Cooling Infrastructure Solution
Room, Row and Chiller
Close-Coupled Air-conditioners
Technical Chillers
Room Air-conditioners
Dynamic
Load Control
Raised Modular Floor
[Link]
One Stop Complete
Cooling Solution
• Amico • InRow Direct Expansion
• Leonardo • InRow Chilled Water
• Leonardo Max • Thermal Containment
• HXCV
• Unisplit
• Fan Wall
• InRack direct expansion • Technical Chillers
• Read Door Heat • Free Cooling Chillers
Exchanger and Economizers
• Liquid cooling
[Link]
Table of contents
Precision Air Conditioning units - Amico & Leonardo Page 04 - 05
Variable Speed Precision AC units-IDAV Page 06 - 07
Ceiling / Wall Mount Precision AC unit- Unisplit Page 08 - 09
Rack Mounted Room Cooling Page 10 - 11
Precision Technical cooling Chillers Page 12 - 13
Precision Inrow Cooling Page 14 - 15
Non raised floor precision Cooing unit - Fan Wall Page 16 - 17
[Link]
UniflairAir Cooled
Precision Cooling
Amico & Leonardo
(5-280kW)
Standard Features
1 High Efficeincy Tandem scroll compressor
2 Higher part load efficiency due to Tandem arrangement
3 Electronic Expansion Valve standard on leonardo units
4 Energy efficient EC fans
5 Hydrphilic coating on evaporator coil
6 Stainless Steel drain tray with insultation
7 Variable capacity steam humidifier
8 Multistage AL strip heaters
9 Liquid Receiver, LLSV, NRV as safety components
10 Micr-Vee high efficiency EU4 filters
11 CAREL Controller
12 Refrigerant R-410A / R407C
Life is On | Schneider Electric 04
Air cooled / Water cooled direct expansion Precisionunits with direct drive AC motor
Model SDA-SUA 0151 0251 0351 0501 0601
Height mm 1740 1740 1740 1740 1740
Width mm 550 550 850 1200 1200
Depth mm 450 450 450 450 450
Weight kg 130 135 185 260 265
Airflow m3/h 1600 1600 3000 5000 5000
Total cooling capacity kW* 5.7 8.0 12.5 16.1 18.9
Sensible cooling capacity kW* 5.4 6.4 11.0 16.1 17.0
Refrigerant circuits 1 1 1 1 1
Compressors 1 1 1 1 1
Electric supply voltage 400 V / 3 PH / 50 Hz
(*) Based on 24°C / 50% RH, Condensing temperature=45°C with R407C
Air cooled / Water cooled direct expansion Precision units with EC motor
Model TDAV-TUAV / LDAV 611 811 721 921 1011 1021 1321 1422 1622 1822 2222 2242 2522 2542 2842 3342 3542
Height mm 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960
Width mm 1010 1010 1310 1310 1010 1310 1720 2185 2185 2185 2582 2582 2582 2582 2582 2582 2600
Depth mm 750 750 865 865 750 865 865 865 865 865 865 865 865 865 865 865 900
Weight kg 400 430 430 440 450 450 575 700 715 720 910 920 930 940 1040 1100 1130
Airflow m3/h 6000 6000 8500 8500 8500 8500 12500 16000 16000 16000 23500 23500 23500 23500 23500 23500 27000
Total cooling capacity kW* 19.9 28.1 27.2 33.2 37.0 36.9 44.7 54.1 61.6 68.9 73.0 79.7 92.6 88.9 100.0 114.2 125
Sensible cooling capacity kW* 18.8 28.1 27.2 31.7 35.0 34.5 44.7 54.1 61.0 61.1 73.0 78.5 86.0 84.2 93.7 100.3 118
Refrigerant circuits 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2
Compressors 1 1 2 2 1 2 2 2 2 2 2 4 2 4 4 4 4
Electric supply voltage 400 V / 3 PH / 50 Hz
(*) Based on 24°C / 50% RH, Condensing temperature=45°C with R-410A
Chilled Water Based Precision Air conditioning units with direct drive AC motor
Model SDA-SUA 0200 0250 0300 0400 0600
Height mm 1740 1740 1740 1740 1740
Width mm 550 700 850 850 1200
Depth mm 450 450 450 450 450
Weight kg 100 115 150 155 220
Airflow m3/h 1600 1900 2050 3020 5000
Total cooling capacity kW* 7.5 9.6 10.6 13.6 22.1
Sensible cooling capacity kW* 6.3 8.0 8.6 11.7 19.0
Electric supply voltage 230 v / 1 ph / 50 Hz
(*) Based on 24°C / 50% RH, Chilled water at 7/12°C
Chilled Water Based Precision Air conditioning units with direct drive EC motor
Model TDCV-TUCV 600 700 1000 1200 1700 2000 2500 2700 3400 4000 4300 4600 HXCV5500 HXCV6200 HXCV6800
Height mm 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960 2510 2510 2510 2510
Width mm 1010 1010 1310 1310 1720 2185 2185 2185 2582 2582 2582 2582 2582 3200 3400
Depth mm 750 750 865 865 865 865 865 865 865 865 865 865 1100 1100 1100
Weight kg 280 285 310 315 400 450 460 500 700 740 820 900 1050 1100 1200
Airflow m3/h 6000 6000 10000 10000 14000 19000 19000 19000 25000 25000 30000 34000 35000 48000 55000
Total cooling capacity kW* 21.1 24.6 33.4 42.2 59.1 69.3 88.4 98 110.8 125.6 168.7 185 200 250 280
Sensible cooling capacity kW* 21.1 24.6 32.7 40.0 57.7 67.0 82.2 88.8 103.8 113.6 155 175 200 250 280
Electric supply voltage 400 V / 3 PH / 50 Hz
(*) Based on 24°C / 50% RH, Chilled water at 10/15°C
Life is On | Schneider Electric 05
Uniflair Variable Speed Air Cooled
Precision Cooling IDAV (15-135kW)
Standard Features
1 High Efficeincy DC Inverter scroll compressor
2 Higher part load efficiency due to variable speed
compressor
3 Electronic Expansion Valve
4 Energy efficient EC fans
5 Hydrphilic coating on evaporator coil
6 Stainless Steel drain tray with insultation
7 Variable capacity steam humidifier
8 Multistage AL strip heaters
9 Liquid Receiver, Oil separator, LLSV, NRV as safety
components
10 Micr-Vee high efficiency EU4 filters
11 CAREL Controller
12 Refrigerant R-410A
Brushless VSD scroll
compressor
• Discharge temperature control
• High energy efficiency at partial load
• Low starting current
• No sliding contacts
[Link]
IDAV
Air cooled / Water cooled direct expansion Variable Speed DC Invereter Compressor Precision units
Model IDAV-IUAV 511 811 1011 1311 1811 2522 3022 3822
Height mm 2100 2100 2100 2100 2150 2150 2150 2150
Width mm 1010 1010 1010 1200 1777 2082 2650 2650
Depth mm 900 900 900 900 900 900 900 900
Weight kg 450 480 500 520 650 750 950 1100
Airflow m3/h 5000 8000 11000 11000 18000 18000 23000 29000
Total cooling capacity kW* 18 30 37 45 64 88 100 130
Sensible cooling capacity kW* 17.5 29 36 43 64 88 100 130
Refrigerant circuits 1 1 1 1 1 2 2 2
Compressors 1 1 1 1 1 2 2 2
Electric supply voltage 400 V / 3 PH / 50 Hz
(*) Based on 24°C / 50% RH, Condensing temperature=45°C with R-410A
Main configurable options
Power supply Fan module configurations (IDAV models)
• Single power supply • Fan module with bottom supply
• Double power supply with automatic commutation to • Fan module with rear supply
provide redundancy and ensure a constant power supply • Fan module with front supply
• Fan module with front and side supply
• Fan module with fully open supply
Construction options
• Downflow units (IDAV): top air return with bottom or front Air-cooled remote condensers
discharge (without /small additional floor stands)
• Vertical or horizontal installation
• Upflow units (IUAV): front or bottom air return with top
• Fan speed regulator works exclusively via Modbus
discharge
commands
• Underfloor units (IDAV): top air return with bottom supply
• Coil protection treatment for aggressive ambient (optional)
with multiple fan module configurations
• Low temperature versions to operate down to 40°C
• Standard, cleanable or low conductibility humidifier
(optional)
(cooling + humidification configuration)
• Standard electrical heaters with extended fins, complete
Additional accessories
with double safety thermostat and manual resetting
• High efficiency air filters
• EU4 (standard) or EU5 air filters with or without motorized
damper • Motorized damper
• Automatic Floor Pressurization System through Active Floor • Water leak detector
Control (AFC) • Room air temperature / humidity sensor
Life is On | Schneider Electric 07
Unisplit UCA-UCF - UWA-UWF
range 5,9 - 14,5 kW (Ceiling & Wall Mount Precision AC units)
MRA
Q.E.
Internal Unit
(UCA-UCF)
External Unit External Unit
(MRA) (MRA) Internal Unit
(UWA-UWF)
Evaporator sections are equipped with: Power supply:
• Microprocessor control • 230V/ 1/ 50 Hz or 400V/3+N/50Hz (standard, according to the model)
• EU4 filter (optional) • Main power supply + UPS 48VDC (evaporator DC-fan/s) (Optional)
Condensing units are equipped with:
• Scroll compressor
• Modulating fan/s speed control
• Amico
• Leonardo
• Leonardo Max
• HXCV
• Unisplit
• Fan Wall
[Link]
Unisplit
Air cooled direct expansion Ceiling/Wall Mount Precision units
Model Ceiling UCA/UCF Wall UWA/UWF
0341 0481 0341 0481
Airflow m3/h 1850 3900 1850 3900
Total cooling capacity kW* 7.1 14.5 7.1 14.5
Sensible cooling capacity kW* 7.1 14.5 7.1 14.5
Indoor unit
Height mm 330 410 2100 2150
Width mm 950 1150 1200 1777
Depth mm 1050 1300 900 900
Power supply 230/1/50 230/1/50
Outdoor unit
Height mm 610 1230 2100 2150
Width mm 850 1200 1200 1777
Depth mm 345 480 900 900
Power supply 230/1/50 400/3/50 230/1/50 400/3/50
(*) Based on 26°C / 45% RH, ambient temperature=35°C with R407C
Life is On | Schneider Electric 09
Compact, intelligent cooling
for your Edge Data Center
Uniflair Rack Mounted
Room Cooling
3.5kW, 5U, direct expansion split solution
[Link]/cooling
Technical specifications
INDOOR UNIT 50 Hz CE version
Commercial References ACRMD4KI-1
Total Cooling Capacity 3.6 kW (12,300 BTU/hr)
Sensible Cooling Capacity* 3.5 kW (11,900 BTU/hr)
Rated Power Input 200-240 V~, 1 Ph, 50 Hz
Rated Air Volume 700 m³/h (410 SCFM)
Number of Fans 1
IDU Fan Input Power 0.43 kW
Size of Liquid Pipe/Air Pipe Connection 9.52/12.7 mm (0.37/0.50 in.)
Energy Efficiency Ratio (EER) 2.5
Sound Pressure Level 62.5 dB(A)
OUTDOOR UNIT 50 Hz CE version
Commercial References ACRMD4KI-2 (precharged) ACRMD4KI-3 (non-precharged)
Heat Exchange 6.3 kW
Rated Air Volume 1700 m³/h (1000 SCFM)
Input Power 1.00 kW
Number of Fans 1
Number of Compressors 1
Sound Pressure Level 51.1 dB(A)
Main features - Internal unit
1 Variable Speed DC Fan
Designed for 24x7 mission critical operation
and high airflow output. Quickly responds to
heat loads and lowers energy consumption.
2 Electronic Expansion Valve
1
4 Quick and accurate response to control the
2 refrigerant flow once the IT load changes to ensure
rack always stays at constant cold temperature.
3 Front mounting flanges
5 Discrete, easy installation with any rack.
3
4 Upward air plenum
Ensures even cooling distribution to the entire height
of the rack.
5 Optional embedded user interface
Color touchscreen display ensures easy temperature
control and system monitoring.
Main features - External unit
1
1 Compact design
Condensing unit can be placed almost
anywhere: on the ground, on a wall, or even on
top of the rack.
2 Robust design
2 Built for 24x7 mission critical operation.
Life is On | Schneider Electric 11
Chillers designed for technical
cooling applications in data centers,
buildings, and industrial processes
5 - 2000 kW
[Link]
Air cooled Variable Capacity/Speed Screw Compressor Precision Chiller Units
Model XRAC 1812 2212 2512 2812 3212 3612 4212 4812 5622 6422
Height mm 5305 6735 6735 6735 9110 9110 10540 10540 11955 13385
Width mm 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200
Depth mm 2531 2531 2531 2531 2531 2531 2531 2531 2551 2551
Stepless Version - R134a
Cooling capacity kW* 601,8 758,4 807,4 954,3 1170 1283,5 1509 1656,3 1876 2085,6
Power consumption kW* 146 180,8 196,1 236,5 280,2 317,1 376 414,1 457,8 501,9
EER 4,12 4,19 4,12 4,04 4,18 4,05 4,01 4,00 4,10 4,16
Hybrid Version - R134a
Cooling capacity kW* 613,3 750 835 963,6 1187,9 1298,4 1527,7 1678,4 1850,1 2063,5
Power consumption kW* 150,5 179,5 204,4 244,6 290,3 325 389,7 428,7 439,5 486,9
EER 4,08 4,18 4,09 3,94 4,09 4,00 3,92 3,92 4,21 4,24
Full VSD Version - R134a
Cooling capacity kW* 624,8 741,5 862,8 972,7 1206,4 1313,4 1546,2 1700,6 1823,8 2041
Power consumption kW* 155,1 178,2 212,7 252,7 300,5 333 403,4 443,3 421,3 472
EER 4,03 4,16 4,06 3,85 4,01 3,94 3,83 3,84 4,33 4,32
Stepless Version - R1234ze
Cooling capacity kW* 490,7 620 657,9 768,6 956,3 1053,6 1257 1342 1501,2 1678,8
Power consumption kW* 107,4 131,7 142,8 170,5 198,1 225,2 272,5 295,7 331,7 365,5
EER 4,57 4,71 4,61 4,51 4,83 4,68 4,61 4,54 4,53 4,59
Hybrid Version - R1234ze
Cooling capacity kW* 498,9 608,6 677,1 781,4 965,1 1055,6 1271,6 1365,5 1481 1658
Power consumption kW* 110,9 131,8 148,9 176,4 207,4 230,2 280,5 307,9 319,7 355,9
EER 4,50 4,62 4,55 4,43 4,65 4,59 4,53 4,43 4,63 4,66
Full VSD Version - R1234ze
Cooling capacity kW* 507,3 597,5 696,8 797,6 974 1057,7 1286,6 1388,9 1461,1 1637,6
Power consumption kW* 114,4 131,9 155 182,4 216,8 235,2 288,6 320,2 307,8 346,5
EER 4,43 4,53 4,50 4,36 4,49 4,50 4,46 4,34 4,75 4,73
*Inlet/outlet evaporator temp. 30/20°C, 0% ethylene glycol
• Outdoor temp. 35°C
• Units equipped with EC fans
• Basic noise version
Above mentioned range is also available in free cooling version and other refrigerants R513A & R1234yf as well
Life is On | Schneider Electric 13
Intelligently controlled
high-performance
close-coupled cooling
Uniflair InRow Cooling
[Link]
Inrow
Air cooled / Chilled water based Inrow Precision units
Type Air Cooled Chilled Water Dual Fluid
Model ACRD101 ACRC301 ACRD602 ACRC300 ACRC600 ACRH301
Airflow m3/h 3800 5800 6900 7140 10200 5250
Cooling capacity 10 kW to 35kW 20kW to 70kW 27 kW
Indoor unit
Height mm 1991 1991 1991 1991 1991 1991
Width mm 300 300 600 300 600 300
Depth mm 1095 1095 1070 1095 1070 1095
Close-coupled architecture
Flexible, reliable, standardized solutions
• Modular unit design allows a pod/zone expansion as IT
needs change and grow
• Greenfield/brownfield environments Uniflair InRow
cooling products
• Raised/slab floor
are designed by
• Room neutral combining cutting-
• Non-conventional IT spaces/office space edge technology
• Worldwide availability
with extensive tests
for energy
efficiency and
Predictable solution for the unpredictable environment continuous
A close-coupled cooling architecture moves the cooling unit availability.
from a traditional perimeter placement to a location that is in
the row or above the IT racks. Energy savings,
complete reliability,
The Uniflair InRow unit targets the heat that is generated by the Initial deployment and total flexibility
IT equipment by pulling the hot air directly from the hot aisle guarantee TCO
where the heat is generated. The unit removes the heat and reduction.
supplies cool air into the cold aisle/environment, which is the
source of cool air for the IT equipment.
25 kW
Cooling units
per rack when
combined with
Close coupling keeps the hot air in thermal
the hot aisle containment system
Expansion
+80%
of additional
capacity* by
capturing the heat
Uniflair InRow cooling with EcoAisle
at the source
containment maximizes efficiency
*29.4 °C (85 °F) vs.
and predictability 22.2 °C (72 °F)
return air temperature
Final deployment
Life is On | Schneider Electric 15
Uniflair Cooling solutions
for IT rooms without a raised floor
Application guide to customized fan wall & hyper front flow
chilled water cooling solutions
Non-raised Floor Solutions
FXCV
FXCV FWCV
Frontal Hyper Front
Discharge Flow Chilled
Chilled Water Water Room
Room Cooling Cooling
[Link]
FXCV MODEL - InCorridor 4000 5000 6000 6500 6800
HT - High temperature version
Airflow m3/h 32000 40000 45000 53000 56000
Net sensible cooling capacity kw 140 174 200 231 244
HT - High temperature extended
Airflow m3/h 32000 40000 45000 53000 56000
Net sensible cooling capacity kw 132 164 188 220 230
EC Fans nr 2 3 3 4 4
DIMENSIONS
Width mm 2170 2580 3110 3405 3405
Depth mm 1070 1070 1070 1070 1070
Height mm 3150 3150 3150 3150 3270
RAT: 37°C, 30%R.H.
Humidity: 30%;
ESP: 20 Pa; EU4 filter
HT: Water temperature inlet-outlet: 20-30°C, 0% glycol
HTE: Water temperature inlet-outlet: 20-30°C, 0% glycol
FWCV MODEL 0065L 0085L 0100L 0120L 0135L
Airflow m3/h 62150 74750 110000 118000 138000
Net sensible cooling capacity kW 234 286 415 432 507
EC Fans nr 4 8 8 12 12
Width mm 2400 3600 3600 4000 4000
Depth mm 1600 1600 1600 1600 1600
Height mm 4000 4000 4000 4000 4000
RAT: 37°C, 30%R.H.
Humidity: 30%;
ESP: 20 Pa; EU4 filter
Life is On | Schneider Electric 17
To learn more about Schneider Electric cooling solutions visit
[Link]/cooling
Schneider Electric IT Business India Private Ltd
3 & 188/3, Jigani Rd, Bommasandra Industrial Area,
Bengaluru, Karnataka 560105
© 2022 Schneider Electric. All Rights Reserved. Life Is On Schneider Electric is a trademark and the property of Schneider Electric SE, its subsidiaries and affiliated companies.
• 998-20862752_GMA