status 1 Wiring from DDC to Potential free contact
Incoming Voltage Monitoring (Digital Volt meter) 1 Voltage Transducer and field wiring
Trivector/Multi Function Meter Soft Integration 20 points per Energy meter
K LT PANEL 1
LT Incoming Breaker Status 1 Wiring from DDC to Potential free contact
LT Outgoing Breaker Status 1 Wiring from DDC to Potential free contact
LT Incoming MFM / MDC with RS 485 Port Soft Integration
MFM Metering RS 485 Port. - All Outgoing From LT
Panel (Except Capacitor & Fire fighting) Soft Integration
L DG SET 1
DG Run Status (On / Off) 1 Relay output @ 2 amp, 230 V & wiring from DG MCC
DG Battery Monitoring 1 Voltage Transducer and field wiring
Earth Fault Alarm 1 Wiring from DDC to Potential free contact
Over Load Alarm 1 Wiring from DDC to Potential free contact
Oil Tank High/Low Level Monitoring 1 Flameproof level switch by BMS vendor
M Buildings Integration with the BMS
Aerospace Engineering Building
Engineering Core Building
Science & Technology Park Building The new BMS system shall be capable of integrating with the
Research Park Building upcoming these buildings BMS System on Bacnet/IP/Modbus.
(Total soft Points :5000)
Earthscience Engineering Building
Centre for Engineering Building
2 nos. other Buildings.
TOTAL IO POINTS 51 11 0 94 60
Note: Provision of atleast 1000 soft points in addition to the above have to be made or any future requirements