Climatix™
Climatix I/O extension module with 14 I/Os
POL955.60
This product offers the following features:
● Power supply AC 24 V or DC 24 V via the controller
● 8 universal I/Os for analog or digital signals (configurable inputs/outputs)
● 4 relay outputs (NO contacts, three of them with high inrush capacity)
● 2 analog outputs (DC 0…10 V)
● Peripheral bus interface for local/remote extension I/Os
A6V11626142_en--_b Smart Infrastructure
2019-07-12
Use
POL955.60/STN is a versatile Climatix I/O extension module that can be connected to any
type of Climatix POL6XX controller. Its high flexibility of universal inputs meets the
requirements of the compact air handling unit industry plus those of other air conditioning
applications and other applications. It is part of the Climatix product range (refer to Data
Sheet 3900 and Mounting Instructions M3910).
Climatix product range
Installation concept
Ordering
Climatix I/O extension module 14 I/Os 12 pcs POL955.60/STN
Connector set (spring cage, cable top entry) 12 pcs POL095.56/STD
Connector set (screw, cable side entry) 12 pcs POL095.55/STD
Accessories
Connector set (spring cage, cable top entry) POL095.56/STD
1 x Phoenix FKCT 2,5/2-ST GY7035
1 x Phoenix FKCT 2,5/3-ST GY7035
3 x Phoenix FKCT 2,5/6-ST GY7035
1 x Phoenix ZEC 1,0 / 4-LPV-3,5 GY35AUC2CI1
Connector set (screw, cable side entry) POL095.55/STD
1 x Phoenix MVSTBW 2,5/2-ST GY7035
1 x Phoenix MVSTBW 2,5/3-ST GY7035
3 x Phoenix MVSTBW 2,5/6-ST GY7035
1 x Phoenix ZEC 1,0 / 4-LPV-3,5 GY35AUC2CI1
Board-to-wire connector POL002.43/STD
2 x Phoenix ZEC 1,0 / 4-ST-3,5 GY35AUC1R1,4 50 pcs
Technical data
Power supply
Operating voltage AC 24 V ±20%; DC 24 V ±10%
Frequency 45…65 Hz
Max. AC-Current consumption 600 mA at AC 24 V
Max. DC-Current consumption 340 mA at DC 24 V
Connection Peripheral bus
2
Siemens A6V11626142_en--_b
Smart Infrastructure 2019-07-12
Power distribution
Max. pass through current 3.4 A at AC 24V
3.66 A at DC 24 V
Relay outputs Q1...Q3 (with high inrush capacity)
Relay: type, contact Monostable, NO contact
Contact ratings
Switching voltage AC 24…230 V (-20%, +10%)
Nominal current (res. / ind.) AC 4 A / 1 A (cosφ ≥ 0.6)
Inrush current Max. 80 A / max. 100 µs
External overcurrent protection Fuse slow max. 10 A or
Circuit breaker max. 13 A
Operations Min. 10,000
Minimum switching load 30 mA / 19 V respectively 10 mA / 200 V
Connecting Circulator Pumps to relay output
Relay output Q4 (T4)
Relay: type, contact Monostable, NO contact
Contact rating
Switching voltage AC 24…230 V (-20%, +10%)
Nominal current (res. / ind.) AC 4 A / 1 A (cosφ ≥ 0.6)
Inrush current Max. 10 A / max. 10 ms
External overcurrent protection Fuse slow max. 10 A or
Circuit breaker max. 13 A
Operations Min. 10,000
Minimum switching load 30 mA / 19 V respectively 10 mA / 200 V
3
Siemens A6V11626142_en--_b
Smart Infrastructure 2019-07-12
Connecting indicator lamps to relay output
Universal I/Os
X1…X8
Configurable By software
Reference potential Terminals ┴
Contact voltage Max. DC 24 V (SELV)
Over voltage protection Up to 40 V
Analog inputs (X1…X8)
Ni1000
Sensor current 1.4 mA
Resolution 0.1 K
Accuracy within the range -50…150 °C 0.5 K
Pt1000
Sensor current 1.8 mA
Resolution 0.1 K
Accuracy within the range -50…150 °C 0.5 K
NTC 10k (B25/85 = 3977K)
Sensor current 140 μA
Temperature range Accuracy Resolution
-50…-26 °C 1K 0.2 K
-25…74 °C 0.5 K 0.1 K
75…99 °C 1K 0.3 K
100…124 °C 3K 1.0 K
4
Siemens A6V11626142_en--_b
Smart Infrastructure 2019-07-12
125…150 °C 6K 2.5 K
NTC 100k (B25/85 = 3977K)
Sensor current 140 μA
Temperature range Accuracy Resolution
-25…-11 °C 3K 0.2 K
-10…9 °C 1K 0.1 K
10…99 °C 0.5 K 0.1 K
100…150 °C 1K 0.2 K
0...2,500 Ω
Sensor current 1.8 mA
Resolution 1Ω
Accuracy 4Ω
Connecting a ratiometric sensor to universal I/Os
Connecting NTC to universal I/Os
Analog inputs (X1…X8)
DC 0...10 V input
Resolution 1 mV
Accuracy at 0 V 2 mV
Accuracy at 5 V 25 mV
Accuracy at 10 V 50 mV
Input resistance 100 kΩ
DC 0/4…20 mA input
5
Siemens A6V11626142_en--_b
Smart Infrastructure 2019-07-12
Resolution 1 μA
Accuracy at 4 V 25 μA
Accuracy at 12 V 70 μA
Accuracy at 20 V 120 μA
Impedance of DC 0/4…20 mA input Typ. 450 Ω
Voltage input DC 0…10 V
Current input 4…20 mA
Digital inputs (X1…X8)
0/1 digital signal (binary) For potential-free contacts
Sampling voltage / current DC 24 V / 8 mA
Contact resistance Max. 200 Ω (closed)
Min. 50 kΩ (open)
Delay 10 ms
Pulse frequency Max. 30 Hz
Connecting floating contacts to universal I/O
6
Siemens A6V11626142_en--_b
Smart Infrastructure 2019-07-12
Analog outputs (X1…X8)
DC 0...10 V output
Resolution 11 mV
Accuracy at 0 V 66 mV
Accuracy at 5 V 95 mV
Accuracy at 10 V 124 mV
Output current 1 mA (short-circuit-proof)
DC 4…20 mA output
Resolution 22 μA
Accuracy at 4 V 150 μA
Accuracy at 12 V 196 μA
Accuracy at 20 V 243 μA
Connecting voltage output and current output to universal I/O
Analog outputs
Y1...Y2
DC 0…10 V output
Resolution 11 mV
Accuracy at 0 V 66 mV
Accuracy at 5 V 95 mV
Accuracy at 10 V 124 mV
Output current 1 mA
7
Siemens A6V11626142_en--_b
Smart Infrastructure 2019-07-12
Connecting voltage output and offboard relays to analog output
Connection terminals
Optional plugs for IO signals Phoenix FKCVW 2,5 / x-ST
Phoenix FKCT 2,5 / x-ST
Phoenix MVSTBW 2,5 / x-ST
Solid wire 0.5…2.5 mm²
Stranded wire (twisted and with ferrule) 0.5…1.5 mm²
Cable lengths In compliance with load, local regulations and
installation documents
Peripheral bus
Power supply Ueff = AC 24 V ±20%, fmain = 45...65 Hz
or U = DC 24 V ±10%, no internal fuse
Bus termination selectable (680 Ω / 120 Ω +1 nF / 680 Ω )
Solid wire 0.2…1.0 mm²
Stranded wire (twisted and with ferrule) 0.2…1.0 mm²
Cable lengths Max. 30 m
Addressing DIP switch 1…5
Termination DIP switch 6
Ambient conditions and protection classification
Operation IEC 60721-3-3 class 3K5
Temperature -40...70 °C
Humidity <90% r.h. (non-condensing)
Atmospheric pressure Min. 700 hPa, corresponding to max. 3,000 m above
sea level
Transport IEC 60721-3-2 class 2K3/2K4
Temperature -40...70 °C
Humidity <95% r.h. (non-condensing)
Atmospheric pressure Min. 260 hPa, corresponding to max. 10,000 m above
sea level
8
Siemens A6V11626142_en--_b
Smart Infrastructure 2019-07-12
Ambient conditions and protection classification
Protection
Degree of protection IP20 (EN 60529)
Safety class Suitable for use in plants with safety class II
Standards, directives and approvals
Product standard EN 60730-1
Automatic electronic controls for household and similar
use.
Electromagnetic compatibility For use in residential, commerce, light-industrial and
(applications) industrial environments.
EU conformity (CE) CB1T3920xx *)
RCM conformity CB1T3909en_C1
Listings UL916, UL873 [Link]
CSA Class 4812 [Link]
Environmental compatibility The product environmental declaration CB1E3920en
contains data on environmentally compatible product
design and assessments (RoHS compliance, materials
composition, packaging, environmental benefit,
disposal).
*) The document can be downloaded from [Link]
General Data
Dimensions of controller 108 x 110 x 75 mm
Weight excl. packaging 183.5 g
Base Plastic, pigeon-blue RAL 5014
Housing Plastic, light-grey RAL 7035
Status of LEDs
The status of BSP LED is defined as follows:
Status Meaning
Red flashing at 2 Hz BSP error or slave address error
Green on BSP running
The status of BUS LED is defined as follows:
Status Meaning
Red on Communication error
Green on Communication running
Orange on Communication running but parameter not successfully
configured
DIP switch
The extension module is equipped with DIP switch to communicate with the controller.
Switch 1, 2, 3, 4, and 5 are configurable to set the slave address, while switch 6 serves as
9
Siemens A6V11626142_en--_b
Smart Infrastructure 2019-07-12
peripheral bus termination. If the extension module works as the termination in the network,
switch 6 must be set to ON.
The order of bit is from 5 to 1. The lowest bit is 5 while the highest bit is 1. Max. 31 slave
addresses can be configured as follows:
DIP Switch configuration of Extension Module
No. Schematics No. Schematics No. Switch 5 No. Schematics
1 9 17 25
2 10 18 26
3 11 19 27
4 12 20 28
5 13 21 29
6 14 22 30
7 15 23 31
8 16 24
NOTICE
The same address of extension module must be set respectively in the application program
of the controller. 0 cannot be set as the slave address.
10
Siemens A6V11626142_en--_b
Smart Infrastructure 2019-07-12
Notes
Engineering notes
NOTICE
To ensure protection against accidental contact with relay connections carrying voltages
above 42 Veff, the extension module must be installed in an enclosure (preferably a control
panel). It must be impossible to open the enclosure without the aid of a key or tool.
AC 230 V cables must be double-insulated against safety extra low-voltage (SELV) cables
Disposal
The device is considered an electronics device for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic garbage.
● Dispose of the device through channels provided for this purpose.
● Comply with all local and currently applicable laws and regulations.
Dimensions (in mm)
Right side Left side
11
Siemens A6V11626142_en--_b
Smart Infrastructure 2019-07-12
Issued by © Siemens Switzerland Ltd, 2019
Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724 2424
[Link]/buildingtechnologies
12
Siemens A6V11626142_en--_b
Smart Infrastructure 2019-07-12
Document ID A6V11626142_en--_b
Edition 2019-07-12